TIC-RMTI4-G9000-G2020-MIB
174 objects
No module-level DESCRIPTION found.
Imported Objects
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.186 | Nodetoshiba | |||
| 1.3.6.1.4.1.186.1 | Nodeequ | |||
| 1.3.6.1.4.1.186.1.19 | NodeequUPS | |||
| 1.3.6.1.4.1.186.1.19.2 | NodeticUPS | |||
| 1.3.6.1.4.1.186.1.19.2.5 | Nodermti4 | |||
| 1.3.6.1.4.1.186.1.19.2.5.1 | NodeupsG9000-G2020 | |||
| 1.3.6.1.4.1.186.1.19.2.5.1.1 | NodeupsIdent | |||
| 1.3.6.1.4.1.186.1.19.2.5.1.1 | NodeupsTrapFault | Alarm: One or more fault/status alarm(s) reported. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.1.1 | ScalarupsIdentManufacturer | read-only | mandatory | The name of the UPS manufacturer. |
| 1.3.6.1.4.1.186.1.19.2.5.1.1.2 | ScalarupsIdentTypeform | read-only | mandatory | The UPS Model designation. |
| 1.3.6.1.4.1.186.1.19.2.5.1.1.3 | ScalarupsIdentUPSFirmwareVersion | read-only | mandatory | The UPS firmware version. |
| 1.3.6.1.4.1.186.1.19.2.5.1.1.4 | ScalarupsIdentSysName | read-write | mandatory | A string identifying the UPS. This object is set by the administrator. |
| 1.3.6.1.4.1.186.1.19.2.5.1.1.5 | ScalarupsIdentAttachedDevices | read-write | mandatory | A string identifying the devices attached to the output(s) of the UPS. This object is set by the administrator. |
| 1.3.6.1.4.1.186.1.19.2.5.1.2 | NodeupsInput | |||
| 1.3.6.1.4.1.186.1.19.2.5.1.2 | NodeupsTrapFaultClear | Alarm Clear: One or more fault/status reported. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.2.1 | ScalarupsInputNumOfPhases | read-only | mandatory | Number of input lines. This data is used by upsInputNumLines. |
| 1.3.6.1.4.1.186.1.19.2.5.1.2.2 | ScalarupsInputLLVoltageAB | read-only | mandatory | The input line to line voltage for AB in RMS volts. |
| 1.3.6.1.4.1.186.1.19.2.5.1.2.3 | ScalarupsInputLLVoltageBC | read-only | mandatory | The input line to line voltage for BC in RMS volts. |
| 1.3.6.1.4.1.186.1.19.2.5.1.2.4 | ScalarupsInputLLVoltageCA | read-only | mandatory | The input line to line voltage for CA in RMS volts. |
| 1.3.6.1.4.1.186.1.19.2.5.1.2.5 | ScalarupsInputLLVoltagePercentAB | read-only | mandatory | The input line to line voltage percent for AB. |
| 1.3.6.1.4.1.186.1.19.2.5.1.2.6 | ScalarupsInputLLVoltagePercentBC | read-only | mandatory | The input line to line voltage percent for BC. |
| 1.3.6.1.4.1.186.1.19.2.5.1.2.7 | ScalarupsInputLLVoltagePercentCA | read-only | mandatory | The input line to line voltage percent for CA. |
| 1.3.6.1.4.1.186.1.19.2.5.1.2.8 | ScalarupsInputCurrentPhaseA | read-only | mandatory | The input phase current for Phase A. |
| 1.3.6.1.4.1.186.1.19.2.5.1.2.9 | ScalarupsInputCurrentPhaseB | read-only | mandatory | The input phase current unit for Phase B. |
| 1.3.6.1.4.1.186.1.19.2.5.1.2.10 | ScalarupsInputCurrentPhaseC | read-only | mandatory | The input phase current unit for Phase C. |
| 1.3.6.1.4.1.186.1.19.2.5.1.2.11 | ScalarupsInputFrequency | read-only | mandatory | The input frequency unit 0.1 Hertz. |
| 1.3.6.1.4.1.186.1.19.2.5.1.2.12 | ScalarupsInputActivePowerA | read-only | mandatory | The magnitude of the present input true power for phase A. |
| 1.3.6.1.4.1.186.1.19.2.5.1.2.13 | ScalarupsInputActivePowerB | read-only | mandatory | The magnitude of the present input true power for phase B. |
| 1.3.6.1.4.1.186.1.19.2.5.1.2.14 | ScalarupsInputActivePowerC | read-only | mandatory | The magnitude of the present input true power for phase C. |
| 1.3.6.1.4.1.186.1.19.2.5.1.2.15 | ScalarupsInputTotalActivePower | read-only | mandatory | The magnitude of the total input true power. |
| 1.3.6.1.4.1.186.1.19.2.5.1.2.16 | ScalarupsInputRatedLLVoltage | read-only | mandatory | The input line to line rated voltage in RMS volts. |
| 1.3.6.1.4.1.186.1.19.2.5.1.3 | NodeupsOutput | |||
| 1.3.6.1.4.1.186.1.19.2.5.1.3 | NodeupsTrapOnBattery | Info: The UPS is on Battery Mode. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.3.1 | ScalarupsOutputSource | read-only | mandatory | The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the… |
| 1.3.6.1.4.1.186.1.19.2.5.1.3.2 | ScalarupsOutputNumOfPhases | read-only | mandatory | The number of output lines utilized in this device. |
| 1.3.6.1.4.1.186.1.19.2.5.1.3.3 | ScalarupsOutputLLVoltageAB | read-only | mandatory | The output line to line voltage for AB in RMS volts. |
| 1.3.6.1.4.1.186.1.19.2.5.1.3.4 | ScalarupsOutputLLVoltageBC | read-only | mandatory | The output line to line voltage for BC in RMS volts. |
| 1.3.6.1.4.1.186.1.19.2.5.1.3.5 | ScalarupsOutputLLVoltageCA | read-only | mandatory | The output line to line voltage for CA in RMS volts. |
| 1.3.6.1.4.1.186.1.19.2.5.1.3.6 | ScalarupsOutputCurrentPhaseA | read-only | mandatory | The Output phase current for phase A in amps. |
| 1.3.6.1.4.1.186.1.19.2.5.1.3.7 | ScalarupsOutputCurrentPhaseB | read-only | mandatory | The Output phase current for phase B in amps. |
| 1.3.6.1.4.1.186.1.19.2.5.1.3.8 | ScalarupsOutputCurrentPhaseC | read-only | mandatory | The Output phase current for phase C in amps. |
| 1.3.6.1.4.1.186.1.19.2.5.1.3.9 | ScalarupsOutputFrequency | read-only | mandatory | The Output Frequency for phase A in 1/10 of HZ. |
| 1.3.6.1.4.1.186.1.19.2.5.1.3.10 | ScalarupsOutputCurrentPercentA | read-only | mandatory | The output current for phase A in percent. |
| 1.3.6.1.4.1.186.1.19.2.5.1.3.11 | ScalarupsOutputCurrentPercentB | read-only | mandatory | The output current for phase B in percent. |
| 1.3.6.1.4.1.186.1.19.2.5.1.3.12 | ScalarupsOutputCurrentPercentC | read-only | mandatory | The output current for phase C in percent. |
| 1.3.6.1.4.1.186.1.19.2.5.1.3.13 | ScalarupsOutputTotalActivePower | read-only | mandatory | The output active power. |
| 1.3.6.1.4.1.186.1.19.2.5.1.3.14 | ScalarupsOutputTotalActivePowerPercent | read-only | mandatory | The output active power in percent. |
| 1.3.6.1.4.1.186.1.19.2.5.1.3.15 | ScalarupsOutputPowerFactor | read-only | mandatory | The UPS output power factor. |
| 1.3.6.1.4.1.186.1.19.2.5.1.3.16 | ScalarupsOutputRatedActivePower | read-only | mandatory | The output rated active power for the UPS. |
| 1.3.6.1.4.1.186.1.19.2.5.1.3.17 | ScalarupsOutputRatedApparentPower | read-only | mandatory | The output rated apparent power for the UPS. |
| 1.3.6.1.4.1.186.1.19.2.5.1.3.18 | ScalarupsOutputRatedLLVoltage | read-only | mandatory | The output rated line to line voltage for the UPS. |
| 1.3.6.1.4.1.186.1.19.2.5.1.4 | NodeupsBypass | |||
| 1.3.6.1.4.1.186.1.19.2.5.1.4 | NodeupsTrapOnBatteryClear | Info Clear: The UPS is on Battery Mode. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.4.1 | ScalarupsBypassNumOfPhases | read-only | mandatory | The number of bypass lines utilized. |
| 1.3.6.1.4.1.186.1.19.2.5.1.4.2 | ScalarupsBypassLLVoltageAB | read-only | mandatory | The Bypass line to line voltage for AB in RMS volts. |
| 1.3.6.1.4.1.186.1.19.2.5.1.4.3 | ScalarupsBypassLLVoltageBC | read-only | mandatory | The Bypass line to line voltage for BC in RMS volts. |
| 1.3.6.1.4.1.186.1.19.2.5.1.4.4 | ScalarupsBypassLLVoltageCA | read-only | mandatory | The Bypass line to line voltage for CA in RMS volts. |
| 1.3.6.1.4.1.186.1.19.2.5.1.4.5 | ScalarupsBypassFrequency | read-only | mandatory | The Bypass frequency in 0.1 Hertz. |
| 1.3.6.1.4.1.186.1.19.2.5.1.5 | NodeupsBattery | |||
| 1.3.6.1.4.1.186.1.19.2.5.1.5 | NodeupsTrapBatteryLow | Warning: Battery Low Voltage. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.5.1 | ScalarupsBatteryStatus | read-only | mandatory | The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run time sufficient to handle the… |
| 1.3.6.1.4.1.186.1.19.2.5.1.5.2 | ScalarupsElapsedTimeOnBatteryPower | read-only | mandatory | If the unit is on battery power, the elapsed time since the UPS on battery power, or the time since the network management subsystem was last restarted, whiche… |
| 1.3.6.1.4.1.186.1.19.2.5.1.5.3 | ScalarupsEstimatedBatteryRuntime | read-only | mandatory | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and… |
| 1.3.6.1.4.1.186.1.19.2.5.1.5.4 | ScalarupsBatteryVoltage | read-only | mandatory | The battery voltage DC. |
| 1.3.6.1.4.1.186.1.19.2.5.1.5.5 | ScalarupsBatteryVoltagePercent | read-only | mandatory | Battery voltage in percent. |
| 1.3.6.1.4.1.186.1.19.2.5.1.5.6 | ScalarupsBatteryEstimatedCharge | read-only | mandatory | An estimate of the charge to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost a… |
| 1.3.6.1.4.1.186.1.19.2.5.1.5.7 | ScalarupsBatteryDischargeCurrent | read-only | mandatory | The present battery discharge Current in percent. |
| 1.3.6.1.4.1.186.1.19.2.5.1.5.8 | ScalarupsBatteryChargeCurrent | read-only | mandatory | The present battery charge Current in percent. |
| 1.3.6.1.4.1.186.1.19.2.5.1.5.9 | ScalarupsBatteryModel | read-write | mandatory | The Battery manufacturer. |
| 1.3.6.1.4.1.186.1.19.2.5.1.5.10 | ScalarupsBatteryInSeries | read-write | mandatory | The Battery rated holding time in minutes. |
| 1.3.6.1.4.1.186.1.19.2.5.1.5.11 | ScalarupsBatteryNumStrings | read-write | mandatory | The Battery rated holding time in minutes. |
| 1.3.6.1.4.1.186.1.19.2.5.1.5.12 | ScalarupsBatteryRatedAmpereHour | read-write | mandatory | The Battery rated holding time in minutes. |
| 1.3.6.1.4.1.186.1.19.2.5.1.5.13 | ScalarupsBatteryRatedBackupTime | read-write | mandatory | The Battery rated holding time in minutes. |
| 1.3.6.1.4.1.186.1.19.2.5.1.5.14 | ScalarupsBatteryInstallationDate | read-only | mandatory | The battery install date. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6 | NodeupsAlarm | |||
| 1.3.6.1.4.1.186.1.19.2.5.1.6 | NodeupsTrapBatteryLowClear | Warning Clear: Battery Low Voltage. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.6.1 | ScalarupsAlarmsPresent | read-only | mandatory | The present number of active alarm conditions. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.2 | TableupsAlarmTable | not-accessible | mandatory | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is … |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.2.1 | RowupsAlarmEntry | not-accessible | mandatory | An entry containing information applicable to a particular alarm. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.1 | ColumnupsAlarmId | not-accessible | mandatory | A unique identifier for an alarm condition. This value must remain constant. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.2 | ColumnupsAlarmDescr | read-only | mandatory | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con… |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.3 | ColumnupsAlarmTime | read-only | mandatory | The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag… |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3 | NodeupsWellKnownAlarms | |||
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.1 | ScalarupsAlarmFault | read-only | mandatory | Fault: A UPS fault/Alarm condition exists. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.2 | ScalarupsAlarmOnBattery | read-only | mandatory | Info: The UPS is on Battery mode; it is supplying output power from its batteries. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.3 | ScalarupsAlarmBatteryLow | read-only | mandatory | Warning: The battery level is low. It has dropped to less than 90% of its nominal value. Continued operation in Battery Mode will deplete Batteries and result … |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.4 | ScalarupsAlarmBatteryDepleted | read-only | mandatory | Warning: UPS contains depleted batteries, it will be unable to support critical loads. Shut down excess equipment to reduce Load. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.5 | ScalarupsAlarmBatteryOverheat | read-only | mandatory | Fault: Detection of over temperature at the batteries. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.6 | ScalarupsAlarmBatteryVoltageAbnormal | read-only | mandatory | Fault: Battery voltage is abnormality. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.7 | ScalarupsAlarmUPSOverheat | read-only | mandatory | Fault: The UPS is overheating (warning is given when the internal temperature reaches and exceeds 50?C rise @ 40?C ambient). Check to see if the ambient temper… |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.8 | ScalarupsAlarmPowerFailure | read-only | mandatory | Info: Power Failure. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.9 | ScalarupsAlarmUPSOverload | read-only | mandatory | Fault: The UPS is overloaded. UPS will switch to bypass operation or shut down if no action is taken. Shut down excess equipment to reduce Load. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.10 | ScalarupsAlarmUserDefinedOverloadWarning | read-only | mandatory | Warning: The inverter output load % is greater than the user defined overload set point (default: 110%). |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.11 | ScalarupsAlarmOnBypass | read-only | mandatory | Warning: The UPS is in Stop (Bypass) mode. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.12 | ScalarupsAlarmOutputOff | read-only | mandatory | Info: The UPS output is off. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.13 | ScalarupsAlarmAsyncOperation | read-only | mandatory | Warning: Async Operation |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.14 | ScalarupsAlarmDCBusOverCurrent | read-only | mandatory | Fault: UPS is reporting a DC bus overcurrent condition. Contact your Toshiba authorized service center for examination of a DCOC fault. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.15 | ScalarupsAlarmDCBusOverVoltage | read-only | mandatory | Fault: UPS is reporting a DC bus overvoltage condition. Contact your Toshiba authorized service center for examination of a DCOV fault. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.16 | ScalarupsAlarmDCBusUnderVoltage | read-only | mandatory | Fault: UPS is reporting a DC bus undervoltage condition. Contact your Toshiba authorized service center for examination of a DCUV fault. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.17 | ScalarupsAlarmDCBusImbalanced | read-only | mandatory | Fault: The DC imbalanced alarm detection. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.18 | ScalarupsAlarmOutputUnderVoltage | read-only | mandatory | Fault: UPS is reporting an output undervoltage condition. Contact your Toshiba authorized service center for examination of a INVUV fault. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.19 | ScalarupsAlarmOutputOverVoltage | read-only | mandatory | Fault: UPS is reporting an output overvoltage condition. Contact your Toshiba authorized service center for examination of a INVOV fault. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.20 | ScalarupsAlarmInverterOverload | read-only | mandatory | Fault: Short time over-current has been detected. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.21 | ScalarupsAlarmInverterOvercurrent | read-only | mandatory | Fault: Detection of inverter overcurrent. |
| 1.3.6.1.4.1.186.1.19.2.5.1.6.3.22 | ScalarupsAlarmRemotEyeCommError | read-only | mandatory | Warning: Communication error between the RemotEye 4 and the UPS. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7 | NodeupsConfig | |||
| 1.3.6.1.4.1.186.1.19.2.5.1.7 | NodeupsTrapBatteryDepleted | Warning: UPS contains depleted batteries, it will be unable to support critical loads. Shutdown excess equipment to reduce load. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.7.1 | ScalarupsConfigModelIDString | read-only | mandatory | UPS Model ID string. This string contains codes for the UPS series,input voltage, output voltage, output VA, and addition option. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.2 | ScalarupsConfigUPSFirmwareVersion | read-only | mandatory | The G9000 software version. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.3 | ScalarupsConfigInputNumOfPhases | read-only | mandatory | Number of input lines. This data is used by upsInputNumLines. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.4 | ScalarupsConfigRatedInputFrequency | read-only | mandatory | The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is no… |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.5 | ScalarupsConfigRatedInputLLVoltage | read-write | mandatory | The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a v… |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.6 | ScalarupsConfigRatedInputPowerFactor | read-only | mandatory | UNITS are in hundredths. For 0.95 = 95. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.7 | ScalarupsConfigOutputNumOfPhases | read-only | mandatory | Number of output lines. This data is used by upsOutputNumLines. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.8 | ScalarupsConfigRatedOutputFrequency | read-only | mandatory | The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is n… |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.9 | ScalarupsConfigRatedOutputLLVoltage | read-write | mandatory | The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a … |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.10 | ScalarupsConfigRatedOutputApperentPower | read-only | mandatory | The magnitude of the nominal Volt-Amp rating. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.11 | ScalarupsConfigRatedOutputActivePower | read-only | mandatory | The magnitude of the nominal true power rating. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.12 | ScalarupsConfigRatedOutputPowerFactor | read-only | mandatory | UNITS are in hundredths. For 0.70 = 70. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.13 | ScalarupsConfigBypassNumOfPhases | read-only | mandatory | The number of bypass lines utilized. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.14 | ScalarupsConfigLowVoltageTransferPoint | read-write | mandatory | The minimum input line voltage allowed before the UPS system transfers to battery backup. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.15 | ScalarupsConfigHighVoltageTransferPoint | read-write | mandatory | The maximum line voltage allowed before the UPS system transfers to battery backup. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.16 | ScalarupsConfigBatteryInSeries | read-write | mandatory | The number of batteries in each string connected in series. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.17 | ScalarupsConfigBatteryNumStrings | read-write | mandatory | The number of parallel battery strings. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.18 | ScalarupsConfigRatedBatteryVoltage | read-write | mandatory | Rated voltage of a single battery. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.19 | ScalarupsConfigRatedBatteryAmpereHour | read-write | mandatory | The rated battery in ampere hour. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.20 | ScalarupsConfigBatteryModel | read-write | mandatory | The manufacturer of the battery. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.21 | ScalarupsConfigBatteryRatedBackupTime | read-write | mandatory | The rated duration batteries can hold when unit is in backup mode with full load. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.22 | ScalarupsConfigUserDefinedOverloadSetPoint | read-write | mandatory | The maximum output load % defined by the user. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.23 | ScalarupsConfigBatteryInstallationDate | read-write | mandatory | The battery install date. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.24 | ScalarupsConfigSysName | read-write | mandatory | A string identifying the UPS. This object is set by the administrator. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.25 | ScalarupsConfigAttachedDevices | read-write | mandatory | A string identifying the devices attached to the output(s) of the UPS. This object is set by the administrator. |
| 1.3.6.1.4.1.186.1.19.2.5.1.7.26 | ScalarupsConfigPassword | read-write | mandatory | Password. |
| 1.3.6.1.4.1.186.1.19.2.5.1.8 | NodeupsTime | |||
| 1.3.6.1.4.1.186.1.19.2.5.1.8 | NodeupsTrapBatteryDepletedClear | Warning Clear: UPS contains depleted batteries, it will be unable to support critical loads. Shutdown excess equipment to reduce load.. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.8.1 | ScalarupsTimeRealDate | read-write | mandatory | Present date: year-month-date-day of the week. |
| 1.3.6.1.4.1.186.1.19.2.5.1.8.2 | ScalarupsTimeRealTime | read-write | mandatory | Present time (military format): hour-minute-second. For example,2:00pm would be 14:00:00. |
| 1.3.6.1.4.1.186.1.19.2.5.1.9 | NodeupsTrap | |||
| 1.3.6.1.4.1.186.1.19.2.5.1.9 | NodeupsTrapBatteryOverheat | Fault: Battery Overheat. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.10 | NodeupsTrapBatteryOverheatClear | Fault Clear: Battery Overheat. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.11 | NodeupsTrapBatteryVoltageAbnormal | Fault: Battery Voltage Abnormal. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.12 | NodeupsTrapBatteryVoltageAbnormalClear | Fault Clear: Battery Voltage Abnormal. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.13 | NodeupsTrapUPSOverheat | Fault: UPS Overheat, heatsinks temperature exceeds thermal settings. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.14 | NodeupsTrapUPSOverheatClear | Fault Clear: UPS Overheat, heatsinks temperature exceeds thermal settings. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.15 | NodeupsTrapPowerFailure | Info: Power Failure. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.16 | NodeupsTrapPowerFailureClear | Info Clear: PowerFailure. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.17 | NodeupsTrapUPSOverload | Fault: UPS Overload (OL), the output load exceeds the rated current. Decrease load. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.18 | NodeupsTrapUPSOverloadClear | Fault Clear: UPS Overload (OL), the output load exceeds the rated current. Decrease load. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.19 | NodeupsTrapUserDefinedOverloadWarning | Warning: The inverter output load % is greater than the user defined overload set point (default: 110%). | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.20 | NodeupsTrapUserDefinedOverloadWarningClear | Warning Clear: The inverter output load % is greater than the user defined overload set point (default: 110%). | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.21 | NodeupsTrapOnBypass | Warning:On Bypass. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.22 | NodeupsTrapOnBypassClear | Warning Clear: On Bypass. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.23 | NodeupsTrapOutputOff | Info: The UPS output is off. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.24 | NodeupsTrapOutputOffClear | Info Clear: The UPS output is off. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.25 | NodeupsTrapAsyncOperation | Warning: Inverter Synchronous. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.26 | NodeupsTrapAsyncOperationClear | Warning Clear: Inverter Synchronous. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.27 | NodeupsTrapDCBusOverCurrent | Fault: DC Overcurrent (DCOC). Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.28 | NodeupsTrapDCBusOverCurrentClear | Fault Clear: DC Overcurrent (DCOC). Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.29 | NodeupsTrapDCBusOverVoltage | Fault: DC Overvoltage (DCOV). Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.30 | NodeupsTrapDCBusOverVoltageClear | Fault Clear: DC Overvoltage (DCOV). Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.31 | NodeupsTrapDCBusUnderVoltage | Fault: DC Undervoltage (DCUV). Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.32 | NodeupsTrapDCBusUnderVoltageClear | Fault Clear: DC Undervoltage (DCUV). Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.33 | NodeupsTrapDCBusImbalance | Fault: DC Unbalance. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.34 | NodeupsTrapDCBusImbalanceClear | Fault Clear: DC Unbalance. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.35 | NodeupsTrapOutputUnderVoltage | Fault: Output Undervoltage. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.36 | NodeupsTrapOutputUnderVoltageClear | Fault Clear: Output Undervoltage. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.37 | NodeupsTrapOutputOverVoltage | Fault: Output Overvoltage (VLOV). Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.38 | NodeupsTrapOutputOverVoltageClear | Fault Clear: Output Overvoltage (VLOV). Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.39 | NodeupsTrapInverterOverload | Fault: UPS Overload, short time over-current has been detected during On-Line operation. Decrease Load. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.40 | NodeupsTrapInverterOverloadClear | Fault Clear: UPS Overload, short time over-current has been detected during On-Line operation. Decrease Load. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.41 | NodeupsTrapInverterOvercurrent | Fault: Inverter Overcurrent. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.42 | NodeupsTrapInverterOvercurrentClear | Fault Clear: Inverter Overcurrent. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.43 | NodeupsTrapRemotEyeCommError | Warning: RemotEye UPS communication error. | ||
| 1.3.6.1.4.1.186.1.19.2.5.1.44 | NodeupsTrapRemotEyeCommErrorClear | Warning Clear:RemotEye UPS communication error. |