OIDNameAccessStatusDescription
1.3.6.1.4.1.186Nodetoshiba
1.3.6.1.4.1.186.1Nodeequ
1.3.6.1.4.1.186.1.19NodeequUPS
1.3.6.1.4.1.186.1.19.2NodeticUPS
1.3.6.1.4.1.186.1.19.2.5Nodermti4
1.3.6.1.4.1.186.1.19.2.5.1NodeupsG9000-G2020
1.3.6.1.4.1.186.1.19.2.5.1.1NodeupsIdent
1.3.6.1.4.1.186.1.19.2.5.1.1NodeupsTrapFaultAlarm: One or more fault/status alarm(s) reported.
1.3.6.1.4.1.186.1.19.2.5.1.1.1ScalarupsIdentManufacturerread-onlymandatoryThe name of the UPS manufacturer.
1.3.6.1.4.1.186.1.19.2.5.1.1.2ScalarupsIdentTypeformread-onlymandatoryThe UPS Model designation.
1.3.6.1.4.1.186.1.19.2.5.1.1.3ScalarupsIdentUPSFirmwareVersionread-onlymandatoryThe UPS firmware version.
1.3.6.1.4.1.186.1.19.2.5.1.1.4ScalarupsIdentSysNameread-writemandatoryA string identifying the UPS. This object is set by the administrator.
1.3.6.1.4.1.186.1.19.2.5.1.1.5ScalarupsIdentAttachedDevicesread-writemandatoryA string identifying the devices attached to the output(s) of the UPS. This object is set by the administrator.
1.3.6.1.4.1.186.1.19.2.5.1.2NodeupsInput
1.3.6.1.4.1.186.1.19.2.5.1.2NodeupsTrapFaultClearAlarm Clear: One or more fault/status reported.
1.3.6.1.4.1.186.1.19.2.5.1.2.1ScalarupsInputNumOfPhasesread-onlymandatoryNumber of input lines. This data is used by upsInputNumLines.
1.3.6.1.4.1.186.1.19.2.5.1.2.2ScalarupsInputLLVoltageABread-onlymandatoryThe input line to line voltage for AB in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.2.3ScalarupsInputLLVoltageBCread-onlymandatoryThe input line to line voltage for BC in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.2.4ScalarupsInputLLVoltageCAread-onlymandatoryThe input line to line voltage for CA in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.2.5ScalarupsInputLLVoltagePercentABread-onlymandatoryThe input line to line voltage percent for AB.
1.3.6.1.4.1.186.1.19.2.5.1.2.6ScalarupsInputLLVoltagePercentBCread-onlymandatoryThe input line to line voltage percent for BC.
1.3.6.1.4.1.186.1.19.2.5.1.2.7ScalarupsInputLLVoltagePercentCAread-onlymandatoryThe input line to line voltage percent for CA.
1.3.6.1.4.1.186.1.19.2.5.1.2.8ScalarupsInputCurrentPhaseAread-onlymandatoryThe input phase current for Phase A.
1.3.6.1.4.1.186.1.19.2.5.1.2.9ScalarupsInputCurrentPhaseBread-onlymandatoryThe input phase current unit for Phase B.
1.3.6.1.4.1.186.1.19.2.5.1.2.10ScalarupsInputCurrentPhaseCread-onlymandatoryThe input phase current unit for Phase C.
1.3.6.1.4.1.186.1.19.2.5.1.2.11ScalarupsInputFrequencyread-onlymandatoryThe input frequency unit 0.1 Hertz.
1.3.6.1.4.1.186.1.19.2.5.1.2.12ScalarupsInputActivePowerAread-onlymandatoryThe magnitude of the present input true power for phase A.
1.3.6.1.4.1.186.1.19.2.5.1.2.13ScalarupsInputActivePowerBread-onlymandatoryThe magnitude of the present input true power for phase B.
1.3.6.1.4.1.186.1.19.2.5.1.2.14ScalarupsInputActivePowerCread-onlymandatoryThe magnitude of the present input true power for phase C.
1.3.6.1.4.1.186.1.19.2.5.1.2.15ScalarupsInputTotalActivePowerread-onlymandatoryThe magnitude of the total input true power.
1.3.6.1.4.1.186.1.19.2.5.1.2.16ScalarupsInputRatedLLVoltageread-onlymandatoryThe input line to line rated voltage in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.3NodeupsOutput
1.3.6.1.4.1.186.1.19.2.5.1.3NodeupsTrapOnBatteryInfo: The UPS is on Battery Mode.
1.3.6.1.4.1.186.1.19.2.5.1.3.1ScalarupsOutputSourceread-onlymandatoryThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.186.1.19.2.5.1.3.2ScalarupsOutputNumOfPhasesread-onlymandatoryThe number of output lines utilized in this device.
1.3.6.1.4.1.186.1.19.2.5.1.3.3ScalarupsOutputLLVoltageABread-onlymandatoryThe output line to line voltage for AB in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.3.4ScalarupsOutputLLVoltageBCread-onlymandatoryThe output line to line voltage for BC in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.3.5ScalarupsOutputLLVoltageCAread-onlymandatoryThe output line to line voltage for CA in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.3.6ScalarupsOutputCurrentPhaseAread-onlymandatoryThe Output phase current for phase A in amps.
1.3.6.1.4.1.186.1.19.2.5.1.3.7ScalarupsOutputCurrentPhaseBread-onlymandatoryThe Output phase current for phase B in amps.
1.3.6.1.4.1.186.1.19.2.5.1.3.8ScalarupsOutputCurrentPhaseCread-onlymandatoryThe Output phase current for phase C in amps.
1.3.6.1.4.1.186.1.19.2.5.1.3.9ScalarupsOutputFrequencyread-onlymandatoryThe Output Frequency for phase A in 1/10 of HZ.
1.3.6.1.4.1.186.1.19.2.5.1.3.10ScalarupsOutputCurrentPercentAread-onlymandatoryThe output current for phase A in percent.
1.3.6.1.4.1.186.1.19.2.5.1.3.11ScalarupsOutputCurrentPercentBread-onlymandatoryThe output current for phase B in percent.
1.3.6.1.4.1.186.1.19.2.5.1.3.12ScalarupsOutputCurrentPercentCread-onlymandatoryThe output current for phase C in percent.
1.3.6.1.4.1.186.1.19.2.5.1.3.13ScalarupsOutputTotalActivePowerread-onlymandatoryThe output active power.
1.3.6.1.4.1.186.1.19.2.5.1.3.14ScalarupsOutputTotalActivePowerPercentread-onlymandatoryThe output active power in percent.
1.3.6.1.4.1.186.1.19.2.5.1.3.15ScalarupsOutputPowerFactorread-onlymandatoryThe UPS output power factor.
1.3.6.1.4.1.186.1.19.2.5.1.3.16ScalarupsOutputRatedActivePowerread-onlymandatoryThe output rated active power for the UPS.
1.3.6.1.4.1.186.1.19.2.5.1.3.17ScalarupsOutputRatedApparentPowerread-onlymandatoryThe output rated apparent power for the UPS.
1.3.6.1.4.1.186.1.19.2.5.1.3.18ScalarupsOutputRatedLLVoltageread-onlymandatoryThe output rated line to line voltage for the UPS.
1.3.6.1.4.1.186.1.19.2.5.1.4NodeupsBypass
1.3.6.1.4.1.186.1.19.2.5.1.4NodeupsTrapOnBatteryClearInfo Clear: The UPS is on Battery Mode.
1.3.6.1.4.1.186.1.19.2.5.1.4.1ScalarupsBypassNumOfPhasesread-onlymandatoryThe number of bypass lines utilized.
1.3.6.1.4.1.186.1.19.2.5.1.4.2ScalarupsBypassLLVoltageABread-onlymandatoryThe Bypass line to line voltage for AB in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.4.3ScalarupsBypassLLVoltageBCread-onlymandatoryThe Bypass line to line voltage for BC in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.4.4ScalarupsBypassLLVoltageCAread-onlymandatoryThe Bypass line to line voltage for CA in RMS volts.
1.3.6.1.4.1.186.1.19.2.5.1.4.5ScalarupsBypassFrequencyread-onlymandatoryThe Bypass frequency in 0.1 Hertz.
1.3.6.1.4.1.186.1.19.2.5.1.5NodeupsBattery
1.3.6.1.4.1.186.1.19.2.5.1.5NodeupsTrapBatteryLowWarning: Battery Low Voltage.
1.3.6.1.4.1.186.1.19.2.5.1.5.1ScalarupsBatteryStatusread-onlymandatoryThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run time sufficient to handle the…
1.3.6.1.4.1.186.1.19.2.5.1.5.2ScalarupsElapsedTimeOnBatteryPowerread-onlymandatoryIf the unit is on battery power, the elapsed time since the UPS on battery power, or the time since the network management subsystem was last restarted, whiche…
1.3.6.1.4.1.186.1.19.2.5.1.5.3ScalarupsEstimatedBatteryRuntimeread-onlymandatoryAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.186.1.19.2.5.1.5.4ScalarupsBatteryVoltageread-onlymandatoryThe battery voltage DC.
1.3.6.1.4.1.186.1.19.2.5.1.5.5ScalarupsBatteryVoltagePercentread-onlymandatoryBattery voltage in percent.
1.3.6.1.4.1.186.1.19.2.5.1.5.6ScalarupsBatteryEstimatedChargeread-onlymandatoryAn estimate of the charge to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost a…
1.3.6.1.4.1.186.1.19.2.5.1.5.7ScalarupsBatteryDischargeCurrentread-onlymandatoryThe present battery discharge Current in percent.
1.3.6.1.4.1.186.1.19.2.5.1.5.8ScalarupsBatteryChargeCurrentread-onlymandatoryThe present battery charge Current in percent.
1.3.6.1.4.1.186.1.19.2.5.1.5.9ScalarupsBatteryModelread-writemandatoryThe Battery manufacturer.
1.3.6.1.4.1.186.1.19.2.5.1.5.10ScalarupsBatteryInSeriesread-writemandatoryThe Battery rated holding time in minutes.
1.3.6.1.4.1.186.1.19.2.5.1.5.11ScalarupsBatteryNumStringsread-writemandatoryThe Battery rated holding time in minutes.
1.3.6.1.4.1.186.1.19.2.5.1.5.12ScalarupsBatteryRatedAmpereHourread-writemandatoryThe Battery rated holding time in minutes.
1.3.6.1.4.1.186.1.19.2.5.1.5.13ScalarupsBatteryRatedBackupTimeread-writemandatoryThe Battery rated holding time in minutes.
1.3.6.1.4.1.186.1.19.2.5.1.5.14ScalarupsBatteryInstallationDateread-onlymandatoryThe battery install date.
1.3.6.1.4.1.186.1.19.2.5.1.6NodeupsAlarm
1.3.6.1.4.1.186.1.19.2.5.1.6NodeupsTrapBatteryLowClearWarning Clear: Battery Low Voltage.
1.3.6.1.4.1.186.1.19.2.5.1.6.1ScalarupsAlarmsPresentread-onlymandatoryThe present number of active alarm conditions.
1.3.6.1.4.1.186.1.19.2.5.1.6.2TableupsAlarmTablenot-accessiblemandatoryA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.186.1.19.2.5.1.6.2.1RowupsAlarmEntrynot-accessiblemandatoryAn entry containing information applicable to a particular alarm.
1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.1ColumnupsAlarmIdnot-accessiblemandatoryA unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.2ColumnupsAlarmDescrread-onlymandatoryA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.3ColumnupsAlarmTimeread-onlymandatoryThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag…
1.3.6.1.4.1.186.1.19.2.5.1.6.3NodeupsWellKnownAlarms
1.3.6.1.4.1.186.1.19.2.5.1.6.3.1ScalarupsAlarmFaultread-onlymandatoryFault: A UPS fault/Alarm condition exists.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.2ScalarupsAlarmOnBatteryread-onlymandatoryInfo: The UPS is on Battery mode; it is supplying output power from its batteries.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.3ScalarupsAlarmBatteryLowread-onlymandatoryWarning: The battery level is low. It has dropped to less than 90% of its nominal value. Continued operation in Battery Mode will deplete Batteries and result …
1.3.6.1.4.1.186.1.19.2.5.1.6.3.4ScalarupsAlarmBatteryDepletedread-onlymandatoryWarning: UPS contains depleted batteries, it will be unable to support critical loads. Shut down excess equipment to reduce Load.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.5ScalarupsAlarmBatteryOverheatread-onlymandatoryFault: Detection of over temperature at the batteries.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.6ScalarupsAlarmBatteryVoltageAbnormalread-onlymandatoryFault: Battery voltage is abnormality.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.7ScalarupsAlarmUPSOverheatread-onlymandatoryFault: The UPS is overheating (warning is given when the internal temperature reaches and exceeds 50?C rise @ 40?C ambient). Check to see if the ambient temper…
1.3.6.1.4.1.186.1.19.2.5.1.6.3.8ScalarupsAlarmPowerFailureread-onlymandatoryInfo: Power Failure.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.9ScalarupsAlarmUPSOverloadread-onlymandatoryFault: The UPS is overloaded. UPS will switch to bypass operation or shut down if no action is taken. Shut down excess equipment to reduce Load.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.10ScalarupsAlarmUserDefinedOverloadWarningread-onlymandatoryWarning: The inverter output load % is greater than the user defined overload set point (default: 110%).
1.3.6.1.4.1.186.1.19.2.5.1.6.3.11ScalarupsAlarmOnBypassread-onlymandatoryWarning: The UPS is in Stop (Bypass) mode.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.12ScalarupsAlarmOutputOffread-onlymandatoryInfo: The UPS output is off.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.13ScalarupsAlarmAsyncOperationread-onlymandatoryWarning: Async Operation
1.3.6.1.4.1.186.1.19.2.5.1.6.3.14ScalarupsAlarmDCBusOverCurrentread-onlymandatoryFault: UPS is reporting a DC bus overcurrent condition. Contact your Toshiba authorized service center for examination of a DCOC fault.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.15ScalarupsAlarmDCBusOverVoltageread-onlymandatoryFault: UPS is reporting a DC bus overvoltage condition. Contact your Toshiba authorized service center for examination of a DCOV fault.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.16ScalarupsAlarmDCBusUnderVoltageread-onlymandatoryFault: UPS is reporting a DC bus undervoltage condition. Contact your Toshiba authorized service center for examination of a DCUV fault.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.17ScalarupsAlarmDCBusImbalancedread-onlymandatoryFault: The DC imbalanced alarm detection.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.18ScalarupsAlarmOutputUnderVoltageread-onlymandatoryFault: UPS is reporting an output undervoltage condition. Contact your Toshiba authorized service center for examination of a INVUV fault.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.19ScalarupsAlarmOutputOverVoltageread-onlymandatoryFault: UPS is reporting an output overvoltage condition. Contact your Toshiba authorized service center for examination of a INVOV fault.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.20ScalarupsAlarmInverterOverloadread-onlymandatoryFault: Short time over-current has been detected.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.21ScalarupsAlarmInverterOvercurrentread-onlymandatoryFault: Detection of inverter overcurrent.
1.3.6.1.4.1.186.1.19.2.5.1.6.3.22ScalarupsAlarmRemotEyeCommErrorread-onlymandatoryWarning: Communication error between the RemotEye 4 and the UPS.
1.3.6.1.4.1.186.1.19.2.5.1.7NodeupsConfig
1.3.6.1.4.1.186.1.19.2.5.1.7NodeupsTrapBatteryDepletedWarning: UPS contains depleted batteries, it will be unable to support critical loads. Shutdown excess equipment to reduce load.
1.3.6.1.4.1.186.1.19.2.5.1.7.1ScalarupsConfigModelIDStringread-onlymandatoryUPS Model ID string. This string contains codes for the UPS series,input voltage, output voltage, output VA, and addition option.
1.3.6.1.4.1.186.1.19.2.5.1.7.2ScalarupsConfigUPSFirmwareVersionread-onlymandatoryThe G9000 software version.
1.3.6.1.4.1.186.1.19.2.5.1.7.3ScalarupsConfigInputNumOfPhasesread-onlymandatoryNumber of input lines. This data is used by upsInputNumLines.
1.3.6.1.4.1.186.1.19.2.5.1.7.4ScalarupsConfigRatedInputFrequencyread-onlymandatoryThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is no…
1.3.6.1.4.1.186.1.19.2.5.1.7.5ScalarupsConfigRatedInputLLVoltageread-writemandatoryThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a v…
1.3.6.1.4.1.186.1.19.2.5.1.7.6ScalarupsConfigRatedInputPowerFactorread-onlymandatoryUNITS are in hundredths. For 0.95 = 95.
1.3.6.1.4.1.186.1.19.2.5.1.7.7ScalarupsConfigOutputNumOfPhasesread-onlymandatoryNumber of output lines. This data is used by upsOutputNumLines.
1.3.6.1.4.1.186.1.19.2.5.1.7.8ScalarupsConfigRatedOutputFrequencyread-onlymandatoryThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is n…
1.3.6.1.4.1.186.1.19.2.5.1.7.9ScalarupsConfigRatedOutputLLVoltageread-writemandatoryThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a …
1.3.6.1.4.1.186.1.19.2.5.1.7.10ScalarupsConfigRatedOutputApperentPowerread-onlymandatoryThe magnitude of the nominal Volt-Amp rating.
1.3.6.1.4.1.186.1.19.2.5.1.7.11ScalarupsConfigRatedOutputActivePowerread-onlymandatoryThe magnitude of the nominal true power rating.
1.3.6.1.4.1.186.1.19.2.5.1.7.12ScalarupsConfigRatedOutputPowerFactorread-onlymandatoryUNITS are in hundredths. For 0.70 = 70.
1.3.6.1.4.1.186.1.19.2.5.1.7.13ScalarupsConfigBypassNumOfPhasesread-onlymandatoryThe number of bypass lines utilized.
1.3.6.1.4.1.186.1.19.2.5.1.7.14ScalarupsConfigLowVoltageTransferPointread-writemandatoryThe minimum input line voltage allowed before the UPS system transfers to battery backup.
1.3.6.1.4.1.186.1.19.2.5.1.7.15ScalarupsConfigHighVoltageTransferPointread-writemandatoryThe maximum line voltage allowed before the UPS system transfers to battery backup.
1.3.6.1.4.1.186.1.19.2.5.1.7.16ScalarupsConfigBatteryInSeriesread-writemandatoryThe number of batteries in each string connected in series.
1.3.6.1.4.1.186.1.19.2.5.1.7.17ScalarupsConfigBatteryNumStringsread-writemandatoryThe number of parallel battery strings.
1.3.6.1.4.1.186.1.19.2.5.1.7.18ScalarupsConfigRatedBatteryVoltageread-writemandatoryRated voltage of a single battery.
1.3.6.1.4.1.186.1.19.2.5.1.7.19ScalarupsConfigRatedBatteryAmpereHourread-writemandatoryThe rated battery in ampere hour.
1.3.6.1.4.1.186.1.19.2.5.1.7.20ScalarupsConfigBatteryModelread-writemandatoryThe manufacturer of the battery.
1.3.6.1.4.1.186.1.19.2.5.1.7.21ScalarupsConfigBatteryRatedBackupTimeread-writemandatoryThe rated duration batteries can hold when unit is in backup mode with full load.
1.3.6.1.4.1.186.1.19.2.5.1.7.22ScalarupsConfigUserDefinedOverloadSetPointread-writemandatoryThe maximum output load % defined by the user.
1.3.6.1.4.1.186.1.19.2.5.1.7.23ScalarupsConfigBatteryInstallationDateread-writemandatoryThe battery install date.
1.3.6.1.4.1.186.1.19.2.5.1.7.24ScalarupsConfigSysNameread-writemandatoryA string identifying the UPS. This object is set by the administrator.
1.3.6.1.4.1.186.1.19.2.5.1.7.25ScalarupsConfigAttachedDevicesread-writemandatoryA string identifying the devices attached to the output(s) of the UPS. This object is set by the administrator.
1.3.6.1.4.1.186.1.19.2.5.1.7.26ScalarupsConfigPasswordread-writemandatoryPassword.
1.3.6.1.4.1.186.1.19.2.5.1.8NodeupsTime
1.3.6.1.4.1.186.1.19.2.5.1.8NodeupsTrapBatteryDepletedClearWarning Clear: UPS contains depleted batteries, it will be unable to support critical loads. Shutdown excess equipment to reduce load..
1.3.6.1.4.1.186.1.19.2.5.1.8.1ScalarupsTimeRealDateread-writemandatoryPresent date: year-month-date-day of the week.
1.3.6.1.4.1.186.1.19.2.5.1.8.2ScalarupsTimeRealTimeread-writemandatoryPresent time (military format): hour-minute-second. For example,2:00pm would be 14:00:00.
1.3.6.1.4.1.186.1.19.2.5.1.9NodeupsTrap
1.3.6.1.4.1.186.1.19.2.5.1.9NodeupsTrapBatteryOverheatFault: Battery Overheat.
1.3.6.1.4.1.186.1.19.2.5.1.10NodeupsTrapBatteryOverheatClearFault Clear: Battery Overheat.
1.3.6.1.4.1.186.1.19.2.5.1.11NodeupsTrapBatteryVoltageAbnormalFault: Battery Voltage Abnormal. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.12NodeupsTrapBatteryVoltageAbnormalClearFault Clear: Battery Voltage Abnormal. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.13NodeupsTrapUPSOverheatFault: UPS Overheat, heatsinks temperature exceeds thermal settings. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.14NodeupsTrapUPSOverheatClearFault Clear: UPS Overheat, heatsinks temperature exceeds thermal settings. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.15NodeupsTrapPowerFailureInfo: Power Failure.
1.3.6.1.4.1.186.1.19.2.5.1.16NodeupsTrapPowerFailureClearInfo Clear: PowerFailure.
1.3.6.1.4.1.186.1.19.2.5.1.17NodeupsTrapUPSOverloadFault: UPS Overload (OL), the output load exceeds the rated current. Decrease load.
1.3.6.1.4.1.186.1.19.2.5.1.18NodeupsTrapUPSOverloadClearFault Clear: UPS Overload (OL), the output load exceeds the rated current. Decrease load.
1.3.6.1.4.1.186.1.19.2.5.1.19NodeupsTrapUserDefinedOverloadWarningWarning: The inverter output load % is greater than the user defined overload set point (default: 110%).
1.3.6.1.4.1.186.1.19.2.5.1.20NodeupsTrapUserDefinedOverloadWarningClearWarning Clear: The inverter output load % is greater than the user defined overload set point (default: 110%).
1.3.6.1.4.1.186.1.19.2.5.1.21NodeupsTrapOnBypassWarning:On Bypass.
1.3.6.1.4.1.186.1.19.2.5.1.22NodeupsTrapOnBypassClearWarning Clear: On Bypass.
1.3.6.1.4.1.186.1.19.2.5.1.23NodeupsTrapOutputOffInfo: The UPS output is off.
1.3.6.1.4.1.186.1.19.2.5.1.24NodeupsTrapOutputOffClearInfo Clear: The UPS output is off.
1.3.6.1.4.1.186.1.19.2.5.1.25NodeupsTrapAsyncOperationWarning: Inverter Synchronous.
1.3.6.1.4.1.186.1.19.2.5.1.26NodeupsTrapAsyncOperationClearWarning Clear: Inverter Synchronous.
1.3.6.1.4.1.186.1.19.2.5.1.27NodeupsTrapDCBusOverCurrentFault: DC Overcurrent (DCOC). Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.28NodeupsTrapDCBusOverCurrentClearFault Clear: DC Overcurrent (DCOC). Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.29NodeupsTrapDCBusOverVoltageFault: DC Overvoltage (DCOV). Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.30NodeupsTrapDCBusOverVoltageClearFault Clear: DC Overvoltage (DCOV). Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.31NodeupsTrapDCBusUnderVoltageFault: DC Undervoltage (DCUV). Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.32NodeupsTrapDCBusUnderVoltageClearFault Clear: DC Undervoltage (DCUV). Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.33NodeupsTrapDCBusImbalanceFault: DC Unbalance. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.34NodeupsTrapDCBusImbalanceClearFault Clear: DC Unbalance. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.35NodeupsTrapOutputUnderVoltageFault: Output Undervoltage. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.36NodeupsTrapOutputUnderVoltageClearFault Clear: Output Undervoltage. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.37NodeupsTrapOutputOverVoltageFault: Output Overvoltage (VLOV). Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.38NodeupsTrapOutputOverVoltageClearFault Clear: Output Overvoltage (VLOV). Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.39NodeupsTrapInverterOverloadFault: UPS Overload, short time over-current has been detected during On-Line operation. Decrease Load.
1.3.6.1.4.1.186.1.19.2.5.1.40NodeupsTrapInverterOverloadClearFault Clear: UPS Overload, short time over-current has been detected during On-Line operation. Decrease Load.
1.3.6.1.4.1.186.1.19.2.5.1.41NodeupsTrapInverterOvercurrentFault: Inverter Overcurrent. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.42NodeupsTrapInverterOvercurrentClearFault Clear: Inverter Overcurrent. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.5.1.43NodeupsTrapRemotEyeCommErrorWarning: RemotEye UPS communication error.
1.3.6.1.4.1.186.1.19.2.5.1.44NodeupsTrapRemotEyeCommErrorClearWarning Clear:RemotEye UPS communication error.