This MIB module defines MIB objects which provide mechanisms for remote management capabilities of Tripp Lite PowerAlert and related software.
Imported Objects
SNMPv2-CONFNOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIenterprises Gauge32 Integer32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-IDENTITY OBJECT-TYPE TimeTicks Unsigned32
SNMPv2-TCDisplayString RowStatus TimeStamp TruthValue
TRIPPLITEtripplite
OIDNameAccessStatusDescription
1.3.6.1.4.1.850.1IdentitytlpProductsThis MIB module defines MIB objects which provide mechanisms for remote management capabilities of Tripp Lite PowerAlert and related software.
1.3.6.1.4.1.850.1.1NodetlpHardware
1.3.6.1.4.1.850.1.1.1NodetlpDevice
1.3.6.1.4.1.850.1.1.1.1ScalartlpDeviceNumDevicesread-onlycurrentThe number of devices that this agent is currently managing.
1.3.6.1.4.1.850.1.1.1.2TabletlpDeviceTablenot-accessiblecurrentA list of device table entries. The number of entries is given by the value of tlpDevicesNumDevices.
1.3.6.1.4.1.850.1.1.1.2.1RowtlpDeviceEntrynot-accessiblecurrentAn entry containing information applicable to a particular device managed by this agent.
1.3.6.1.4.1.850.1.1.1.2.1.1ColumntlpDeviceIndexread-onlycurrentThe table row index for the device.
1.3.6.1.4.1.850.1.1.1.2.1.2ColumntlpDeviceRowStatusread-onlycurrentUsed with table edits to indicate the status of a given row in tlDeviceTable.
1.3.6.1.4.1.850.1.1.1.2.1.3ColumntlpDeviceTyperead-onlycurrentThe type of device. One of the appropriate hardware types: ups, pdu, envirosense, etc.
1.3.6.1.4.1.850.1.1.1.2.1.4ColumntlpDeviceManufacturerread-onlycurrentThe name of the manufacturer.
1.3.6.1.4.1.850.1.1.1.2.1.5ColumntlpDeviceModelread-onlycurrentThe model designation.
1.3.6.1.4.1.850.1.1.1.2.1.6ColumntlpDeviceNameread-writecurrentA user-supplied name for the device.
1.3.6.1.4.1.850.1.1.1.2.1.7ColumntlpDeviceIDread-writecurrentA user-supplied ID for the device.
1.3.6.1.4.1.850.1.1.1.2.1.8ColumntlpDeviceLocationread-writecurrentA user-supplied location for the device.
1.3.6.1.4.1.850.1.1.1.2.1.9ColumntlpDeviceRegionread-writecurrentA user-supplied region for the device.
1.3.6.1.4.1.850.1.1.1.2.1.10ColumntlpDeviceStatusread-onlycurrentThe currently most critical alarm status for the device.
1.3.6.1.4.1.850.1.1.2NodetlpDeviceDetail
1.3.6.1.4.1.850.1.1.2.1TabletlpDeviceIdentTablenot-accessiblecurrentThe identity details of each device in device table. The number of entries is given by the value of tlpDevicesNumDevices.
1.3.6.1.4.1.850.1.1.2.1.1RowtlpDeviceIdentEntrynot-accessiblecurrentAn entry containing details for a particular device.
1.3.6.1.4.1.850.1.1.2.1.1.1ColumntlpDeviceIdentProtocolread-onlycurrentThe Tripplite protocol used to communicate with the device.
1.3.6.1.4.1.850.1.1.2.1.1.2ColumntlpDeviceIdentCommPortTyperead-onlycurrentThe type of communications port used to connect with the device.
1.3.6.1.4.1.850.1.1.2.1.1.3ColumntlpDeviceIdentCommPortNameread-onlycurrentThe name of the communications port.
1.3.6.1.4.1.850.1.1.2.1.1.4ColumntlpDeviceIdentFirmwareVersionread-onlycurrentThe firmware version of the device.
1.3.6.1.4.1.850.1.1.2.1.1.5ColumntlpDeviceIdentSerialNumread-onlycurrentThe serial number of the device.
1.3.6.1.4.1.850.1.1.2.1.1.6ColumntlpDeviceIdentDateInstalledread-writecurrentThe installation date for this device in the format of mm/dd/yyyy.
1.3.6.1.4.1.850.1.1.2.1.1.7ColumntlpDeviceIdentHardwareVersionread-onlycurrentThe hardware revision of the device. This value will return ERROR_NO_SUCH_NAME if not supported by the device.
1.3.6.1.4.1.850.1.1.2.1.1.8ColumntlpDeviceIdentCurrentUptimeread-onlycurrentThe device uptime since its last startup. The format of this value is a comma- delimited string representing days, hours and minutes. For example, the value of…
1.3.6.1.4.1.850.1.1.2.1.1.9ColumntlpDeviceIdentTotalUptimeread-onlycurrentThe cumulative (total) uptime for the device. The format of this value is a comma- delimited string representing days, hours and minutes. For example, the valu…
1.3.6.1.4.1.850.1.1.3NodetlpDeviceTypes
1.3.6.1.4.1.850.1.1.3.1NodetlpUps
1.3.6.1.4.1.850.1.1.3.1.1NodetlpUpsIdent
1.3.6.1.4.1.850.1.1.3.1.1.1ScalartlpUpsIdentNumUpsread-onlycurrentThe number of ups devices that this agent is currently managing.
1.3.6.1.4.1.850.1.1.3.1.1.2TabletlpUpsIdentTablenot-accessiblecurrentThe identity details of each ups in device table. This is a sparse dependent table, and will contain some subset of devices that are upss.
1.3.6.1.4.1.850.1.1.3.1.1.2.1RowtlpUpsIdentEntrynot-accessiblecurrentAn entry containing details for a particular ups.
1.3.6.1.4.1.850.1.1.3.1.1.2.1.1ColumntlpUpsIdentNumInputsread-onlycurrentThe number of input lines supported by the ups.
1.3.6.1.4.1.850.1.1.3.1.1.2.1.2ColumntlpUpsIdentNumOutputsread-onlycurrentThe number of output lines supported by the ups.
1.3.6.1.4.1.850.1.1.3.1.1.2.1.3ColumntlpUpsIdentNumBypassread-onlycurrentThe number of bypass lines supported by the ups.
1.3.6.1.4.1.850.1.1.3.1.1.2.1.4ColumntlpUpsIdentNumPhasesread-onlycurrentThe number of phases supported by the ups.
1.3.6.1.4.1.850.1.1.3.1.1.2.1.5ColumntlpUpsIdentNumOutletsread-onlycurrentThe number of receptacles supported by the ups.
1.3.6.1.4.1.850.1.1.3.1.1.2.1.6ColumntlpUpsIdentNumOutletGroupsread-onlycurrentThe number of receptacle groups supported by the ups.
1.3.6.1.4.1.850.1.1.3.1.1.2.1.7ColumntlpUpsIdentNumBatteryPacksread-onlycurrentThe number of battery packs, internal and external combined, supported by the ups.
1.3.6.1.4.1.850.1.1.3.1.1.3TabletlpUpsSupportsTablenot-accessiblecurrentThe supported details of each ups in device table. This is a sparse dependent table, and will contain some subset of devices that are upss.
1.3.6.1.4.1.850.1.1.3.1.1.3.1RowtlpUpsSupportsEntrynot-accessiblecurrentAn entry containing supported details for a particular ups.
1.3.6.1.4.1.850.1.1.3.1.1.3.1.1ColumntlpUpsSupportsEnergywiseread-onlycurrentIndicates whether the ups supports Cisco EnergyWise.
1.3.6.1.4.1.850.1.1.3.1.1.3.1.2ColumntlpUpsSupportsRampShedread-onlycurrentIndicates whether the ups supports ramping and shedding.
1.3.6.1.4.1.850.1.1.3.1.1.3.1.3ColumntlpUpsSupportsOutletGroupread-onlycurrentIndicates whether the ups supports outlet groups.
1.3.6.1.4.1.850.1.1.3.1.1.3.1.4ColumntlpUpsSupportsOutletCurrentPowerread-onlycurrentIndicates whether the ups reports individual receptacle current and power measurements. Devices that do not support individual receptacle measurements will alw…
1.3.6.1.4.1.850.1.1.3.1.1.3.1.5ColumntlpUpsSupportsOutletVoltageread-onlycurrentIndicates whether the ups reports individual receptacle voltage measurements. Devices that do not support individual receptacle measurements will always return…
1.3.6.1.4.1.850.1.1.3.1.2NodetlpUpsDevice
1.3.6.1.4.1.850.1.1.3.1.2.1TabletlpUpsDeviceTablenot-accessiblecurrentThe device details of each ups in device table. This is a sparse dependent table, and will contain some subset of devices that are upss.
1.3.6.1.4.1.850.1.1.3.1.2.1.1RowtlpUpsDeviceEntrynot-accessiblecurrentAn entry containing device details for a particular ups.
1.3.6.1.4.1.850.1.1.3.1.2.1.1.1ColumntlpUpsDeviceMainLoadStateread-onlycurrentThe current state of the main output of the device.
1.3.6.1.4.1.850.1.1.3.1.2.1.1.2ColumntlpUpsDeviceMainLoadControllableread-onlycurrentIndicates whether or not the main output is controllable, and whether the ups can be turned off and on.
1.3.6.1.4.1.850.1.1.3.1.2.1.1.3ColumntlpUpsDeviceMainLoadCommandread-writecurrentReading this value will always return 0. Setting this value to turnOff(1) will turn off the main output of the ups. Setting this value to turnOn(2) will turn o…
1.3.6.1.4.1.850.1.1.3.1.2.1.1.4ColumntlpUpsDevicePowerOnDelayread-writecurrentThe configurable delay value, which sets the amount of additional time a given device will wait before it connects to a valid AC source. By default the delay v…
1.3.6.1.4.1.850.1.1.3.1.2.1.1.5ColumntlpUpsDeviceTestDateread-onlycurrentThe date of the last self-test run on the ups, in the format YYYY-MM-DD.
1.3.6.1.4.1.850.1.1.3.1.2.1.1.6ColumntlpUpsDeviceTestResultsStatusread-onlycurrentThe result of the last self-test run on the ups.
1.3.6.1.4.1.850.1.1.3.1.2.1.1.7ColumntlpUpsDeviceTemperatureCread-onlycurrentThe ambient temperature at or near the ups casing. Temperature measurements are not supported on all models. If not supported, this value will always return ER…
1.3.6.1.4.1.850.1.1.3.1.2.1.1.8ColumntlpUpsDeviceTemperatureFread-onlycurrentThe ambient temperature at or near the ups casing. Temperature measurements are not supported on all models. If not supported, this value will always return ER…
1.3.6.1.4.1.850.1.1.3.1.3NodetlpUpsDetail
1.3.6.1.4.1.850.1.1.3.1.3.1NodetlpUpsBattery
1.3.6.1.4.1.850.1.1.3.1.3.1.1TabletlpUpsBatterySummaryTablenot-accessiblecurrentThe battery system summary of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of u…
1.3.6.1.4.1.850.1.1.3.1.3.1.1.1RowtlpUpsBatterySummaryEntrynot-accessiblecurrentAn entry containing information applicable to a particular battery system managed by this agent.
1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.1ColumntlpUpsBatteryStatusread-onlycurrentThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than tlpUpsCo…
1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.2ColumntlpUpsSecondsOnBatteryread-onlycurrentIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.3ColumntlpUpsEstimatedMinutesRemainingread-onlycurrentAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.4ColumntlpUpsEstimatedChargeRemainingread-onlycurrentAn estimate of the battery charge remaining expressed as a percent of full charge.
1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.5ColumntlpUpsBatteryRunTimeRemainingread-onlycurrentThe run time remaining before batteries are exhausted. If the device does not support run time remaining, then the agent reports ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.850.1.1.3.1.3.1.2TabletlpUpsBatteryDetailTablenot-accessiblecurrentThe battery detail of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss mana…
1.3.6.1.4.1.850.1.1.3.1.3.1.2.1RowtlpUpsBatteryDetailEntrynot-accessiblecurrentAn entry containing information applicable to a particular battery system managed by this agent.
1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.1ColumntlpUpsBatteryDetailVoltageread-onlycurrentThe magnitude of the present battery voltage.
1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.2ColumntlpUpsBatteryDetailCurrentread-onlycurrentThe present battery current.
1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.3ColumntlpUpsBatteryDetailCapacityread-onlycurrentThe estimated remaining battery capacity expressed as a percent of full capacity.
1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.4ColumntlpUpsBatteryDetailChargeread-onlycurrentDenotes the charge state of the battery.
1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.5ColumntlpUpsBatteryDetailChargerStatusread-onlycurrentThe status of the battery charger. If the device does not support this value, then the agent will report ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.850.1.1.3.1.3.1.3TabletlpUpsBatteryPackIdentTablenot-accessiblecurrentThe battery identification details for each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the nu…
1.3.6.1.4.1.850.1.1.3.1.3.1.3.1RowtlpUpsBatteryPackIdentEntrynot-accessiblecurrentAn entry containing information applicable to a particular battery pack managed by this agent.
1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.1ColumntlpUpsBatteryPackIdentIndexread-onlycurrentThe table row index for the ups battery pack.
1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.2ColumntlpUpsBatteryPackIdentManufacturerread-onlycurrentThe manufacturer of the battery pack. If the device does not support this value, then the agent reports ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.3ColumntlpUpsBatteryPackIdentModelread-onlycurrentThe model or device name of the battery pack. If the device does not support this value, then the agent reports ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.4ColumntlpUpsBatteryPackIdentSerialNumread-onlycurrentThe serial number of the battery pack. If the device does not support this value, then the agent reports ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.5ColumntlpUpsBatteryPackIdentFirmwareread-onlycurrentThe firmware of the battery pack. If the device does not support this value, then the agent reports ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.6ColumntlpUpsBatteryPackIdentSKUread-onlycurrentThe SKU of the battery pack. If the device does not support this value, then the agent reports ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.850.1.1.3.1.3.1.4TabletlpUpsBatteryPackConfigTablenot-accessiblecurrentThe battery configuration details for each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the num…
1.3.6.1.4.1.850.1.1.3.1.3.1.4.1RowtlpUpsBatteryPackConfigEntrynot-accessiblecurrentAn entry containing information applicable to a particular battery pack managed by this agent.
1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.1ColumntlpUpsBatteryPackConfigChemistryread-onlycurrentThe type of battery pack.
1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.2ColumntlpUpsBatteryPackConfigStyleread-onlycurrentThe style of battery pack.
1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.3ColumntlpUpsBatteryPackConfigLocationread-onlycurrentThe location of the battery pack.
1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.4ColumntlpUpsBatteryPackConfigStringsread-onlycurrentThe number of series strings in parallel contained in the battery pack. If the device does not support this value, then the agent will report ERROR_NO_SUCH_NAM…
1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.5ColumntlpUpsBatteryPackConfigBatteriesPerStringread-onlycurrentThe number of battery per each string in the battery pack. If the device does not support this value, then the agent will report ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.6ColumntlpUpsBatteryPackConfigCellsPerBatteryread-onlycurrentThe number of cells per battery..
1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.7ColumntlpUpsBatteryPackConfigNumBatteriesread-onlycurrentThe total number of batteries contained in the battery pack. If the device does not support this value, then the agent will report ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.8ColumntlpUpsBatteryPackConfigCapacityUnitsread-onlycurrentThe units of measurement used for tlpUpsBatteryPackConfigDesignCapacity and tlpUpsBatteryPackConfigCellCapacity. If supported, this value will report either mA…
1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.9ColumntlpUpsBatteryPackConfigDesignCapacityread-onlycurrentThe theoretical or nominal capacity of the battery pack in the measurement defined by tlpUpsBatteryPackConfigCapacityUnits. If the device does not support this…
1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.10ColumntlpUpsBatteryPackConfigCellCapacityread-onlycurrentThe capacity of the batteries in the measurement defined by tlpUpsBatteryPackConfigCapacityUnits. If the device does not support this value, then the agent wil…
1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.11ColumntlpUpsBatteryPackConfigMinCellVoltageread-onlycurrentThe minimum cell voltage for the batteries. If the device does not support this value, then the agent will report ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.12ColumntlpUpsBatteryPackConfigMaxCellVoltageread-onlycurrentThe maximum cell voltage for the batteries. If the device does not support this value, then the agent will report ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.850.1.1.3.1.3.1.5TabletlpUpsBatteryPackDetailTablenot-accessiblecurrentThe details of each battery pack for each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the numb…
1.3.6.1.4.1.850.1.1.3.1.3.1.5.1RowtlpUpsBatteryPackDetailEntrynot-accessiblecurrentAn entry containing information applicable to a particular battery system managed by this agent.
1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.1ColumntlpUpsBatteryPackDetailConditionread-onlycurrentThe condition of the battery. A bad battery should be replaced.
1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.2ColumntlpUpsBatteryPackDetailTemperatureCread-onlycurrentThe ambient temperature at or near the UPS Battery casing.
1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.3ColumntlpUpsBatteryPackDetailTemperatureFread-onlycurrentThe ambient temperature at or near the UPS Battery casing.
1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.4ColumntlpUpsBatteryPackDetailAgeread-onlycurrentThe age of the battery in years. This is equal to the current date minus tlpUpsBatteryPackIdentInstallDate.
1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.5ColumntlpUpsBatteryPackDetailLastReplaceDateread-writecurrentThe date when the batteries were last replaced in YYYYMMDD format.
1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.6ColumntlpUpsBatteryPackDetailNextReplaceDateread-onlycurrentThe date when the batteries should next be replaced in YYYYMMDD format.
1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.7ColumntlpUpsBatteryPackDetailCycleCountread-onlycurrentThe number of times the battery went into invert mode. This number is incremented by 1 each time the unit goes on battery mode (with the exception of Self Test…
1.3.6.1.4.1.850.1.1.3.1.3.2NodetlpUpsInput
1.3.6.1.4.1.850.1.1.3.1.3.2.1TabletlpUpsInputTablenot-accessiblecurrentThe input details of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss manag…
1.3.6.1.4.1.850.1.1.3.1.3.2.1.1RowtlpUpsInputEntrynot-accessiblecurrentAn entry containing information applicable to all input lines per each ups managed by this agent.
1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.1ColumntlpUpsInputLineBadsread-onlycurrentA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i…
1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.2ColumntlpUpsInputNominalVoltageread-onlycurrentThe nominal value of the input line voltage. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.3ColumntlpUpsInputNominalFrequencyread-onlycurrentThe nominal value of the input line frequency. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.4ColumntlpUpsInputLowTransferVoltageread-onlycurrentThe minimum line voltage allowed before the ups system transfers to battery backup.
1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.5ColumntlpUpsInputLowTransferVoltageLowerBoundread-onlycurrentThe lower boundary value of tlpUpsInputLowTransferVoltage as dictated by the hardware of the unit.
1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.6ColumntlpUpsInputLowTransferVoltageUpperBoundread-onlycurrentThe upper boundary value of tlpUpsInputLowTransferVoltage as dictated by the hardware of the unit.
1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.7ColumntlpUpsInputHighTransferVoltageread-onlycurrentThe maximum line voltage allowed before the ups system transfers to battery backup.
1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.8ColumntlpUpsInputHighTransferVoltageLowerBoundread-onlycurrentThe lower boundary value of tlpUpsInputHighTransferVoltage as dictated by the hardware of the unit.
1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.9ColumntlpUpsInputHighTransferVoltageUpperBoundread-onlycurrentThe upper boundary value of tlpUpsInputHighTransferVoltage as dictated by the hardware of the unit.
1.3.6.1.4.1.850.1.1.3.1.3.2.2TabletlpUpsInputPhaseTablenot-accessiblecurrentThe input phase details of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss…
1.3.6.1.4.1.850.1.1.3.1.3.2.2.1RowtlpUpsInputPhaseEntrynot-accessiblecurrentAn entry containing information applicable to a particular input phase managed by this agent.
1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.1ColumntlpUpsInputPhaseIndexread-onlycurrentThe table row index for the ups input phase.
1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.2ColumntlpUpsInputPhaseFrequencyread-onlycurrentThe present input frequency for a given input line.
1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.3ColumntlpUpsInputPhaseVoltageread-onlycurrentThe magnitude of the present input voltage for a given input line.
1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.4ColumntlpUpsInputPhaseVoltageMinread-writecurrentThe minimum input voltage value since the last reset of this value for a given input line. If any value is written to either tlpUpsInputVoltageMin or tlpUpsInp…
1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.5ColumntlpUpsInputPhaseVoltageMaxread-writecurrentThe maximum input voltage value since the last reset of this value for a given input line. If any value is written to either tlpUpsInputVoltageMin or tlpUpsInp…
1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.6ColumntlpUpsInputPhaseCurrentread-onlycurrentThe magnitude of the present input current.
1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.7ColumntlpUpsInputPhasePowerread-onlycurrentThe magnitude of the present input true power.
1.3.6.1.4.1.850.1.1.3.1.3.3NodetlpUpsOutput
1.3.6.1.4.1.850.1.1.3.1.3.3.1TabletlpUpsOutputTablenot-accessiblecurrentThe output details of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss mana…
1.3.6.1.4.1.850.1.1.3.1.3.3.1.1RowtlpUpsOutputEntrynot-accessiblecurrentAn entry containing information applicable to a particular output line managed by this agent.
1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.1ColumntlpUpsOutputSourceread-onlycurrentThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.2ColumntlpUpsOutputNominalVoltageread-onlycurrentThe nominal value of the output voltage. This value may not be supported on all models. If not supported, the agent reports ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.3ColumntlpUpsOutputFrequencyread-onlycurrentThe present output frequency. The output frequency on most ups devices is common across all output lines. Some ups devices, however, maintain the output freque…
1.3.6.1.4.1.850.1.1.3.1.3.3.2TabletlpUpsOutputLineTablenot-accessiblecurrentThe output line details of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss…
1.3.6.1.4.1.850.1.1.3.1.3.3.2.1RowtlpUpsOutputLineEntrynot-accessiblecurrentAn entry containing information applicable to a particular output line managed by this agent.
1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.1ColumntlpUpsOutputLineIndexread-onlycurrentThe table row index for the ups output line.
1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.2ColumntlpUpsOutputLineVoltageread-onlycurrentThe magnitude of the present output voltage for a given output line.
1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.3ColumntlpUpsOutputLineCurrentread-onlycurrentThe present output current.
1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.4ColumntlpUpsOutputLinePowerread-onlycurrentThe present output true power.
1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.5ColumntlpUpsOutputLinePercentLoadread-onlycurrentThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent…
1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.6ColumntlpUpsOutputLineFrequencyread-onlycurrentThe present output frequency on this output line. The output frequency on most ups devices is common across all output lines. Some ups devices, however, mainta…
1.3.6.1.4.1.850.1.1.3.1.3.4NodetlpUpsBypass
1.3.6.1.4.1.850.1.1.3.1.3.4.1TabletlpUpsBypassTablenot-accessiblecurrentThe bypass details of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss mana…
1.3.6.1.4.1.850.1.1.3.1.3.4.1.1RowtlpUpsBypassEntrynot-accessiblecurrentAn entry containing information applicable to all input lines per each ups managed by this agent.
1.3.6.1.4.1.850.1.1.3.1.3.4.1.1.1ColumntlpUpsBypassFrequencyread-onlycurrentThe present bypass frequency.
1.3.6.1.4.1.850.1.1.3.1.3.4.2TabletlpUpsBypassLineTablenot-accessiblecurrentThe bypass line details of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss…
1.3.6.1.4.1.850.1.1.3.1.3.4.2.1RowtlpUpsBypassLineEntrynot-accessiblecurrentAn entry containing information applicable to a particular bypass line managed by this agent.
1.3.6.1.4.1.850.1.1.3.1.3.4.2.1.1ColumntlpUpsBypassLineIndexread-onlycurrentThe bypass line identifier.
1.3.6.1.4.1.850.1.1.3.1.3.4.2.1.2ColumntlpUpsBypassLineVoltageread-onlycurrentThe present bypass voltage.
1.3.6.1.4.1.850.1.1.3.1.3.4.2.1.3ColumntlpUpsBypassLineCurrentread-onlycurrentThe present bypass current.
1.3.6.1.4.1.850.1.1.3.1.3.4.2.1.4ColumntlpUpsBypassLinePowerread-onlycurrentThe present true power conveyed by the bypass.
1.3.6.1.4.1.850.1.1.3.1.3.5NodetlpUpsOutlet
1.3.6.1.4.1.850.1.1.3.1.3.5.1TabletlpUpsOutletTablenot-accessiblecurrentThe details of each ups outlet in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of upss mana…
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1RowtlpUpsOutletEntrynot-accessiblecurrentAn entry containing information applicable to a particular outlet managed by this agent.
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.1ColumntlpUpsOutletIndexread-onlycurrentThe table row index for the ups outlet.
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.2ColumntlpUpsOutletNameread-writecurrentA user-definable string identifying the name of the outlet.
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.3ColumntlpUpsOutletDescriptionread-writecurrentA user-definable string identifying the device(s) connected to the given outlet.
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.4ColumntlpUpsOutletStateread-onlycurrentThe current state of the outlet.
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.5ColumntlpUpsOutletControllableread-onlycurrentDenotes whether this outlet is controllable.
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.6ColumntlpUpsOutletCommandread-writecurrentReading this value will always return 0. Setting this value to turnOff(1) will turn off the outlet. Setting this value to turnOn(2) will turn on the outlet. Se…
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.7ColumntlpUpsOutletVoltageread-onlycurrentThe magnitude of the present output voltage for a given outlet. If the voltage measurement is not supported for an individual receptacle regardless whether dev…
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.8ColumntlpUpsOutletCurrentread-onlycurrentThe present output current, in hundreths of amps, of a given outlet. If the current measurement is not supported for an individual receptacle regardless whethe…
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.9ColumntlpUpsOutletPowerread-onlycurrentThe output power of a given outlet. If the power measurement is not supported for an individual receptacle regardless whether device-wide or just for this rece…
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.10ColumntlpUpsOutletRampActionread-writecurrentThe ramp action to take on a given outlet when powering on the device. If this receptacle is not controllable, as denoted by tlpUpsOutletControllable, then thi…
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.11ColumntlpUpsOutletRampDelayread-writecurrentThe number of seconds to delay before powering on the given outlet. If this receptacle is not controllable, as denoted by tlpUpsOutletControllable, then this v…
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.12ColumntlpUpsOutletShedActionread-writecurrentThe shed action to take on a given outlet when powering off the device. If this receptacle is not controllable, as denoted by tlpUpsOutletControllable, then th…
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.13ColumntlpUpsOutletShedDelayread-writecurrentThe number of seconds to delay before powering off the given outlet. If this receptacle is not controllable, as denoted by tlpUpsOutletControllable, then this …
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.14ColumntlpUpsOutletGroupread-writecurrentThe tlpUpsOutletGroupIndex group index of the respective group to which the given outlet is assigned, or zero (0) if the given outlet is not grouped.
1.3.6.1.4.1.850.1.1.3.1.3.5.2TabletlpUpsOutletGroupTablenot-accessiblecurrentThe receptacle grouping details of each ups in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of t…
1.3.6.1.4.1.850.1.1.3.1.3.5.2.1RowtlpUpsOutletGroupEntrynot-accessiblecurrentAn entry containing information applicable to a particular outlet group managed by this agent.
1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.1ColumntlpUpsOutletGroupIndexread-onlycurrentThe table row index for the ups outlet group.
1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.2ColumntlpUpsOutletGroupRowStatusread-writecurrentRow status for the tlpUpsOutletGroupTable
1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.3ColumntlpUpsOutletGroupNameread-writecurrentThe name of this outlet group.
1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.4ColumntlpUpsOutletGroupDescriptionread-writecurrentA description for this outlet group.
1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.5ColumntlpUpsOutletGroupStateread-onlycurrentThe current state of the outlet group. This value will report off(1) if all outlets in the group are off, on(2) if all outlets in the group are on, mixed(3) if…
1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.6ColumntlpUpsOutletGroupCommandread-writecurrentReading this value will always return 0. Setting this value to turnOff(1) will turn off every outlet associated with the group. Setting this value to turnOn(2)…
1.3.6.1.4.1.850.1.1.3.1.3.6NodetlpUpsWatchdog
1.3.6.1.4.1.850.1.1.3.1.3.6.1TabletlpUpsWatchdogTablenot-accessiblecurrentThe watchdog details of each ups in device table. This is a sparse dependent table, and will contain some subset of devices that are upss.
1.3.6.1.4.1.850.1.1.3.1.3.6.1.1RowtlpUpsWatchdogEntrynot-accessiblecurrentAn entry containing watchdog details for a particular ups.
1.3.6.1.4.1.850.1.1.3.1.3.6.1.1.1ColumntlpUpsWatchdogSupportedread-onlycurrentIndicates whether or not this ups supports a watchdog reboot.
1.3.6.1.4.1.850.1.1.3.1.3.6.1.1.2ColumntlpUpsWatchdogSecsBeforeRebootread-writecurrentThe maximum number of seconds that can expire between polls that the engine makes to the ups for data. If this time runs out, then the ups will cycle its outpu…
1.3.6.1.4.1.850.1.1.3.1.4NodetlpUpsControl
1.3.6.1.4.1.850.1.1.3.1.4.1TabletlpUpsControlTablenot-accessiblecurrentThe actionable controls for each ups in device table. This is a sparse dependent table, and will contain some subset of devices that are upss.
1.3.6.1.4.1.850.1.1.3.1.4.1.1RowtlpUpsControlEntrynot-accessiblecurrentAn entry containing controls for a particular ups.
1.3.6.1.4.1.850.1.1.3.1.4.1.1.1ColumntlpUpsControlSelfTestread-writecurrentSet to TRUE to initiate a self test on the ups.
1.3.6.1.4.1.850.1.1.3.1.4.1.1.2ColumntlpUpsControlRampread-writecurrentSet to TRUE to initiate the pre-designated ramp sequence on the ups.
1.3.6.1.4.1.850.1.1.3.1.4.1.1.3ColumntlpUpsControlShedread-writecurrentSet to TRUE to initiate the pre-designated shed sequence on the ups.
1.3.6.1.4.1.850.1.1.3.1.4.1.1.4ColumntlpUpsControlUpsOnread-writecurrentSet to TRUE to turn the ups on.
1.3.6.1.4.1.850.1.1.3.1.4.1.1.5ColumntlpUpsControlUpsOffread-writecurrentSet to TRUE to turn the ups off.
1.3.6.1.4.1.850.1.1.3.1.4.1.1.6ColumntlpUpsControlUpsRebootread-writecurrentSet to TRUE to reboot the ups.
1.3.6.1.4.1.850.1.1.3.1.4.1.1.7ColumntlpUpsControlBypassread-writecurrentThis switches the ups in and out of bypass mode. This value returns the current bypass mode: disable(0) if the ups is not in bypass mode, enable(1) if the ups …
1.3.6.1.4.1.850.1.1.3.1.5NodetlpUpsConfig
1.3.6.1.4.1.850.1.1.3.1.5.1TabletlpUpsConfigTablenot-accessiblecurrentThe configuration details of each ups in the device table. This is a sparse dependent table, and will contain the number of entries based upon the number of up…
1.3.6.1.4.1.850.1.1.3.1.5.1.1RowtlpUpsConfigEntrynot-accessiblecurrentAn entry containing information applicable to all input lines per each ups managed by this agent.
1.3.6.1.4.1.850.1.1.3.1.5.1.1.1ColumntlpUpsConfigInputVoltageread-writecurrentThe nominal value of the input line voltage. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME. This v…
1.3.6.1.4.1.850.1.1.3.1.5.1.1.2ColumntlpUpsConfigInputFrequencyread-writecurrentThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is no…
1.3.6.1.4.1.850.1.1.3.1.5.1.1.3ColumntlpUpsConfigOutputVoltageread-writecurrentThe nominal value of the output voltage. This value may not be supported on all models. If not supported, the agent reports ERROR_NO_SUCH_NAME. This value may …
1.3.6.1.4.1.850.1.1.3.1.5.1.1.4ColumntlpUpsConfigOutputFrequencyread-writecurrentThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is n…
1.3.6.1.4.1.850.1.1.3.1.5.1.1.5ColumntlpUpsConfigAudibleStatusread-writecurrentThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self- describing. Setting this…
1.3.6.1.4.1.850.1.1.3.1.5.1.1.6ColumntlpUpsConfigAutoBatteryTestread-writecurrentWhen disabled(0), the ups will not perform an automatic battery selftest. When set to another value, the ups will perform an automatic selftest in the approxim…
1.3.6.1.4.1.850.1.1.3.1.5.1.1.7ColumntlpUpsConfigAutoRestartAfterShutdownread-writecurrentWhen enabled(1), the ups should autorestart after a shutdown from battery mode if valid AC is applied. When disabled(0), the ups should not autorestart when AC…
1.3.6.1.4.1.850.1.1.3.1.5.1.1.8ColumntlpUpsConfigAutoRampOnTransitionread-writecurrentWhen enabled(1), the ups should perform its preconfigured ramp sequence when valid AC is restored while in battery mode. If this value is not supported by the …
1.3.6.1.4.1.850.1.1.3.1.5.1.1.9ColumntlpUpsConfigAutoShedOnTransitionread-writecurrentWhen enabled(1), the ups should perform its preconfigured shed sequence when valid AC is lost causing the ups to enter battery mode. If this value is not suppo…
1.3.6.1.4.1.850.1.1.3.1.5.1.1.10ColumntlpUpsConfigBypassLowerLimitPercentread-writecurrentThe lowest AC input voltage allowed to be output to the load while in bypass mode. This setting is expressed as a percentage from nominal voltage. If this valu…
1.3.6.1.4.1.850.1.1.3.1.5.1.1.11ColumntlpUpsConfigBypassUpperLimitPercentread-writecurrentThe highest AC input voltage allowed to be output to the load while in bypass mode. This setting is expressed as a percentage from nominal voltage. If this val…
1.3.6.1.4.1.850.1.1.3.1.5.1.1.12ColumntlpUpsConfigBypassLowerLimitVoltageread-writecurrentThe lowest AC input voltage allowed to be output to the load while in bypass mode. If this value is not supported by the ups, then this value will always retur…
1.3.6.1.4.1.850.1.1.3.1.5.1.1.13ColumntlpUpsConfigBypassUpperLimitVoltageread-writecurrentThe highest AC input voltage allowed to be output to the load while in bypass mode. If this value is not supported by the ups, then this value will always retu…
1.3.6.1.4.1.850.1.1.3.1.5.1.1.14ColumntlpUpsConfigColdStartread-writecurrentThis option enables or disables the ability to turn the ups on without AC supplied. If this value is not supported by the ups, then this value will always retu…
1.3.6.1.4.1.850.1.1.3.1.5.1.1.15ColumntlpUpsConfigEconomicModeread-writecurrentThe configurable economic mode options for the ups. The online(0) mode is the default configuration of most upss, which is synonymous as having the economic mo…
1.3.6.1.4.1.850.1.1.3.1.5.1.1.16ColumntlpUpsConfigFaultActionread-writecurrentDetermines the action to take if the output needs to be shut down due to a fault condition, limited by the type of fault incurred. When configured for bypass(0…
1.3.6.1.4.1.850.1.1.3.1.5.1.1.17ColumntlpUpsConfigOffModeread-writecurrentThis option governs what mode the ups should go into when AC input is available, but the load is either off or not battery backed up. If this setting is config…
1.3.6.1.4.1.850.1.1.3.1.5.1.1.18ColumntlpUpsConfigLineSensitivityread-writecurrentAdjusts the AC line voltage sensitivity setting. If this value is not supported by the ups, then this value will always return ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.850.1.1.3.1.5.2TabletlpUpsConfigAutoRestartTablenot-accessiblecurrentThe configurable automatic restart options of each ups in device table. This is a sparse dependent table, and will contain some subset of devices that are upss…
1.3.6.1.4.1.850.1.1.3.1.5.2.1RowtlpUpsConfigAutoRestartEntrynot-accessiblecurrentAn entry containing configurable automatic restart options for a particular ups.
1.3.6.1.4.1.850.1.1.3.1.5.2.1.1ColumntlpUpsConfigAutoRestartInverterShutdownread-writecurrentIf enabled(1) and the ups is turned off from invert mode (via user interaction), if line becomes valid, the ups will automatically go to line mode. If disabled…
1.3.6.1.4.1.850.1.1.3.1.5.2.1.2ColumntlpUpsConfigAutoRestartDelayedWakeupread-writecurrentIf enabled(1) and power fails during a DelayBeforeStartup and line remains invalid after the timeout expires, the ups will be set to turn back on automatically…
1.3.6.1.4.1.850.1.1.3.1.5.2.1.3ColumntlpUpsConfigAutoRestartLowVoltageCutoffread-writecurrentIf enabled(1) and the ups is turned off from invert mode (via low voltage cutoff), if line becomes valid, the ups will automatically go to line mode. If disabl…
1.3.6.1.4.1.850.1.1.3.1.5.2.1.4ColumntlpUpsConfigAutoRestartOverLoadread-writecurrentIf enabled(1) and the ups is turned off from invert mode (via overload), if line becomes valid, the ups will automatically go to line mode. If disabled(0), the…
1.3.6.1.4.1.850.1.1.3.1.5.2.1.5ColumntlpUpsConfigAutoRestartOverTemperatureread-writecurrentIf enabled(1) and the ups is turned off from invert mode (via over temperature), if line becomes valid, the ups will automatically go to line mode. If disabled…
1.3.6.1.4.1.850.1.1.3.1.5.3TabletlpUpsConfigThresholdTablenot-accessiblecurrentThe configurable threshold options of each ups in device table. This is a sparse dependent table, and will contain some subset of devices that are upss. Not al…
1.3.6.1.4.1.850.1.1.3.1.5.3.1RowtlpUpsConfigThresholdEntrynot-accessiblecurrentAn entry containing configurable threshold options for a particular ups.
1.3.6.1.4.1.850.1.1.3.1.5.3.1.1ColumntlpUpsConfigBatteryAgeThresholdread-writecurrentThe number of months for a battery to be in service. The battery age alarm, tlpUpsAlarmBatteryAgeAboveThreshold, is triggered when the current date exceeds tlp…
1.3.6.1.4.1.850.1.1.3.1.5.3.1.2ColumntlpUpsConfigLowBatteryThresholdread-writecurrentThis value denotes the percentage of battery capacity remaining warning level. The low battery alarm, tlpUpsAlarmLowBattery, is triggered when tlpUpsEstimatedC…
1.3.6.1.4.1.850.1.1.3.1.5.3.1.3ColumntlpUpsConfigLowBatteryTimeread-writecurrentThe value in seconds of tlpUpsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) val…
1.3.6.1.4.1.850.1.1.3.1.5.3.1.4ColumntlpUpsConfigOverLoadThresholdread-writecurrentThis value denotes the percentage of load at which the overload condition occurs. The overload alarm, tlpUpsAlarmOutputOverload, is triggered when the percenta…
1.3.6.1.4.1.850.1.1.3.2NodetlpPdu
1.3.6.1.4.1.850.1.1.3.2.1NodetlpPduIdent
1.3.6.1.4.1.850.1.1.3.2.1.1ScalartlpPduIdentNumPduread-onlycurrentThe number of pdu devices that this agent is currently managing.
1.3.6.1.4.1.850.1.1.3.2.1.2TabletlpPduIdentTablenot-accessiblecurrentThe identity details of each pdu in device table. This is a sparse dependent table, and will contain some subset of devices that are pdus.
1.3.6.1.4.1.850.1.1.3.2.1.2.1RowtlpPduIdentEntrynot-accessiblecurrentAn entry containing details for a particular pdu.
1.3.6.1.4.1.850.1.1.3.2.1.2.1.1ColumntlpPduIdentNumInputsread-onlycurrentThe number of input lines supported by the pdu.
1.3.6.1.4.1.850.1.1.3.2.1.2.1.2ColumntlpPduIdentNumOutputsread-onlycurrentThe number of output lines supported by the pdu.
1.3.6.1.4.1.850.1.1.3.2.1.2.1.3ColumntlpPduIdentNumPhasesread-onlycurrentThe number of phases supported by the pdu.
1.3.6.1.4.1.850.1.1.3.2.1.2.1.4ColumntlpPduIdentNumOutletsread-onlycurrentThe number of receptacles supported by the pdu.
1.3.6.1.4.1.850.1.1.3.2.1.2.1.5ColumntlpPduIdentNumOutletGroupsread-onlycurrentThe number of receptacle groups supported by the pdu.
1.3.6.1.4.1.850.1.1.3.2.1.2.1.6ColumntlpPduIdentNumCircuitsread-onlycurrentThe number of circuits supported by the pdu.
1.3.6.1.4.1.850.1.1.3.2.1.2.1.7ColumntlpPduIdentNumBreakersread-onlycurrentThe number of bank breakers supported by the pdu.
1.3.6.1.4.1.850.1.1.3.2.1.2.1.8ColumntlpPduIdentNumHeatsinksread-onlycurrentThe number of heatsink thermistors supported by the pdu.
1.3.6.1.4.1.850.1.1.3.2.1.3TabletlpPduSupportsTablenot-accessiblecurrentThe supported details of each pdu in device table. This is a sparse dependent table, and will contain some subset of devices that are pdus.
1.3.6.1.4.1.850.1.1.3.2.1.3.1RowtlpPduSupportsEntrynot-accessiblecurrentAn entry containing supported details for a particular pdu.
1.3.6.1.4.1.850.1.1.3.2.1.3.1.1ColumntlpPduSupportsEnergywiseread-onlycurrentIndicates whether the pdu supports Cisco EnergyWise.
1.3.6.1.4.1.850.1.1.3.2.1.3.1.2ColumntlpPduSupportsRampShedread-onlycurrentIndicates whether the pdu supports ramping and shedding.
1.3.6.1.4.1.850.1.1.3.2.1.3.1.3ColumntlpPduSupportsOutletGroupread-onlycurrentIndicates whether the pdu supports outlet groups.
1.3.6.1.4.1.850.1.1.3.2.1.3.1.4ColumntlpPduSupportsOutletCurrentPowerread-onlycurrentIndicates whether the pdu reports individual receptacle current and power measurements. Devices that do not support individual receptacle measurements will alw…
1.3.6.1.4.1.850.1.1.3.2.1.3.1.5ColumntlpPduSupportsOutletVoltageread-onlycurrentIndicates whether the pdu reports individual receptacle voltage measurements. Devices that do not support individual receptacle measurements will always return…
1.3.6.1.4.1.850.1.1.3.2.1.4TabletlpPduDisplayTablenot-accessiblecurrentThe display details of each pdu in device table. This is a sparse dependent table, and will contain some subset of devices that are pdus.
1.3.6.1.4.1.850.1.1.3.2.1.4.1RowtlpPduDisplayEntrynot-accessiblecurrentAn entry containing display details for a particular pdu.
1.3.6.1.4.1.850.1.1.3.2.1.4.1.1ColumntlpPduDisplaySchemeread-writecurrentIndicates the display scheme of the LED display. The value schemeReverse(0) indicates the tricolor LED indicator uses an alternate pattern. The value schemeNor…
1.3.6.1.4.1.850.1.1.3.2.1.4.1.2ColumntlpPduDisplayOrientationread-writecurrentIndicates the physical orientation of the LED display. The value displayNormal(0) indicates the display is right-side-up (normal). The value displayReverse(1) …
1.3.6.1.4.1.850.1.1.3.2.1.4.1.3ColumntlpPduDisplayAutoScrollread-writecurrentIndicates whether the LED display automatically scrolls through displaying status values.
1.3.6.1.4.1.850.1.1.3.2.1.4.1.4ColumntlpPduDisplayIntensityread-writecurrentIndicates the intensity, as a percentage, of the LED display. The value intensity100(4) indicates the display is at 100% intensity. The other values indicate t…
1.3.6.1.4.1.850.1.1.3.2.1.4.1.5ColumntlpPduDisplayUnitsread-writecurrentIndicates the units of measurement displayed on the LED display. The value normal(0) indicates that a temperature value, for example, is displayed in degrees F…
1.3.6.1.4.1.850.1.1.3.2.2NodetlpPduDevice
1.3.6.1.4.1.850.1.1.3.2.2.1TabletlpPduDeviceTablenot-accessiblecurrentThe device details of each pdu in device table. This is a sparse dependent table, and will contain some subset of devices that are pdus.
1.3.6.1.4.1.850.1.1.3.2.2.1.1RowtlpPduDeviceEntrynot-accessiblecurrentAn entry containing device details for a particular pdu.
1.3.6.1.4.1.850.1.1.3.2.2.1.1.1ColumntlpPduDeviceMainLoadStateread-onlycurrentThe current state of the main output of the device.
1.3.6.1.4.1.850.1.1.3.2.2.1.1.2ColumntlpPduDeviceMainLoadControllableread-onlycurrentIndicates whether or not the main output is controllable, and whether the ups can be turned off and on.
1.3.6.1.4.1.850.1.1.3.2.2.1.1.3ColumntlpPduDeviceMainLoadCommandread-writecurrentReading this value will always return 0. Setting this value to turnOff(1) will turn off the main output of the ups. Setting this value to turnOn(2) will turn o…
1.3.6.1.4.1.850.1.1.3.2.2.1.1.4ColumntlpPduDevicePowerOnDelayread-writecurrentThe configurable delay value, which sets the amount of additional time a given device will wait before it connects to a valid AC source. By default the delay v…
1.3.6.1.4.1.850.1.1.3.2.2.1.1.5ColumntlpPduDeviceTotalInputPowerRatingread-onlycurrentThe total input power rating of all phases on the device. This value may not be supported on all models. If not supported, this value will always return ERROR_…
1.3.6.1.4.1.850.1.1.3.2.2.1.1.6ColumntlpPduDeviceTemperatureCread-onlycurrentThe ambient temperature at or near the PDU casing. Temperature measurements are not supported on all models. If not supported, this value will always return ER…
1.3.6.1.4.1.850.1.1.3.2.2.1.1.7ColumntlpPduDeviceTemperatureFread-onlycurrentThe ambient temperature at or near the PDU casing. Temperature measurements are not supported on all models. If not supported, this value will always return ER…
1.3.6.1.4.1.850.1.1.3.2.2.1.1.8ColumntlpPduDevicePhaseImbalanceread-onlycurrentThe percentage of imbalance of the three phases. This value is in the range from 0% imbalance to 100% imbalance. The lower the value, the better balanced the p…
1.3.6.1.4.1.850.1.1.3.2.2.1.1.9ColumntlpPduDeviceOutputPowerTotalread-onlycurrentThe AC output total power for all circuits.
1.3.6.1.4.1.850.1.1.3.2.2.1.1.10ColumntlpPduDeviceAggregatePowerFactorread-onlycurrentThe aggregrate power factor of all phases.
1.3.6.1.4.1.850.1.1.3.2.2.1.1.11ColumntlpPduDeviceOutputCurrentPrecisionread-onlycurrentOutput current is reported by tlpPduOutputCurrent, tlpPduOutputCurrentMin and tlpPduOutputCurrentMax. These values are all reported in hundredths (0.01A), whic…
1.3.6.1.4.1.850.1.1.3.2.3NodetlpPduDetail
1.3.6.1.4.1.850.1.1.3.2.3.1NodetlpPduInput
1.3.6.1.4.1.850.1.1.3.2.3.1.1TabletlpPduInputTablenot-accessiblecurrentThe input details of each pdu in device table. This is a sparse dependent table, and will contain the number of entries based upon the number of pdus managed b…
1.3.6.1.4.1.850.1.1.3.2.3.1.1.1RowtlpPduInputEntrynot-accessiblecurrentAn entry containing information applicable to a particular pdu managed by this agent.
1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.1ColumntlpPduInputNominalVoltageread-onlycurrentThe nominal value of the input line voltage. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.2ColumntlpPduInputNominalVoltagePhaseToPhaseread-onlycurrentThe nominal value of the input line voltage as measured from phase to phase. This value may not be supported on all models. If not supported, this value will a…
1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.3ColumntlpPduInputNominalVoltagePhaseToNeutralread-onlycurrentThe nominal value of the input line voltage as measured from phase to neutral. This value may not be supported on all models. If not supported, this value will…
1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.4ColumntlpPduInputLowTransferVoltageread-onlycurrentThe minimum line voltage allowed before the unit disconnects the AC input connection. This value may not be writable on all models. If not writable, the value …
1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.5ColumntlpPduInputLowTransferVoltageLowerBoundread-onlycurrentThe lower boundary value of tlpPduInputLowTransferVoltage as dictated by the hardware of the unit.
1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.6ColumntlpPduInputLowTransferVoltageUpperBoundread-onlycurrentThe upper boundary value of tlpPduInputLowTransferVoltage as dictated by the hardware of the unit.
1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.7ColumntlpPduInputHighTransferVoltageread-onlycurrentThe maximum line voltage allowed before the unit disconnects the AC input connection. This value may not be writable on all models. If not writable, the value …
1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.8ColumntlpPduInputHighTransferVoltageLowerBoundread-onlycurrentThe lower boundary value of tlpPduInputHighTransferVoltage as dictated by the hardware of the unit.
1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.9ColumntlpPduInputHighTransferVoltageUpperBoundread-onlycurrentThe upper boundary value of tlpPduInputHighTransferVoltage as dictated by the hardware of the unit.
1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.10ColumntlpPduInputCurrentLimitread-onlycurrentThe capacity of each phase conductor in the pdu limited by the AC input cord or any other potential limiting factors unique to a given unit.
1.3.6.1.4.1.850.1.1.3.2.3.1.2TabletlpPduInputPhaseTablenot-accessiblecurrentThe input phase details of each pdu in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of tlpPduIde…
1.3.6.1.4.1.850.1.1.3.2.3.1.2.1RowtlpPduInputPhaseEntrynot-accessiblecurrentAn entry containing information applicable to a particular input phase managed by this agent.
1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.1ColumntlpPduInputPhaseIndexread-onlycurrentThe table row index for the pdu phase.
1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.2ColumntlpPduInputPhasePhaseTyperead-onlycurrentDenotes whether measurements are phase to neutral(0) or phase to phase(1).
1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.3ColumntlpPduInputPhaseFrequencyread-onlycurrentThe present input frequency for a given phase.
1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.4ColumntlpPduInputPhaseVoltageread-onlycurrentThe magnitude of the present input voltage for a given phase.
1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.5ColumntlpPduInputPhaseVoltageMinread-writecurrentThe minimum input voltage value since the last reset of this value for a given phase. If any value is written to either tlpPduInputVoltageMin or tlpPduInputVol…
1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.6ColumntlpPduInputPhaseVoltageMaxread-writecurrentThe maximum input voltage value since the last reset of this value for a given phase. If any value is written to either tlpPduInputVoltageMin or tlpPduInputVol…
1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.7ColumntlpPduInputPhaseCurrentread-onlycurrentThe magnitude of the present input current for a given phase.
1.3.6.1.4.1.850.1.1.3.2.3.2NodetlpPduOutput
1.3.6.1.4.1.850.1.1.3.2.3.2.1TabletlpPduOutputTablenot-accessiblecurrentThe output details of each pdu in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of tlpPduIdentNum…
1.3.6.1.4.1.850.1.1.3.2.3.2.1.1RowtlpPduOutputEntrynot-accessiblecurrentAn entry containing output information applicable to a particular phase managed by this agent.
1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.1ColumntlpPduOutputIndexread-onlycurrentThe table row index for the pdu phase.
1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.2ColumntlpPduOutputPhaseread-onlycurrentIndicates the phase associated with the output line.
1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.3ColumntlpPduOutputPhaseTyperead-onlycurrentDenotes whether measurements are phase to neutral(0) or phase to phase(1).
1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.4ColumntlpPduOutputVoltageread-onlycurrentThe magnitude of the present output voltage for a given output line.
1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.5ColumntlpPduOutputCurrentread-onlycurrentThe output current, in hundreths of amps, for a given phase.
1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.6ColumntlpPduOutputCurrentMinread-onlycurrentThe minimum current observed for a given phase since last reset.
1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.7ColumntlpPduOutputCurrentMaxread-onlycurrentThe maximum current observed for a given phase since last reset.
1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.8ColumntlpPduOutputActivePowerread-onlycurrentThe output power for a given phase.
1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.9ColumntlpPduOutputPowerFactorread-onlycurrentThe output power factor, in hundreths of a percent, for a given phase.
1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.10ColumntlpPduOutputSourceread-onlycurrentThe present source of output power. The enumeration none(0) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.850.1.1.3.2.3.3NodetlpPduOutlet
1.3.6.1.4.1.850.1.1.3.2.3.3.1TabletlpPduOutletTablenot-accessiblecurrentThe receptacle status details of each pdu in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of tlp…
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1RowtlpPduOutletEntrynot-accessiblecurrentAn entry containing information applicable to a particular outlet managed by this agent.
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.1ColumntlpPduOutletIndexread-onlycurrentThe table row index for the pdu outlet.
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.2ColumntlpPduOutletNameread-writecurrentA user-definable string identifying the name of the outlet.
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.3ColumntlpPduOutletDescriptionread-writecurrentA user-definable string identifying the device(s) connected to the given outlet.
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.4ColumntlpPduOutletStateread-onlycurrentThe current state of the outlet.
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.5ColumntlpPduOutletControllableread-onlycurrentDenotes whether this outlet is controllable.
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.6ColumntlpPduOutletCommandread-writecurrentReading this value will always return 0. Setting this value to turnOff(1) will turn off the outlet. Setting this value to turnOn(2) will turn on the outlet. Se…
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.7ColumntlpPduOutletVoltageread-onlycurrentThe magnitude of the present output voltage for a given outlet. If the voltage measurement is not supported for an individual receptacle regardless whether dev…
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.8ColumntlpPduOutletCurrentread-onlycurrentThe present output current, in hundreths of amps, of a given outlet. If the current measurement is not supported for an individual receptacle regardless whethe…
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.9ColumntlpPduOutletPowerread-onlycurrentThe output power of a given outlet. If the power measurement is not supported for an individual receptacle regardless whether device-wide or just for this rece…
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.10ColumntlpPduOutletRampActionread-writecurrentThe ramp action to take on a given outlet when powering on the device. If this receptacle is not controllable, as denoted by tlpPduOutletControllable, then thi…
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.11ColumntlpPduOutletRampDelayread-writecurrentThe number of seconds to delay before powering on the given outlet. If this receptacle is not controllable, as denoted by tlpPduOutletControllable, then this v…
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.12ColumntlpPduOutletShedActionread-writecurrentThe shed action to take on a given outlet when powering off the device. If this receptacle is not controllable, as denoted by tlpPduOutletControllable, then th…
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.13ColumntlpPduOutletShedDelayread-writecurrentThe number of seconds to delay before powering off the given outlet. If this receptacle is not controllable, as denoted by tlpPduOutletControllable, then this …
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.14ColumntlpPduOutletGroupread-writecurrentThe tlpPduOutletGroupIndex group index of the respective group to which the given outlet is assigned, or zero (0) if the given outlet is not grouped.
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.15ColumntlpPduOutletBankread-onlycurrentIndicates on which bank the given outlet is located.
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.16ColumntlpPduOutletCircuitread-onlycurrentIndicates on which circuit the given outlet is wired.
1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.17ColumntlpPduOutletPhaseread-onlycurrentIndicates on which phase or phases the given outlet is associated. For single phase devices, this object will always return phase1(1). For 3-phase devices with…
1.3.6.1.4.1.850.1.1.3.2.3.3.2TabletlpPduOutletGroupTablenot-accessiblecurrentThe receptacle grouping details of each pdu in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of t…
1.3.6.1.4.1.850.1.1.3.2.3.3.2.1RowtlpPduOutletGroupEntrynot-accessiblecurrentAn entry containing information applicable to a particular outlet group managed by this agent.
1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.1ColumntlpPduOutletGroupIndexread-onlycurrentThe table row index for the pdu outlet group.
1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.2ColumntlpPduOutletGroupRowStatusread-writecurrentRow status for the tlpPduOutletGroupTable
1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.3ColumntlpPduOutletGroupNameread-writecurrentThe name of this outlet group.
1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.4ColumntlpPduOutletGroupDescriptionread-writecurrentA description for this outlet group.
1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.5ColumntlpPduOutletGroupStateread-onlycurrentThe current state of the outlet group. This value will report off(1) if all outlets in the group are off, on(2) if all outlets in the group are on, mixed(3) if…
1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.6ColumntlpPduOutletGroupCommandread-writecurrentReading this value will always return 0. Setting this value to turnOff(1) will turn off every outlet associated with the group. Setting this value to turnOn(2)…
1.3.6.1.4.1.850.1.1.3.2.3.4NodetlpPduCircuit
1.3.6.1.4.1.850.1.1.3.2.3.4.1TabletlpPduCircuitTablenot-accessiblecurrentA list of pdu circuit table entries. The number of entries is given by the value of tlpPduIdentNumCircuits.
1.3.6.1.4.1.850.1.1.3.2.3.4.1.1RowtlpPduCircuitEntrynot-accessiblecurrentAn entry containing information applicable to a particular circuit managed by this agent.
1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.1ColumntlpPduCircuitIndexread-onlycurrentThe table row index for the pdu circuit.
1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.2ColumntlpPduCircuitPhaseread-onlycurrentIndicates on which phase or phases the given circuit is wired. For single phase devices, this object will always return phase1(1). For 3-phase devices with out…
1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.3ColumntlpPduCircuitInputVoltageread-onlycurrentThe input voltage for a circuit.
1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.4ColumntlpPduCircuitTotalCurrentread-onlycurrentThe total current for all receptacles in a given circuit.
1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.5ColumntlpPduCircuitCurrentLimitread-onlycurrentThe current capacity of a circuit in the system limited by the circuit breaker or wiring used in a given unit.
1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.6ColumntlpPduCircuitCurrentMinread-onlycurrentThe minimum total current for all receptacles in a given circuit since last reset.
1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.7ColumntlpPduCircuitCurrentMaxread-onlycurrentThe maximum total current for all receptacles in a given circuit since last reset.
1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.8ColumntlpPduCircuitTotalPowerread-onlycurrentThe total power for all receptacles in a given circuit.
1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.9ColumntlpPduCircuitPowerFactorread-onlycurrentThe power factor for all receptacles in a given circuit.
1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.10ColumntlpPduCircuitUtilizationread-onlycurrentThe percentage of utilization of a given circuit. This is typically a calculation of tlpPduCircuitTotalCurrent / tlpPduCircuitCurrentLimit.
1.3.6.1.4.1.850.1.1.3.2.3.5NodetlpPduBreaker
1.3.6.1.4.1.850.1.1.3.2.3.5.1TabletlpPduBreakerTablenot-accessiblecurrentA list of pdu bank breaker table entries. The number of entries is given by the value of tlpPduIdentNumBreakers.
1.3.6.1.4.1.850.1.1.3.2.3.5.1.1RowtlpPduBreakerEntrynot-accessiblecurrentAn entry containing information applicable to a particular bank breaker managed by this agent.
1.3.6.1.4.1.850.1.1.3.2.3.5.1.1.1ColumntlpPduBreakerIndexread-onlycurrentThe table row index for the pdu bank breaker.
1.3.6.1.4.1.850.1.1.3.2.3.5.1.1.2ColumntlpPduBreakerStatusread-onlycurrentIndicates whether the bank breaker is open(0), closed(1) or not installed(2).
1.3.6.1.4.1.850.1.1.3.2.3.6NodetlpPduHeatsink
1.3.6.1.4.1.850.1.1.3.2.3.6.1TabletlpPduHeatsinkTablenot-accessiblecurrentA list of pdu heatsink thermistor table entries. The number of entries is given by the value of tlpPduIdentNumHeatsinks.
1.3.6.1.4.1.850.1.1.3.2.3.6.1.1RowtlpPduHeatsinkEntrynot-accessiblecurrentAn entry containing information applicable to a particular heatsink thermistor managed by this agent.
1.3.6.1.4.1.850.1.1.3.2.3.6.1.1.1ColumntlpPduHeatsinkIndexread-onlycurrentThe table row index for the pdu heatsink thermistor.
1.3.6.1.4.1.850.1.1.3.2.3.6.1.1.2ColumntlpPduHeatsinkStatusread-onlycurrentIndicates whether the heatsink thermistor is available. The entry will return notAvailable(0) if a thermistor is either non-existent or disconnected, or availa…
1.3.6.1.4.1.850.1.1.3.2.3.6.1.1.3ColumntlpPduHeatsinkTemperatureCread-onlycurrentThe temperature at the heatsink termistor in tenths degrees Centigrade. Heatsink temperature measurements are not supported on all models. If not supported, th…
1.3.6.1.4.1.850.1.1.3.2.3.6.1.1.4ColumntlpPduHeatsinkTemperatureFread-onlycurrentThe temperature at the heatsink termistor in tenths degrees Farenheit. Heatsink temperature measurements are not supported on all models. If not supported, thi…
1.3.6.1.4.1.850.1.1.3.2.4NodetlpPduControl
1.3.6.1.4.1.850.1.1.3.2.4.1TabletlpPduControlTablenot-accessiblecurrentThe actionable controls for each pdu in device table. This is a sparse dependent table, and will contain some subset of devices that are pdus.
1.3.6.1.4.1.850.1.1.3.2.4.1.1RowtlpPduControlEntrynot-accessiblecurrentAn entry containing controls for a particular pdu.
1.3.6.1.4.1.850.1.1.3.2.4.1.1.1ColumntlpPduControlRampread-writecurrentSet to TRUE to initiate the pre-designated ramp sequence on the pdu.
1.3.6.1.4.1.850.1.1.3.2.4.1.1.2ColumntlpPduControlShedread-writecurrentSet to TRUE to initiate the pre-designated shed sequence on the pdu.
1.3.6.1.4.1.850.1.1.3.2.4.1.1.3ColumntlpPduControlPduOnread-writecurrentSet to TRUE to turn the pdu on.
1.3.6.1.4.1.850.1.1.3.2.4.1.1.4ColumntlpPduControlPduOffread-writecurrentSet to TRUE to turn the pdu off.
1.3.6.1.4.1.850.1.1.3.2.4.1.1.5ColumntlpPduControlPduRebootread-writecurrentSet to TRUE to reboot the pdu.
1.3.6.1.4.1.850.1.1.3.2.5NodetlpPduConfig
1.3.6.1.4.1.850.1.1.3.2.5.1TabletlpPduConfigTablenot-accessiblecurrentThe configuration options of each pdu in device table. This is a sparse dependent table, and will contain some subset of devices that are pdus. Not all options…
1.3.6.1.4.1.850.1.1.3.2.5.1.1RowtlpPduConfigEntrynot-accessiblecurrentAn entry containing configuration options for a particular pdu.
1.3.6.1.4.1.850.1.1.3.2.5.1.1.1ColumntlpPduConfigInputVoltageread-writecurrentThe nominal value of the input line voltage. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME. This v…
1.3.6.1.4.1.850.1.1.3.3NodetlpEnvirosense
1.3.6.1.4.1.850.1.1.3.3.1NodetlpEnvIdent
1.3.6.1.4.1.850.1.1.3.3.1.1ScalartlpEnvIdentNumEnvirosenseread-onlycurrentThe number of envirosense devices that this agent is currently managing.
1.3.6.1.4.1.850.1.1.3.3.1.2TabletlpEnvIdentTablenot-accessiblecurrentThe identity details of each envirosense in device table. The number of entries is given by the value of tlpDevicesNumDevices.
1.3.6.1.4.1.850.1.1.3.3.1.2.1RowtlpEnvIdentEntrynot-accessiblecurrentAn entry containing details for a particular envirosense.
1.3.6.1.4.1.850.1.1.3.3.1.2.1.1ColumntlpEnvIdentTempSupportedread-onlycurrentIndicates whether or not temperature is supported.
1.3.6.1.4.1.850.1.1.3.3.1.2.1.2ColumntlpEnvIdentHumiditySupportedread-onlycurrentIndicates whether or not temperature is supported.
1.3.6.1.4.1.850.1.1.3.3.1.2.1.3ColumntlpEnvNumInputContactsread-onlycurrentThe number of input contacts supported by the envirosense.
1.3.6.1.4.1.850.1.1.3.3.1.2.1.4ColumntlpEnvNumOutputContactsread-onlycurrentThe number of output contacts supported by the envirosense.
1.3.6.1.4.1.850.1.1.3.3.3NodetlpEnvDetail
1.3.6.1.4.1.850.1.1.3.3.3.1TabletlpEnvTemperatureTablenot-accessiblecurrentThe temperature details of each envirosense in device table. The number of entries is given by the value of tlpDevicesNumDevices.
1.3.6.1.4.1.850.1.1.3.3.3.1.1RowtlpEnvTemperatureEntrynot-accessiblecurrentAn entry containing temperature details for a particular envirosense.
1.3.6.1.4.1.850.1.1.3.3.3.1.1.1ColumntlpEnvTemperatureCread-onlycurrentThe ambient temperature.
1.3.6.1.4.1.850.1.1.3.3.3.1.1.2ColumntlpEnvTemperatureFread-onlycurrentThe ambient temperature.
1.3.6.1.4.1.850.1.1.3.3.3.1.1.3ColumntlpEnvTemperatureInAlarmread-onlycurrentIndicates whether or not temperature is in alarm.
1.3.6.1.4.1.850.1.1.3.3.3.2TabletlpEnvHumidityTablenot-accessiblecurrentThe humidity details of each envirosense in device table. The number of entries is given by the value of tlpDevicesNumDevices.
1.3.6.1.4.1.850.1.1.3.3.3.2.1RowtlpEnvHumidityEntrynot-accessiblecurrentAn entry containing humidity details for a particular envirosense.
1.3.6.1.4.1.850.1.1.3.3.3.2.1.1ColumntlpEnvHumidityHumidityread-onlycurrentThe ambient humidity.
1.3.6.1.4.1.850.1.1.3.3.3.2.1.2ColumntlpEnvHumidityInAlarmread-onlycurrentIndicates whether or not humidity is in alarm.
1.3.6.1.4.1.850.1.1.3.3.3.3TabletlpEnvInputContactTablenot-accessiblecurrentThe input contact details of each envirosense in device table. The number of entries is given by the value of tlpDevicesNumDevices.
1.3.6.1.4.1.850.1.1.3.3.3.3.1RowtlpEnvInputContactEntrynot-accessiblecurrentAn entry containing input contact details for a particular envirosense.
1.3.6.1.4.1.850.1.1.3.3.3.3.1.1ColumntlpEnvInputContactIndexread-onlycurrentThe table row index for the envirosense input contact details.
1.3.6.1.4.1.850.1.1.3.3.3.3.1.2ColumntlpEnvInputContactNameread-writecurrentThe name or description of the contact.
1.3.6.1.4.1.850.1.1.3.3.3.3.1.3ColumntlpEnvInputContactNormalStateread-writecurrentThe normal operating position of the contact.
1.3.6.1.4.1.850.1.1.3.3.3.3.1.4ColumntlpEnvInputContactCurrentStateread-onlycurrentThe current state of the contact.
1.3.6.1.4.1.850.1.1.3.3.3.3.1.5ColumntlpEnvInputContactInAlarmread-onlycurrentIndicates whether or not the contact is in alarm.
1.3.6.1.4.1.850.1.1.3.3.3.4TabletlpEnvOutputContactTablenot-accessiblecurrentThe output contact details of each envirosense in device table. The number of entries is given by the value of tlpDevicesNumDevices.
1.3.6.1.4.1.850.1.1.3.3.3.4.1RowtlpEnvOutputContactEntrynot-accessiblecurrentAn entry containing output contact details for a particular envirosense.
1.3.6.1.4.1.850.1.1.3.3.3.4.1.1ColumntlpEnvOutputContactIndexread-onlycurrentThe table row index for the envirosense output contact details.
1.3.6.1.4.1.850.1.1.3.3.3.4.1.2ColumntlpEnvOutputContactNameread-writecurrentThe name or description of the contact.
1.3.6.1.4.1.850.1.1.3.3.3.4.1.3ColumntlpEnvOutputContactNormalStateread-writecurrentThe normal operating position of the contact.
1.3.6.1.4.1.850.1.1.3.3.3.4.1.4ColumntlpEnvOutputContactCurrentStateread-writecurrentThe current state of the contact.
1.3.6.1.4.1.850.1.1.3.3.3.4.1.5ColumntlpEnvOutputContactInAlarmread-onlycurrentIndicates whether or not the contact is in alarm.
1.3.6.1.4.1.850.1.1.3.3.5NodetlpEnvConfig
1.3.6.1.4.1.850.1.1.3.3.5.1TabletlpEnvConfigTablenot-accessiblecurrentThe configuration options of each envirosense in device table. This is a sparse dependent table, and will contain some subset of devices that are envirosenses.…
1.3.6.1.4.1.850.1.1.3.3.5.1.1RowtlpEnvConfigEntrynot-accessiblecurrentAn entry containing configuration options for a particular envirosenses.
1.3.6.1.4.1.850.1.1.3.3.5.1.1.1ColumntlpEnvTemperatureLowLimitread-writecurrentThe lower alarm limit for ambient temperature.
1.3.6.1.4.1.850.1.1.3.3.5.1.1.2ColumntlpEnvTemperatureHighLimitread-writecurrentThe upper alarm limit for ambient temperature.
1.3.6.1.4.1.850.1.1.3.3.5.1.1.3ColumntlpEnvHumidityLowLimitread-writecurrentThe lower alarm limit for ambient humidity.
1.3.6.1.4.1.850.1.1.3.3.5.1.1.4ColumntlpEnvHumidityHighLimitread-writecurrentThe upper alarm limit for ambient humidity.
1.3.6.1.4.1.850.1.1.3.4NodetlpAts
1.3.6.1.4.1.850.1.1.3.4.1NodetlpAtsIdent
1.3.6.1.4.1.850.1.1.3.4.1.1ScalartlpAtsIdentNumAtsread-onlycurrentThe number of ats devices that this agent is currently managing.
1.3.6.1.4.1.850.1.1.3.4.1.2TabletlpAtsIdentTablenot-accessiblecurrentThe identity details of each ats in device table. This is a sparse dependent table, and will contain some subset of devices that are atss.
1.3.6.1.4.1.850.1.1.3.4.1.2.1RowtlpAtsIdentEntrynot-accessiblecurrentAn entry containing details for a particular ats.
1.3.6.1.4.1.850.1.1.3.4.1.2.1.1ColumntlpAtsIdentNumInputsread-onlycurrentThe number of inputs supported by the ats.
1.3.6.1.4.1.850.1.1.3.4.1.2.1.2ColumntlpAtsIdentNumOutputsread-onlycurrentThe number of outputs supported by the ats.
1.3.6.1.4.1.850.1.1.3.4.1.2.1.3ColumntlpAtsIdentNumPhasesread-onlycurrentThe number of phases per input supported by the ats.
1.3.6.1.4.1.850.1.1.3.4.1.2.1.4ColumntlpAtsIdentNumOutletsread-onlycurrentThe number of receptacles supported by the ats.
1.3.6.1.4.1.850.1.1.3.4.1.2.1.5ColumntlpAtsIdentNumOutletGroupsread-onlycurrentThe number of receptacle groups supported by the ats.
1.3.6.1.4.1.850.1.1.3.4.1.2.1.6ColumntlpAtsIdentNumCircuitsread-onlycurrentThe number of circuits supported by the ats.
1.3.6.1.4.1.850.1.1.3.4.1.2.1.7ColumntlpAtsIdentNumBreakersread-onlycurrentThe number of bank breakers supported by the ats.
1.3.6.1.4.1.850.1.1.3.4.1.2.1.8ColumntlpAtsIdentNumHeatsinksread-onlycurrentThe number of heatsink thermistors supported by the ats.
1.3.6.1.4.1.850.1.1.3.4.1.3TabletlpAtsSupportsTablenot-accessiblecurrentThe supported details of each ats in device table. This is a sparse dependent table, and will contain some subset of devices that are atss.
1.3.6.1.4.1.850.1.1.3.4.1.3.1RowtlpAtsSupportsEntrynot-accessiblecurrentAn entry containing supported details for a particular ats.
1.3.6.1.4.1.850.1.1.3.4.1.3.1.1ColumntlpAtsSupportsEnergywiseread-onlycurrentIndicates whether the ats supports Cisco EnergyWise.
1.3.6.1.4.1.850.1.1.3.4.1.3.1.2ColumntlpAtsSupportsRampShedread-onlycurrentIndicates whether the ats supports ramping and shedding.
1.3.6.1.4.1.850.1.1.3.4.1.3.1.3ColumntlpAtsSupportsOutletGroupread-onlycurrentIndicates whether the ats supports outlet groups.
1.3.6.1.4.1.850.1.1.3.4.1.3.1.4ColumntlpAtsSupportsOutletCurrentPowerread-onlycurrentIndicates whether the ats reports individual receptacle current and power measurements. Devices that do not support individual receptacle measurements will alw…
1.3.6.1.4.1.850.1.1.3.4.1.3.1.5ColumntlpAtsSupportsOutletVoltageread-onlycurrentIndicates whether the ats reports individual receptacle voltage measurements. Devices that do not support individual receptacle measurements will always return…
1.3.6.1.4.1.850.1.1.3.4.1.4TabletlpAtsDisplayTablenot-accessiblecurrentThe display details of each ats in device table. This is a sparse dependent table, and will contain some subset of devices that are atss.
1.3.6.1.4.1.850.1.1.3.4.1.4.1RowtlpAtsDisplayEntrynot-accessiblecurrentAn entry containing display details for a particular ats.
1.3.6.1.4.1.850.1.1.3.4.1.4.1.1ColumntlpAtsDisplaySchemeread-writecurrentIndicates the display scheme of the LED display. The value schemeReverse(0) indicates the tricolor LED indicator uses an alternate pattern. The value schemeNor…
1.3.6.1.4.1.850.1.1.3.4.1.4.1.2ColumntlpAtsDisplayOrientationread-writecurrentIndicates the physical orientation of the LED display. The value displayNormal(0) indicates the display is right-side-up (normal). The value displayReverse(1) …
1.3.6.1.4.1.850.1.1.3.4.1.4.1.3ColumntlpAtsDisplayAutoScrollread-writecurrentIndicates whether the LED display automatically scrolls through displaying status values.
1.3.6.1.4.1.850.1.1.3.4.1.4.1.4ColumntlpAtsDisplayIntensityread-writecurrentIndicates the intensity, as a percentage, of the LED display. The value intensity100(4) indicates the display is at 100% intensity. The other values indicate t…
1.3.6.1.4.1.850.1.1.3.4.1.4.1.5ColumntlpAtsDisplayUnitsread-writecurrentIndicates the units of measurement displayed on the LED display. The value normal(0) indicates that a temperature value, for example, is displayed in degrees F…
1.3.6.1.4.1.850.1.1.3.4.2NodetlpAtsDevice
1.3.6.1.4.1.850.1.1.3.4.2.1TabletlpAtsDeviceTablenot-accessiblecurrentThe device details of each ats in device table. This is a sparse dependent table, and will contain some subset of devices that are atss.
1.3.6.1.4.1.850.1.1.3.4.2.1.1RowtlpAtsDeviceEntrynot-accessiblecurrentAn entry containing device details for a particular ats.
1.3.6.1.4.1.850.1.1.3.4.2.1.1.1ColumntlpAtsDeviceMainLoadStateread-onlycurrentThe current state of the main output of the device.
1.3.6.1.4.1.850.1.1.3.4.2.1.1.2ColumntlpAtsDeviceMainLoadControllableread-onlycurrentIndicates whether or not the main output is controllable, and whether the ups can be turned off and on.
1.3.6.1.4.1.850.1.1.3.4.2.1.1.3ColumntlpAtsDeviceMainLoadCommandread-writecurrentReading this value will always return 0. Setting this value to turnOff(1) will turn off the main output of the ups. Setting this value to turnOn(2) will turn o…
1.3.6.1.4.1.850.1.1.3.4.2.1.1.4ColumntlpAtsDevicePowerOnDelayread-writecurrentThe configurable delay value, which sets the amount of additional time a given device will wait before it connects to a valid AC source. By default the delay v…
1.3.6.1.4.1.850.1.1.3.4.2.1.1.5ColumntlpAtsDeviceTotalInputPowerRatingread-onlycurrentThe total input power rating of all phases on the device. This value may not be supported on all models. If not supported, this value will always return ERROR_…
1.3.6.1.4.1.850.1.1.3.4.2.1.1.6ColumntlpAtsDeviceTemperatureCread-onlycurrentThe ambient temperature at or near the ats casing. Temperature measurements are not supported on all models. If not supported, this value will always return ER…
1.3.6.1.4.1.850.1.1.3.4.2.1.1.7ColumntlpAtsDeviceTemperatureFread-onlycurrentThe ambient temperature at or near the ats casing. Temperature measurements are not supported on all models. If not supported, this value will always return ER…
1.3.6.1.4.1.850.1.1.3.4.2.1.1.8ColumntlpAtsDevicePhaseImbalanceread-onlycurrentThe percentage of imbalance of the three phases. This value is in the range from 0% imbalance to 100% imbalance. The lower the value, the better balanced the p…
1.3.6.1.4.1.850.1.1.3.4.2.1.1.9ColumntlpAtsDeviceOutputPowerTotalread-onlycurrentThe AC output total power for all circuits.
1.3.6.1.4.1.850.1.1.3.4.2.1.1.10ColumntlpAtsDeviceAggregatePowerFactorread-onlycurrentThe aggregrate power factor of all phases.
1.3.6.1.4.1.850.1.1.3.4.2.1.1.11ColumntlpAtsDeviceOutputCurrentPrecisionread-onlycurrentOutput current is reported by tlpAtsOutputCurrent, tlpAtsOutputCurrentMin and tlpAtsOutputCurrentMax. These values are all reported in hundredths (0.01A), whic…
1.3.6.1.4.1.850.1.1.3.4.2.1.1.12ColumntlpAtsDeviceGeneralFaultread-onlycurrentIndicates whether or not the ats is in a system fault condition. When the ats is in such a fault condition, the condition can be cleared with tlpAtsControlRese…
1.3.6.1.4.1.850.1.1.3.4.3NodetlpAtsDetail
1.3.6.1.4.1.850.1.1.3.4.3.1NodetlpAtsInput
1.3.6.1.4.1.850.1.1.3.4.3.1.1TabletlpAtsInputTablenot-accessiblecurrentThe input details of each ats in device table. This is a sparse dependent table, and will contain the number of entries based upon the number of atss managed b…
1.3.6.1.4.1.850.1.1.3.4.3.1.1.1RowtlpAtsInputEntrynot-accessiblecurrentAn entry containing information applicable to a particular primary input phase managed by this agent.
1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.1ColumntlpAtsInputNominalVoltageread-onlycurrentThe nominal value of the input line voltage. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.2ColumntlpAtsInputNominalVoltagePhaseToPhaseread-onlycurrentThe nominal value of the input line voltage as measured from phase to phase. This value may not be supported on all models. If not supported, this value will a…
1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.3ColumntlpAtsInputNominalVoltagePhaseToNeutralread-onlycurrentThe nominal value of the input line voltage as measured from phase to neutral. This value may not be supported on all models. If not supported, this value will…
1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.4ColumntlpAtsInputBadTransferVoltageread-onlycurrentThe minimum line voltage allowed before the unit disconnects the AC input connection.
1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.5ColumntlpAtsInputBadTransferVoltageLowerBoundread-onlycurrentThe lower boundary value of tlpAtsInputBadTransferVoltage as dictated by the hardware of the unit.
1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.6ColumntlpAtsInputBadTransferVoltageUpperBoundread-onlycurrentThe upper boundary value of tlpAtsInputBadTransferVoltage as dictated by the hardware of the unit.
1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.7ColumntlpAtsInputHighTransferVoltageread-onlycurrentThe maximum line voltage allowed before the unit disconnects the AC input connection.
1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.8ColumntlpAtsInputHighTransferVoltageLowerBoundread-onlycurrentThe lower boundary value of tlpAtsInputHighTransferVoltage as dictated by the hardware of the unit.
1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.9ColumntlpAtsInputHighTransferVoltageUpperBoundread-onlycurrentThe upper boundary value of tlpAtsInputHighTransferVoltage as dictated by the hardware of the unit.
1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.10ColumntlpAtsInputFairVoltageThresholdread-onlycurrentThe voltage level at which the device will transition between sources.
1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.11ColumntlpAtsInputBadVoltageThresholdread-onlycurrentThe minimum line voltage allowed before the device disconnects the AC input connection.
1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.12ColumntlpAtsInputSourceAvailabilityread-onlycurrentThe determination as to which of two AC input lines are available. The agent will return either inputSourceA(1) or inputSourceB(2) if only one line is availabl…
1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.13ColumntlpAtsInputSourceInUseread-onlycurrentThe determination as to which one of two AC input lines is in use. Not all devices support the reporting of which source is currently in use. If not supported,…
1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.14ColumntlpAtsInputSourceTransitionCountread-onlycurrentThe number of times the device transitions between primary and secondary sources. Most devices are limied to 65533 transitions, after which the value will not …
1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.15ColumntlpAtsInputCurrentLimitread-onlycurrentThe capacity of each phase conductor in the ats limited by the AC input cord or any other potential limiting factors unique to a given unit. If not supported, …
1.3.6.1.4.1.850.1.1.3.4.3.1.2TabletlpAtsInputPhaseTablenot-accessiblecurrentThe input phase details of each ats in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of tlpAtsIde…
1.3.6.1.4.1.850.1.1.3.4.3.1.2.1RowtlpAtsInputPhaseEntrynot-accessiblecurrentAn entry containing information applicable to a particular primary input phase managed by this agent.
1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.1ColumntlpAtsInputLineIndexread-onlycurrentThe table row index for the input line on the ats.
1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.2ColumntlpAtsInputPhaseIndexread-onlycurrentThe table row index for the input phase for the input line.
1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.3ColumntlpAtsInputPhaseTyperead-onlycurrentDenotes whether measurements are phase to neutral(0) or phase to phase(1).
1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.4ColumntlpAtsInputPhaseFrequencyread-onlycurrentThe present input frequency for a given phase.
1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.5ColumntlpAtsInputPhaseVoltageread-onlycurrentThe magnitude of the present input voltage for a given phase.
1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.6ColumntlpAtsInputPhaseVoltageMinread-writecurrentThe minimum input voltage value since the last reset of this value for a given phase. If any value is written to either tlpAtsInputVoltageMin or tlpAtsInputVol…
1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.7ColumntlpAtsInputPhaseVoltageMaxread-writecurrentThe maximum input voltage value since the last reset of this value for a given phase. If any value is written to either tlpAtsInputVoltageMin or tlpAtsInputVol…
1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.8ColumntlpAtsInputPhaseCurrentread-onlycurrentThe magnitude of the present input current for a given phase.
1.3.6.1.4.1.850.1.1.3.4.3.2NodetlpAtsOutput
1.3.6.1.4.1.850.1.1.3.4.3.2.1TabletlpAtsOutputTablenot-accessiblecurrentThe output details of each ats in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of tlpAtsIdentNum…
1.3.6.1.4.1.850.1.1.3.4.3.2.1.1RowtlpAtsOutputEntrynot-accessiblecurrentAn entry containing output information applicable to a particular phase managed by this agent.
1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.1ColumntlpAtsOutputIndexread-onlycurrentThe table row index for the ats phase.
1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.2ColumntlpAtsOutputPhaseread-onlycurrentIndicates the phase associated with the output line.
1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.3ColumntlpAtsOutputPhaseTyperead-onlycurrentDenotes whether measurements are phase to neutral(0) or phase to phase(1).
1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.4ColumntlpAtsOutputVoltageread-onlycurrentThe magnitude of the present output voltage for a given output line.
1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.5ColumntlpAtsOutputCurrentread-onlycurrentThe output current, in hundreths of amps, for a given phase.
1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.6ColumntlpAtsOutputCurrentMinread-onlycurrentThe minimum current observed for a given phase since last reset.
1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.7ColumntlpAtsOutputCurrentMaxread-onlycurrentThe maximum current observed for a given phase since last reset.
1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.8ColumntlpAtsOutputActivePowerread-onlycurrentThe output power for a given phase.
1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.9ColumntlpAtsOutputPowerFactorread-onlycurrentThe output power factor, in hundreths of a percent, for a given phase.
1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.10ColumntlpAtsOutputSourceread-onlycurrentThe present source of output power. The enumeration none(0) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.850.1.1.3.4.3.3NodetlpAtsOutlet
1.3.6.1.4.1.850.1.1.3.4.3.3.1TabletlpAtsOutletTablenot-accessiblecurrentThe receptacle status details of each ats in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of tlp…
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1RowtlpAtsOutletEntrynot-accessiblecurrentAn entry containing information applicable to a particular outlet managed by this agent.
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.1ColumntlpAtsOutletIndexread-onlycurrentThe table row index for the ats outlet.
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.2ColumntlpAtsOutletNameread-writecurrentA user-definable string identifying the name of the outlet.
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.3ColumntlpAtsOutletDescriptionread-writecurrentA user-definable string identifying the device(s) connected to the given outlet.
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.4ColumntlpAtsOutletStateread-onlycurrentThe current state of the outlet.
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.5ColumntlpAtsOutletControllableread-onlycurrentDenotes whether this outlet is controllable.
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.6ColumntlpAtsOutletCommandread-writecurrentReading this value will always return 0. Setting this value to turnOff(1) will turn off the outlet. Setting this value to turnOn(2) will turn on the outlet. Se…
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.7ColumntlpAtsOutletVoltageread-onlycurrentThe magnitude of the present output voltage for a given outlet. If the voltage measurement is not supported for an individual receptacle regardless whether dev…
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.8ColumntlpAtsOutletCurrentread-onlycurrentThe present output current, in hundreths of amps, of a given outlet. If the current measurement is not supported for an individual receptacle regardless whethe…
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.9ColumntlpAtsOutletPowerread-onlycurrentThe output power of a given outlet. If the power measurement is not supported for an individual receptacle regardless whether device-wide or just for this rece…
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.10ColumntlpAtsOutletRampActionread-writecurrentThe ramp action to take on a given outlet when powering on the device. If this receptacle is not controllable, as denoted by tlpAtsOutletControllable, then thi…
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.11ColumntlpAtsOutletRampDelayread-writecurrentThe number of seconds to delay before powering on the given outlet. If this receptacle is not controllable, as denoted by tlpAtsOutletControllable, then this v…
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.12ColumntlpAtsOutletShedActionread-writecurrentThe shed action to take on a given outlet when powering off the device. If this receptacle is not controllable, as denoted by tlpAtsOutletControllable, then th…
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.13ColumntlpAtsOutletShedDelayread-writecurrentThe number of seconds to delay before powering off the given outlet. If this receptacle is not controllable, as denoted by tlpAtsOutletControllable, then this …
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.14ColumntlpAtsOutletGroupread-writecurrentThe tlpAtsOutletGroupIndex group index of the respective group to which the given outlet is assigned, or zero (0) if the given outlet is not grouped.
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.15ColumntlpAtsOutletBankread-onlycurrentIndicates on which bank the given outlet is located.
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.16ColumntlpAtsOutletCircuitread-onlycurrentIndicates on which circuit the given outlet is wired.
1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.17ColumntlpAtsOutletPhaseread-onlycurrentIndicates on which phase or phases the given outlet is associated. For single phase devices, this object will always return phase1(1). For 3-phase devices with…
1.3.6.1.4.1.850.1.1.3.4.3.3.2TabletlpAtsOutletGroupTablenot-accessiblecurrentThe receptacle grouping details of each ats in device table. This is a sparse dependent table, and will contain the number of entries based upon the value of t…
1.3.6.1.4.1.850.1.1.3.4.3.3.2.1RowtlpAtsOutletGroupEntrynot-accessiblecurrentAn entry containing information applicable to a particular outlet group managed by this agent.
1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.1ColumntlpAtsOutletGroupIndexread-onlycurrentThe table row index for the ats outlet group.
1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.2ColumntlpAtsOutletGroupRowStatusread-writecurrentRow status for the tlpAtsOutletGroupTable
1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.3ColumntlpAtsOutletGroupNameread-writecurrentThe name of this outlet group.
1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.4ColumntlpAtsOutletGroupDescriptionread-writecurrentA description for this outlet group.
1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.5ColumntlpAtsOutletGroupStateread-onlycurrentThe current state of the outlet group. This value will report off(1) if all outlets in the group are off, on(2) if all outlets in the group are on, mixed(3) if…
1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.6ColumntlpAtsOutletGroupCommandread-writecurrentReading this value will always return 0. Setting this value to turnOff(1) will turn off every outlet associated with the group. Setting this value to turnOn(2)…
1.3.6.1.4.1.850.1.1.3.4.3.4NodetlpAtsCircuit
1.3.6.1.4.1.850.1.1.3.4.3.4.1TabletlpAtsCircuitTablenot-accessiblecurrentA list of ats circuit table entries. The number of entries is given by the value of tlpAtsIdentNumCircuits.
1.3.6.1.4.1.850.1.1.3.4.3.4.1.1RowtlpAtsCircuitEntrynot-accessiblecurrentAn entry containing information applicable to a particular circuit managed by this agent.
1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.1ColumntlpAtsCircuitIndexread-onlycurrentThe table row index for the ats circuit.
1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.2ColumntlpAtsCircuitPhaseread-onlycurrentIndicates on which phase or phases the given circuit is wired. For single phase devices, this object will always return phase1(1). For 3-phase devices with out…
1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.3ColumntlpAtsCircuitInputVoltageread-onlycurrentThe input voltage for a circuit.
1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.4ColumntlpAtsCircuitTotalCurrentread-onlycurrentThe total current for all receptacles in a given circuit.
1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.5ColumntlpAtsCircuitCurrentLimitread-onlycurrentThe current capacity of a circuit in the system limited by the circuit breaker or wiring used in a given unit.
1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.6ColumntlpAtsCircuitCurrentMinread-onlycurrentThe minimum total current for all receptacles in a given circuit since last reset.
1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.7ColumntlpAtsCircuitCurrentMaxread-onlycurrentThe maximum total current for all receptacles in a given circuit since last reset.
1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.8ColumntlpAtsCircuitTotalPowerread-onlycurrentThe total power for all receptacles in a given circuit.
1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.9ColumntlpAtsCircuitPowerFactorread-onlycurrentThe power factor for all receptacles in a given circuit.
1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.10ColumntlpAtsCircuitUtilizationread-onlycurrentThe percentage of utilization of a given circuit. This is typically a calculation of tlpAtsCircuitTotalCurrent / tlpAtsCircuitCurrentLimit.
1.3.6.1.4.1.850.1.1.3.4.3.5NodetlpAtsBreaker
1.3.6.1.4.1.850.1.1.3.4.3.5.1TabletlpAtsBreakerTablenot-accessiblecurrentA list of ats bank breaker table entries. The number of entries is given by the value of tlpAtsIdentNumBreakers.
1.3.6.1.4.1.850.1.1.3.4.3.5.1.1RowtlpAtsBreakerEntrynot-accessiblecurrentAn entry containing information applicable to a particular bank breaker managed by this agent.
1.3.6.1.4.1.850.1.1.3.4.3.5.1.1.1ColumntlpAtsBreakerIndexread-onlycurrentThe table row index for the ats bank breaker.
1.3.6.1.4.1.850.1.1.3.4.3.5.1.1.2ColumntlpAtsBreakerStatusread-onlycurrentIndicates whether the bank breaker is open(0), closed(1) or not installed(2).
1.3.6.1.4.1.850.1.1.3.4.3.6NodetlpAtsHeatsink
1.3.6.1.4.1.850.1.1.3.4.3.6.1TabletlpAtsHeatsinkTablenot-accessiblecurrentA list of ats heatsink thermistor table entries. The number of entries is given by the value of tlpAtsIdentNumHeatsinks.
1.3.6.1.4.1.850.1.1.3.4.3.6.1.1RowtlpAtsHeatsinkEntrynot-accessiblecurrentAn entry containing information applicable to a particular heatsink thermistor managed by this agent.
1.3.6.1.4.1.850.1.1.3.4.3.6.1.1.1ColumntlpAtsHeatsinkIndexread-onlycurrentThe table row index for the ats heatsink thermistor.
1.3.6.1.4.1.850.1.1.3.4.3.6.1.1.2ColumntlpAtsHeatsinkStatusread-onlycurrentIndicates whether the heatsink thermistor is available. The entry will return notAvailable(0) if a thermistor is either non-existent or disconnected, or availa…
1.3.6.1.4.1.850.1.1.3.4.3.6.1.1.3ColumntlpAtsHeatsinkTemperatureCread-onlycurrentThe temperature at the heatsink termistor in tenths degrees Centigrade. Heatsink temperature measurements are not supported on all models. If not supported, th…
1.3.6.1.4.1.850.1.1.3.4.3.6.1.1.4ColumntlpAtsHeatsinkTemperatureFread-onlycurrentThe temperature at the heatsink termistor in tenths degrees Farenheit. Heatsink temperature measurements are not supported on all models. If not supported, thi…
1.3.6.1.4.1.850.1.1.3.4.4NodetlpAtsControl
1.3.6.1.4.1.850.1.1.3.4.4.1TabletlpAtsControlTablenot-accessiblecurrentThe actionable controls for each ats in device table. This is a sparse dependent table, and will contain some subset of devices that are atss.
1.3.6.1.4.1.850.1.1.3.4.4.1.1RowtlpAtsControlEntrynot-accessiblecurrentAn entry containing controls for a particular ats.
1.3.6.1.4.1.850.1.1.3.4.4.1.1.1ColumntlpAtsControlRampread-writecurrentSet to TRUE to initiate the pre-designated ramp sequence on the ats.
1.3.6.1.4.1.850.1.1.3.4.4.1.1.2ColumntlpAtsControlShedread-writecurrentSet to TRUE to initiate the pre-designated shed sequence on the ats.
1.3.6.1.4.1.850.1.1.3.4.4.1.1.3ColumntlpAtsControlAtsOnread-writecurrentSet to TRUE to turn the ats on.
1.3.6.1.4.1.850.1.1.3.4.4.1.1.4ColumntlpAtsControlAtsOffread-writecurrentSet to TRUE to turn the ats off.
1.3.6.1.4.1.850.1.1.3.4.4.1.1.5ColumntlpAtsControlAtsRebootread-writecurrentSet to TRUE to reboot the ats.
1.3.6.1.4.1.850.1.1.3.4.4.1.1.6ColumntlpAtsControlResetGeneralFaultread-writecurrentSet to TRUE to reset the general fault alarm indicated by tlpAtsDeviceGeneralFault.
1.3.6.1.4.1.850.1.1.3.4.5NodetlpAtsConfig
1.3.6.1.4.1.850.1.1.3.4.5.1TabletlpAtsConfigTablenot-accessiblecurrentThe configuration options of each ats in device table. This is a sparse dependent table, and will contain some subset of devices that are atss. Not all options…
1.3.6.1.4.1.850.1.1.3.4.5.1.1RowtlpAtsConfigEntrynot-accessiblecurrentAn entry containing configuration options for a particular ats.
1.3.6.1.4.1.850.1.1.3.4.5.1.1.1ColumntlpAtsConfigInputVoltageread-writecurrentThe nominal value of the input line voltage. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SUCH_NAME. This v…
1.3.6.1.4.1.850.1.1.3.4.5.1.1.2ColumntlpAtsConfigSourceSelectread-writecurrentThe determination as to which of two AC input lines is designated as the primary input source. The other is designated as the secondary input source. This valu…
1.3.6.1.4.1.850.1.1.3.4.5.1.1.3ColumntlpAtsConfigSource1ReturnTimeread-writecurrentThe nominal time to delay a transition to Source 1, if it is the preferred source.
1.3.6.1.4.1.850.1.1.3.4.5.1.1.4ColumntlpAtsConfigSource2ReturnTimeread-writecurrentThe nominal time to delay a transition to Source 2, if it is the preferred source.
1.3.6.1.4.1.850.1.1.3.4.5.1.1.5ColumntlpAtsConfigAutoRampOnTransitionread-writecurrentWhen enabled(1), the ats should perform its preconfigured ramp sequence when the input source transfers from its designated secondary source to its designated …
1.3.6.1.4.1.850.1.1.3.4.5.1.1.6ColumntlpAtsConfigAutoShedOnTransitionread-writecurrentWhen enabled(1), the ats should perform its preconfigured shed sequence when the input source transfers from its designated primary source to its designated se…
1.3.6.1.4.1.850.1.1.3.4.5.2TabletlpAtsConfigVoltageRangeTablenot-accessiblecurrentThe voltage range options in this table is intended to configure the operating voltages of an ats. This is a sparse dependent table, and will contain some subs…
1.3.6.1.4.1.850.1.1.3.4.5.2.1RowtlpAtsConfigVoltageRangeEntrynot-accessiblecurrentAn entry containing voltage range configuration options for a particular ats.
1.3.6.1.4.1.850.1.1.3.4.5.2.1.1ColumntlpAtsConfigHighVoltageTransferread-writecurrentThe maximum line voltage allowed before the unit disconnects the AC input connection. The maximum value allowed is dictated by tlpAtsInputHighTransferVoltageUp…
1.3.6.1.4.1.850.1.1.3.4.5.2.1.2ColumntlpAtsConfigHighVoltageResetread-writecurrentIf a unit is disconnected due to over-voltage, the line voltage has to fall below this value before the unit re-connects the AC input connection. The maximum v…
1.3.6.1.4.1.850.1.1.3.4.5.2.1.3ColumntlpAtsConfigSource1TransferResetread-writecurrentIf input source 1 voltage level is above this value, a unit connected to source 2 will transition to source 1 (if it is the preferred source). The maximum valu…
1.3.6.1.4.1.850.1.1.3.4.5.2.1.4ColumntlpAtsConfigSource1BrownoutSetread-writecurrentThis value dictates the voltage level below which source 1 goes into a brown out condition. The maximum value allowed is dictated by tlpAtsConfigSource1Transfe…
1.3.6.1.4.1.850.1.1.3.4.5.2.1.5ColumntlpAtsConfigSource1TransferSetread-writecurrentIf input source 1 voltage level falls below this value, a unit connected to source 1 will transition to source 2 (if it is in fair condition as denoted by tlpA…
1.3.6.1.4.1.850.1.1.3.4.5.2.1.6ColumntlpAtsConfigSource2TransferResetread-writecurrentIf input source 2 voltage level is above this value, a unit connected to source 1 will transition to source 2 (if it is the preferred source). The maximum valu…
1.3.6.1.4.1.850.1.1.3.4.5.2.1.7ColumntlpAtsConfigSource2BrownoutSetread-writecurrentThis value dictates the voltage level below which source 2 goes into a brown out condition. The maximum value allowed is dictated by tlpAtsConfigSource2Transfe…
1.3.6.1.4.1.850.1.1.3.4.5.2.1.8ColumntlpAtsConfigSource2TransferSetread-writecurrentIf input source 2 voltage level falls below this value, a unit connected to source 2 will transition to source 1 (if it is in fair condition as denoted by tlpA…
1.3.6.1.4.1.850.1.1.3.4.5.2.1.9ColumntlpAtsConfigLowVoltageResetread-writecurrentIf a unit is disconnected due to under-voltage or is not powered up yet, the line voltage has to rise above this value before the unit gets connected to the AC…
1.3.6.1.4.1.850.1.1.3.4.5.2.1.10ColumntlpAtsConfigLowVoltageTransferread-writecurrentThe minimum line voltage allowed before the unit disconnects the AC input connection. The maximum value allowed is dictated by tlpAtsConfigLowVoltageReset. The…
1.3.6.1.4.1.850.1.1.3.4.5.3TabletlpAtsConfigVoltageRangeLimitsTablenot-accessiblecurrentThe voltage range table, as documented by tlpAtsConfigVoltageRangeTable requires that all changes adhere with stack order, from high transfer voltage down to l…
1.3.6.1.4.1.850.1.1.3.4.5.3.1RowtlpAtsConfigVoltageRangeLimitsEntrynot-accessiblecurrentAn entry containing voltage range limits configuration options for a particular ats.
1.3.6.1.4.1.850.1.1.3.4.5.3.1.1ColumntlpAtsConfigSourceBrownoutSetMinimumread-writecurrentThis value dictates the absolute lower limit by which tlpAtsConfigSource1BrownoutSet and tlpAtsConfigSource2BrownoutSet can be set. tlpAtsConfigSource1Transfer…
1.3.6.1.4.1.850.1.1.3.4.5.3.1.2ColumntlpAtsConfigSourceBrownoutSetMaximumread-writecurrentThis value dictates the absolute upper limit by which tlpAtsConfigSource1BrownoutSet and tlpAtsConfigSource2BrownoutSet can be set. tlpAtsConfigSource1Transfer…
1.3.6.1.4.1.850.1.1.3.4.5.3.1.3ColumntlpAtsConfigSourceTransferSetMinimumread-writecurrentThis value dictates the absolute lower limit by which tlpAtsConfigSource1TransferSet and tlpAtsConfigSource2TransferSet can be set. tlpAtsConfigLowVoltageReset…
1.3.6.1.4.1.850.1.1.3.4.5.3.1.4ColumntlpAtsConfigSourceTransferSetMaximumread-writecurrentThis value dictates the absolute upper limit by which tlpAtsConfigSource1TransferSet and tlpAtsConfigSource2TransferSet can be set. tlpAtsConfigSource1Brownout…
1.3.6.1.4.1.850.1.1.3.4.5.4TabletlpAtsConfigThresholdTablenot-accessiblecurrentThe configurable threshold options of each ats in device table. This is a sparse dependent table, and will contain some subset of devices that are atss. Not al…
1.3.6.1.4.1.850.1.1.3.4.5.4.1RowtlpAtsConfigThresholdEntrynot-accessiblecurrentAn entry containing configurable threshold options for a particular ats.
1.3.6.1.4.1.850.1.1.3.4.5.4.1.1ColumntlpAtsConfigOverCurrentThresholdread-writecurrentThe output current measurement at which an over current condition is reported. This value may not be supported on all models. If not supported, this value will…
1.3.6.1.4.1.850.1.1.3.4.5.4.1.2ColumntlpAtsConfigOverTemperatureThresholdread-writecurrentThe system temperature at which an over temperature condition is reported. This value may not be supported on all models. If not supported, this value will ret…
1.3.6.1.4.1.850.1.1.3.4.5.4.1.3ColumntlpAtsConfigOverVoltageThresholdread-writecurrentThe input voltage measurement at which an over voltage condition is reported. This value may not be supported on all models. If not supported, this value will …
1.3.6.1.4.1.850.1.1.3.4.5.4.1.4ColumntlpAtsConfigOverLoadThresholdread-writecurrentThe system load at which an overload condition is reported. This value may not be supported on all models. If not supported, this value will return ERROR_NO_SU…
1.3.6.1.4.1.850.1.1.3.5NodetlpCooling
1.3.6.1.4.1.850.1.1.3.5.1NodetlpCoolingIdent
1.3.6.1.4.1.850.1.1.3.5.1.1ScalartlpCoolingIdentNumCoolingread-onlycurrentThe number of cooling devices that this agent is currently managing.
1.3.6.1.4.1.850.1.1.3.5.2NodetlpCoolingDevice
1.3.6.1.4.1.850.1.1.3.5.3NodetlpCoolingDetail
1.3.6.1.4.1.850.1.1.3.5.3.1NodetlpCoolingInput
1.3.6.1.4.1.850.1.1.3.5.3.2NodetlpCoolingOutput
1.3.6.1.4.1.850.1.1.3.5.4NodetlpCoolingControl
1.3.6.1.4.1.850.1.1.3.5.5NodetlpCoolingConfig
1.3.6.1.4.1.850.1.1.3.6NodetlpKvm
1.3.6.1.4.1.850.1.1.3.6.1NodetlpKvmIdent
1.3.6.1.4.1.850.1.1.3.6.1.1ScalartlpKvmIdentNumKvmread-onlycurrentThe number of kvm devices that this agent is currently managing.
1.3.6.1.4.1.850.1.1.3.6.2NodetlpKvmDevice
1.3.6.1.4.1.850.1.1.3.6.3NodetlpKvmDetail
1.3.6.1.4.1.850.1.1.3.6.4NodetlpKvmControl
1.3.6.1.4.1.850.1.1.3.6.5NodetlpKvmConfig
1.3.6.1.4.1.850.1.1.3.7NodetlpRackTrack
1.3.6.1.4.1.850.1.1.3.7.1NodetlpRackTrackIdent
1.3.6.1.4.1.850.1.1.3.7.1.1ScalartlpRackTrackIdentNumRackTrackread-onlycurrentThe number of rack track devices that this agent is currently managing.
1.3.6.1.4.1.850.1.1.3.7.2NodetlpRackTrackDevice
1.3.6.1.4.1.850.1.1.3.7.3NodetlpRackTrackDetail
1.3.6.1.4.1.850.1.1.3.7.4NodetlpRackTrackControl
1.3.6.1.4.1.850.1.1.3.7.5NodetlpRackTrackConfig
1.3.6.1.4.1.850.1.1.3.8NodetlpSwitch
1.3.6.1.4.1.850.1.1.3.8.1NodetlpSwitchIdent
1.3.6.1.4.1.850.1.1.3.8.1.1ScalartlpSwitchIdentNumSwitchread-onlycurrentThe number of switch devices that this agent is currently managing.
1.3.6.1.4.1.850.1.1.3.8.2NodetlpSwitchDevice
1.3.6.1.4.1.850.1.1.3.8.3NodetlpSwitchDetail
1.3.6.1.4.1.850.1.1.3.8.4NodetlpSwitchControl
1.3.6.1.4.1.850.1.1.3.8.5NodetlpSwitchConfig
1.3.6.1.4.1.850.1.2NodetlpSoftware
1.3.6.1.4.1.850.1.2.1NodetlpAgentDetails
1.3.6.1.4.1.850.1.2.1.1NodetlpAgentIdent
1.3.6.1.4.1.850.1.2.1.1.1ScalartlpAgentTyperead-onlycurrentThe type of PowerAlert engine providing this data.
1.3.6.1.4.1.850.1.2.1.1.2ScalartlpAgentVersionread-onlycurrentThe version of the agent software.
1.3.6.1.4.1.850.1.2.1.1.3ScalartlpAgentDriverVersionread-onlycurrentThe driver version of the agent software.
1.3.6.1.4.1.850.1.2.1.1.4ScalartlpAgentMACread-onlycurrentThe MAC Address of the agent.
1.3.6.1.4.1.850.1.2.1.1.5ScalartlpAgentSerialNumread-onlycurrentSerial number of the web card providing the agent data. This value is only supported by a web card agent. PowerAlert for PC (PAL) agents do not support this va…
1.3.6.1.4.1.850.1.2.1.1.6ScalartlpAgentUuidread-onlycurrentUniversally unique identifier for this host in the form 8-4-4-4-12 for a total of 36 characters (32 alphanumeric characters and four hyphens). For example: 550…
1.3.6.1.4.1.850.1.2.1.2NodetlpAgentAttributes
1.3.6.1.4.1.850.1.2.1.2.1NodetlpAgentAttributesSupports
1.3.6.1.4.1.850.1.2.1.2.1.1ScalartlpAgentAttributesSupportsHTTPread-onlycurrentIndicates whether the agent supports HTTP connections.
1.3.6.1.4.1.850.1.2.1.2.1.2ScalartlpAgentAttributesSupportsHTTPSread-onlycurrentIndicates whether the agent supports HTTPS connections.
1.3.6.1.4.1.850.1.2.1.2.1.3ScalartlpAgentAttributesSupportsFTPread-onlycurrentIndicates whether the agent supports FTP connections.
1.3.6.1.4.1.850.1.2.1.2.1.4ScalartlpAgentAttributesSupportsTelnetMenuread-onlycurrentIndicates whether the agent supports Telnet menu connections.
1.3.6.1.4.1.850.1.2.1.2.1.5ScalartlpAgentAttributesSupportsTelnetCLIread-onlycurrentIndicates whether the agent supports Telnet CLI connections.
1.3.6.1.4.1.850.1.2.1.2.1.6ScalartlpAgentAttributesSupportsSSHMenuread-onlycurrentIndicates whether the agent supports SSH menu connections.
1.3.6.1.4.1.850.1.2.1.2.1.7ScalartlpAgentAttributesSupportsSSHCLIread-onlycurrentIndicates whether the agent supports SSH CLI connections.
1.3.6.1.4.1.850.1.2.1.2.1.8ScalartlpAgentAttributesSupportsSNMPread-onlycurrentIndicates whether the agent supports SNMP connections.
1.3.6.1.4.1.850.1.2.1.2.1.9ScalartlpAgentAttributesSupportsSNMPTrapread-onlycurrentIndicates whether the agent supports listening for SNMP traps. This is only applicable for network monitoring applications, PowerAlert Shutdown Agent for an ex…
1.3.6.1.4.1.850.1.2.1.2.2NodetlpAgentAttributesAutostart
1.3.6.1.4.1.850.1.2.1.2.2.1ScalartlpAgentAttributesAutostartHTTPread-onlycurrentIndicates whether the agent autostarts HTTP services.
1.3.6.1.4.1.850.1.2.1.2.2.2ScalartlpAgentAttributesAutostartHTTPSread-onlycurrentIndicates whether the agent autostarts HTTPS services.
1.3.6.1.4.1.850.1.2.1.2.2.3ScalartlpAgentAttributesAutostartFTPread-onlycurrentIndicates whether the agent autostarts FTP services.
1.3.6.1.4.1.850.1.2.1.2.2.4ScalartlpAgentAttributesAutostartTelnetMenuread-onlycurrentIndicates whether the agent autostarts Telnet menu services.
1.3.6.1.4.1.850.1.2.1.2.2.5ScalartlpAgentAttributesAutostartTelnetCLIread-onlycurrentIndicates whether the agent autostarts Telnet CLI services.
1.3.6.1.4.1.850.1.2.1.2.2.6ScalartlpAgentAttributesAutostartSSHMenuread-onlycurrentIndicates whether the agent autostarts SSH menu services.
1.3.6.1.4.1.850.1.2.1.2.2.7ScalartlpAgentAttributesAutostartSSHCLIread-onlycurrentIndicates whether the agent autostarts SSH CLI services.
1.3.6.1.4.1.850.1.2.1.2.2.8ScalartlpAgentAttributesAutostartSNMPread-onlycurrentIndicates whether the agent autostarts SNMP services.
1.3.6.1.4.1.850.1.2.1.2.3NodetlpAgentAttributesSnmp
1.3.6.1.4.1.850.1.2.1.2.3.1ScalartlpAgentAttributesSNMPv1Enabledread-onlycurrentIndicates whether the agent will allow SNMPv1 connections.
1.3.6.1.4.1.850.1.2.1.2.3.2ScalartlpAgentAttributesSNMPv2cEnabledread-onlycurrentIndicates whether the agent will allow SNMPv2c connections.
1.3.6.1.4.1.850.1.2.1.2.3.3ScalartlpAgentAttributesSNMPv3Enabledread-onlycurrentIndicates whether the agent will allow SNMPv3 connections.
1.3.6.1.4.1.850.1.2.1.2.4NodetlpAgentAttributesPorts
1.3.6.1.4.1.850.1.2.1.2.4.1ScalartlpAgentAttributesHTTPPortread-onlycurrentThe port used for HTTP communications.
1.3.6.1.4.1.850.1.2.1.2.4.2ScalartlpAgentAttributesHTTPSPortread-onlycurrentThe port used for HTTPS communications.
1.3.6.1.4.1.850.1.2.1.2.4.3ScalartlpAgentAttributesFTPPortread-onlycurrentThe port used for FTP communications.
1.3.6.1.4.1.850.1.2.1.2.4.4ScalartlpAgentAttributesTelnetMenuPortread-onlycurrentThe port used for Telnet Menu communications.
1.3.6.1.4.1.850.1.2.1.2.4.5ScalartlpAgentAttributesTelnetCLIPortread-onlycurrentThe port used for Telnet CLI communications.
1.3.6.1.4.1.850.1.2.1.2.4.6ScalartlpAgentAttributesSSHMenuPortread-onlycurrentThe port used for SSH Menu communications.
1.3.6.1.4.1.850.1.2.1.2.4.7ScalartlpAgentAttributesSSHCLIPortread-onlycurrentThe port used for SSH CLI communications.
1.3.6.1.4.1.850.1.2.1.2.4.8ScalartlpAgentAttributesSNMPPortread-onlycurrentThe port used for SNMP communications.
1.3.6.1.4.1.850.1.2.1.2.4.9ScalartlpAgentAttributesSNMPTrapPortread-onlycurrentThe port used for SNMP trap and notifications.
1.3.6.1.4.1.850.1.2.2NodetlpAgentSettings
1.3.6.1.4.1.850.1.2.2.1NodetlpAgentConfig
1.3.6.1.4.1.850.1.2.2.1.1ScalartlpAgentConfigRemoteRegistrationread-writecurrentRegisters an SNMP contact's IP address and the port on which the contact is listening for SNMP traps. Setting this value is used to CREATE a table entry in a n…
1.3.6.1.4.1.850.1.2.2.1.2ScalartlpAgentConfigCurrentTimeread-writecurrentThe current date and time of the system.
1.3.6.1.4.1.850.1.2.3NodetlpAgentContacts
1.3.6.1.4.1.850.1.2.3.1NodetlpAgentEmailContacts
1.3.6.1.4.1.850.1.2.3.1.1ScalartlpAgentNumEmailContactsread-onlycurrentThe number of email contacts currently defined in the agent.
1.3.6.1.4.1.850.1.2.3.1.2TabletlpAgentEmailContactTablenot-accessiblecurrentA list of email contact entries. The number of entries is given by the value of tlpAgentNumEmailContacts.
1.3.6.1.4.1.850.1.2.3.1.2.1RowtlpAgentEmailContactEntrynot-accessiblecurrentAn entry containing the details of an email contact.
1.3.6.1.4.1.850.1.2.3.1.2.1.1ColumntlpAgentEmailContactIndexread-onlycurrentThe table row index for the email contact.
1.3.6.1.4.1.850.1.2.3.1.2.1.2ColumntlpAgentEmailContactRowStatusread-writecurrentRow status for the tlpAgentEmailContactTable.
1.3.6.1.4.1.850.1.2.3.1.2.1.3ColumntlpAgentEmailContactNameread-writecurrentThe name of the email contact.
1.3.6.1.4.1.850.1.2.3.1.2.1.4ColumntlpAgentEmailContactAddressread-writecurrentThe address of the email contact.
1.3.6.1.4.1.850.1.2.3.2NodetlpAgentSnmpContacts
1.3.6.1.4.1.850.1.2.3.2.1ScalartlpAgentNumSnmpContactsread-onlycurrentThe number of SNMP contacts currently defined in the agent.
1.3.6.1.4.1.850.1.2.3.2.2TabletlpAgentSnmpContactTablenot-accessiblecurrentA list of SNMP contact entries. The number of entries is given by the value of tlpAgentNumSnmpContacts.
1.3.6.1.4.1.850.1.2.3.2.2.1RowtlpAgentSnmpContactEntrynot-accessiblecurrentAn entry containing the details of an SNMP contact.
1.3.6.1.4.1.850.1.2.3.2.2.1.1ColumntlpAgentSnmpContactIndexread-onlycurrentThe table row index for the SNMP contact.
1.3.6.1.4.1.850.1.2.3.2.2.1.2ColumntlpAgentSnmpContactRowStatusread-writecurrentRow status for the tlpAgentSnmpContactTable.
1.3.6.1.4.1.850.1.2.3.2.2.1.3ColumntlpAgentSnmpContactNameread-writecurrentThe name of the SNMP contact.
1.3.6.1.4.1.850.1.2.3.2.2.1.4ColumntlpAgentSnmpContactIpAddressread-writecurrentThe IP address of the SNMP contact.
1.3.6.1.4.1.850.1.2.3.2.2.1.5ColumntlpAgentSnmpContactPortread-writecurrentThe port of the SNMP contact.
1.3.6.1.4.1.850.1.2.3.2.2.1.6ColumntlpAgentSnmpContactSnmpVersionread-writecurrentThe SNMP contact version to use for sending traps.
1.3.6.1.4.1.850.1.2.3.2.2.1.7ColumntlpAgentSnmpContactSecurityNameread-writecurrentThe security name for the SNMP contact.
1.3.6.1.4.1.850.1.2.3.2.2.1.8ColumntlpAgentSnmpContactPrivPasswordread-writecurrentThe privacy password to use for sending V3 traps to the SNMP contact.
1.3.6.1.4.1.850.1.2.3.2.2.1.9ColumntlpAgentSnmpContactAuthPasswordread-writecurrentThe authentication password to use for sending V3 traps to the SNMP contact.
1.3.6.1.4.1.850.1.3NodetlpAlarms
1.3.6.1.4.1.850.1.3.1ScalartlpAlarmsPresentread-onlycurrentThe present number of active alarm conditions.
1.3.6.1.4.1.850.1.3.2TabletlpAlarmTablenot-accessiblecurrentA list of alarm conditions for all devices managed by this agent. This table contains zero, one, or many rows at any moment, depending upon the number of alarm…
1.3.6.1.4.1.850.1.3.2.1RowtlpAlarmEntrynot-accessiblecurrentAn entry containing information application to a particular alarm.
1.3.6.1.4.1.850.1.3.2.1.1ColumntlpAlarmIdread-onlycurrentA unique identifier for an alarm condition. This value will remain constant for the duration of the alarm condition.
1.3.6.1.4.1.850.1.3.2.1.2ColumntlpAlarmDescrread-onlycurrentA reference of the alarm description object. The object referenced should not be accessbile, but rather be used to provide a unique description for the alarm c…
1.3.6.1.4.1.850.1.3.2.1.3ColumntlpAlarmTimeread-onlycurrentThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag…
1.3.6.1.4.1.850.1.3.2.1.4ColumntlpAlarmTableRefread-onlycurrentThis value references the OID of a table object applicable to the alarm condition. This, in conjunction with the table row as defined by tlpAlarmTableRowRef, s…
1.3.6.1.4.1.850.1.3.2.1.5ColumntlpAlarmTableRowRefread-onlycurrentThis value is used in conjunction with tlpAlarmTableRef to define the object associated with this alarm condition. See the description of tlpAlarmTableRef for …
1.3.6.1.4.1.850.1.3.2.1.6ColumntlpAlarmDetailread-onlycurrentA textual description of the alarm condition.
1.3.6.1.4.1.850.1.3.2.1.7ColumntlpAlarmTyperead-onlycurrentThe category/group of this alarm.
1.3.6.1.4.1.850.1.3.2.1.8ColumntlpAlarmStateread-onlycurrentThe current state of this alarm condition. An active(1) alarm is a condition that currently exists. An inactive(2) alarm is a condition that no longer exists b…
1.3.6.1.4.1.850.1.3.2.1.9ColumntlpAlarmAcknowledgedread-writecurrentDenotes whether the alarm condition has been acknowledged. The agent will return notAcknowledged(1) if the condition has not been acknowledged, or acknowledged…
1.3.6.1.4.1.850.1.3.3NodetlpAlarmsWellKnown
1.3.6.1.4.1.850.1.3.3.1NodetlpAgentAlarms
1.3.6.1.4.1.850.1.3.3.2NodetlpDeviceAlarms
1.3.6.1.4.1.850.1.3.3.2.1IdentitytlpAlarmCommunicationsLostcurrentA problem has been encountered in the communications between the agent and the device.
1.3.6.1.4.1.850.1.3.3.2.2NodetlpAlarmUserDefined
1.3.6.1.4.1.850.1.3.3.2.2.1IdentitytlpAlarmUserDefined01currentUser-defined event 1 is in alarm.
1.3.6.1.4.1.850.1.3.3.2.2.2IdentitytlpAlarmUserDefined02currentUser-defined event 2 is in alarm.
1.3.6.1.4.1.850.1.3.3.2.2.3IdentitytlpAlarmUserDefined03currentUser-defined event 3 is in alarm.
1.3.6.1.4.1.850.1.3.3.2.2.4IdentitytlpAlarmUserDefined04currentUser-defined event 4 is in alarm.
1.3.6.1.4.1.850.1.3.3.2.2.5IdentitytlpAlarmUserDefined05currentUser-defined event 5 is in alarm.
1.3.6.1.4.1.850.1.3.3.2.2.6IdentitytlpAlarmUserDefined06currentUser-defined event 6 is in alarm.
1.3.6.1.4.1.850.1.3.3.2.2.7IdentitytlpAlarmUserDefined07currentUser-defined event 7 is in alarm.
1.3.6.1.4.1.850.1.3.3.2.2.8IdentitytlpAlarmUserDefined08currentUser-defined event 8 is in alarm.
1.3.6.1.4.1.850.1.3.3.2.2.9IdentitytlpAlarmUserDefined09currentUser-defined event 9 is in alarm.
1.3.6.1.4.1.850.1.3.3.3NodetlpUpsAlarms
1.3.6.1.4.1.850.1.3.3.3.1IdentitytlpUpsAlarmBatteryBadcurrentOne or more batteries have been determined to require replacement.
1.3.6.1.4.1.850.1.3.3.3.2IdentitytlpUpsAlarmOnBatterycurrentThe UPS is drawing power from the batteries.
1.3.6.1.4.1.850.1.3.3.3.3IdentitytlpUpsAlarmLowBatterycurrentThe remaining battery charge is less than or equal to the percentage of capacity warning specified by tlpUpsConfigBatteryCapacityThreshold.
1.3.6.1.4.1.850.1.3.3.3.4IdentitytlpUpsAlarmDepletedBatterycurrentThe UPS will be unable to sustain the present load when and if the utility power is lost.
1.3.6.1.4.1.850.1.3.3.3.5IdentitytlpUpsAlarmTempBadcurrentA temperature is out of tolerance.
1.3.6.1.4.1.850.1.3.3.3.6IdentitytlpUpsAlarmInputBadcurrentAn input condition is out of tolerance.
1.3.6.1.4.1.850.1.3.3.3.7IdentitytlpUpsAlarmOutputBadcurrentAn output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.850.1.3.3.3.8IdentitytlpUpsAlarmOutputOverloadcurrentThe output load exceeds the UPS output capacity.
1.3.6.1.4.1.850.1.3.3.3.9IdentitytlpUpsAlarmOnBypasscurrentThe Bypass is presently engaged on the UPS.
1.3.6.1.4.1.850.1.3.3.3.10IdentitytlpUpsAlarmBypassBadcurrentThe Bypass is out of tolerance.
1.3.6.1.4.1.850.1.3.3.3.11IdentitytlpUpsAlarmOutputOffAsRequestedcurrentThe UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.4.1.850.1.3.3.3.12IdentitytlpUpsAlarmUpsOffAsRequestedcurrentThe entire UPS has shutdown as commanded.
1.3.6.1.4.1.850.1.3.3.3.13IdentitytlpUpsAlarmChargerFailedcurrentAn uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.4.1.850.1.3.3.3.14IdentitytlpUpsAlarmUpsOutputOffcurrentThe output of the UPS is in the off state.
1.3.6.1.4.1.850.1.3.3.3.15IdentitytlpUpsAlarmUpsSystemOffcurrentThe UPS system is in the off state.
1.3.6.1.4.1.850.1.3.3.3.16IdentitytlpUpsAlarmFanFailurecurrentThe failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.850.1.3.3.3.17IdentitytlpUpsAlarmFuseFailurecurrentThe failure of one or more fuses has been detected.
1.3.6.1.4.1.850.1.3.3.3.18IdentitytlpUpsAlarmGeneralFaultcurrentA general fault in the UPS has been detected.
1.3.6.1.4.1.850.1.3.3.3.19IdentitytlpUpsAlarmDiagnosticTestFailedcurrentThe result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.850.1.3.3.3.20IdentitytlpUpsAlarmAwaitingPowercurrentThe UPS output is off and the UPS is awaiting the return of input power.
1.3.6.1.4.1.850.1.3.3.3.21IdentitytlpUpsAlarmShutdownPendingcurrentA tlpUpsShutdownAfterDelay countdown is underway.
1.3.6.1.4.1.850.1.3.3.3.22IdentitytlpUpsAlarmShutdownImminentcurrentThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.
1.3.6.1.4.1.850.1.3.3.3.23NodetlpUpsAlarmLoadLevelAboveThreshold
1.3.6.1.4.1.850.1.3.3.3.23.1IdentitytlpUpsAlarmLoadLevelAboveThresholdTotalcurrentThe total load level is above the designated threshold.
1.3.6.1.4.1.850.1.3.3.3.23.2IdentitytlpUpsAlarmLoadLevelAboveThresholdPhase1currentThe load level on phase 1 exceeds load limits.
1.3.6.1.4.1.850.1.3.3.3.23.3IdentitytlpUpsAlarmLoadLevelAboveThresholdPhase2currentThe load level on phase 2 exceeds load limits.
1.3.6.1.4.1.850.1.3.3.3.23.4IdentitytlpUpsAlarmLoadLevelAboveThresholdPhase3currentThe load level on phase 3 exceeds load limits.
1.3.6.1.4.1.850.1.3.3.3.24IdentitytlpUpsAlarmOutputCurrentChangedcurrentThe output current changed from its last known value.
1.3.6.1.4.1.850.1.3.3.3.25IdentitytlpUpsAlarmBatteryAgeAboveThresholdcurrentOne or more batteries have been determined to require replacement.
1.3.6.1.4.1.850.1.3.3.3.26NodetlpUpsAlarmLoadOff
1.3.6.1.4.1.850.1.3.3.3.26.1IdentitytlpUpsAlarmLoadOff01currentLoad 1 is off.
1.3.6.1.4.1.850.1.3.3.3.26.2IdentitytlpUpsAlarmLoadOff02currentLoad 2 is off.
1.3.6.1.4.1.850.1.3.3.3.26.3IdentitytlpUpsAlarmLoadOff03currentLoad 3 is off.
1.3.6.1.4.1.850.1.3.3.3.26.4IdentitytlpUpsAlarmLoadOff04currentLoad 4 is off.
1.3.6.1.4.1.850.1.3.3.3.26.5IdentitytlpUpsAlarmLoadOff05currentLoad 5 is off.
1.3.6.1.4.1.850.1.3.3.3.26.6IdentitytlpUpsAlarmLoadOff06currentLoad 6 is off.
1.3.6.1.4.1.850.1.3.3.3.26.7IdentitytlpUpsAlarmLoadOff07currentLoad 7 is off.
1.3.6.1.4.1.850.1.3.3.3.26.8IdentitytlpUpsAlarmLoadOff08currentLoad 8 is off.
1.3.6.1.4.1.850.1.3.3.3.26.9IdentitytlpUpsAlarmLoadOff09currentLoad 9 is off.
1.3.6.1.4.1.850.1.3.3.3.26.10IdentitytlpUpsAlarmLoadOff10currentLoad 10 is off.
1.3.6.1.4.1.850.1.3.3.3.26.11IdentitytlpUpsAlarmLoadOff11currentLoad 11 is off.
1.3.6.1.4.1.850.1.3.3.3.26.12IdentitytlpUpsAlarmLoadOff12currentLoad 12 is off.
1.3.6.1.4.1.850.1.3.3.3.26.13IdentitytlpUpsAlarmLoadOff13currentLoad 13 is off.
1.3.6.1.4.1.850.1.3.3.3.26.14IdentitytlpUpsAlarmLoadOff14currentLoad 14 is off.
1.3.6.1.4.1.850.1.3.3.3.26.15IdentitytlpUpsAlarmLoadOff15currentLoad 15 is off.
1.3.6.1.4.1.850.1.3.3.3.26.16IdentitytlpUpsAlarmLoadOff16currentLoad 16 is off.
1.3.6.1.4.1.850.1.3.3.3.26.17IdentitytlpUpsAlarmLoadOff17currentLoad 17 is off.
1.3.6.1.4.1.850.1.3.3.3.26.18IdentitytlpUpsAlarmLoadOff18currentLoad 18 is off.
1.3.6.1.4.1.850.1.3.3.3.26.19IdentitytlpUpsAlarmLoadOff19currentLoad 19 is off.
1.3.6.1.4.1.850.1.3.3.3.26.20IdentitytlpUpsAlarmLoadOff20currentLoad 20 is off.
1.3.6.1.4.1.850.1.3.3.3.26.21IdentitytlpUpsAlarmLoadOff21currentLoad 21 is off.
1.3.6.1.4.1.850.1.3.3.3.26.22IdentitytlpUpsAlarmLoadOff22currentLoad 22 is off.
1.3.6.1.4.1.850.1.3.3.3.26.23IdentitytlpUpsAlarmLoadOff23currentLoad 23 is off.
1.3.6.1.4.1.850.1.3.3.3.26.24IdentitytlpUpsAlarmLoadOff24currentLoad 24 is off.
1.3.6.1.4.1.850.1.3.3.3.26.25IdentitytlpUpsAlarmLoadOff25currentLoad 25 is off.
1.3.6.1.4.1.850.1.3.3.3.26.26IdentitytlpUpsAlarmLoadOff26currentLoad 26 is off.
1.3.6.1.4.1.850.1.3.3.3.26.27IdentitytlpUpsAlarmLoadOff27currentLoad 27 is off.
1.3.6.1.4.1.850.1.3.3.3.26.28IdentitytlpUpsAlarmLoadOff28currentLoad 28 is off.
1.3.6.1.4.1.850.1.3.3.3.26.29IdentitytlpUpsAlarmLoadOff29currentLoad 29 is off.
1.3.6.1.4.1.850.1.3.3.3.26.30IdentitytlpUpsAlarmLoadOff30currentLoad 30 is off.
1.3.6.1.4.1.850.1.3.3.3.26.31IdentitytlpUpsAlarmLoadOff31currentLoad 31 is off.
1.3.6.1.4.1.850.1.3.3.3.26.32IdentitytlpUpsAlarmLoadOff32currentLoad 32 is off.
1.3.6.1.4.1.850.1.3.3.3.26.33IdentitytlpUpsAlarmLoadOff33currentLoad 33 is off.
1.3.6.1.4.1.850.1.3.3.3.26.34IdentitytlpUpsAlarmLoadOff34currentLoad 34 is off.
1.3.6.1.4.1.850.1.3.3.3.26.35IdentitytlpUpsAlarmLoadOff35currentLoad 35 is off.
1.3.6.1.4.1.850.1.3.3.3.26.36IdentitytlpUpsAlarmLoadOff36currentLoad 36 is off.
1.3.6.1.4.1.850.1.3.3.3.26.37IdentitytlpUpsAlarmLoadOff37currentLoad 37 is off.
1.3.6.1.4.1.850.1.3.3.3.26.38IdentitytlpUpsAlarmLoadOff38currentLoad 38 is off.
1.3.6.1.4.1.850.1.3.3.3.26.39IdentitytlpUpsAlarmLoadOff39currentLoad 39 is off.
1.3.6.1.4.1.850.1.3.3.3.26.40IdentitytlpUpsAlarmLoadOff40currentLoad 40 is off.
1.3.6.1.4.1.850.1.3.3.3.27NodetlpUpsAlarmCurrentAboveThreshold
1.3.6.1.4.1.850.1.3.3.3.27.1IdentitytlpUpsAlarmCurrentAboveThreshold1currentThe output current on phase 1 exceeds load limits.
1.3.6.1.4.1.850.1.3.3.3.27.2IdentitytlpUpsAlarmCurrentAboveThreshold2currentThe output current on phase 2 exceeds load limits.
1.3.6.1.4.1.850.1.3.3.3.27.3IdentitytlpUpsAlarmCurrentAboveThreshold3currentThe output current on phase 3 exceeds load limits.
1.3.6.1.4.1.850.1.3.3.3.28IdentitytlpUpsAlarmRuntimeBelowWarningLevelcurrentThe battery seconds remaining is below warning level.
1.3.6.1.4.1.850.1.3.3.3.29IdentitytlpUpsAlarmBusStartVoltageLowcurrentThe inverter start up bus voltage is too low.
1.3.6.1.4.1.850.1.3.3.3.30IdentitytlpUpsAlarmBusOverVoltagecurrentThe inverter bus voltage is too high.
1.3.6.1.4.1.850.1.3.3.3.31IdentitytlpUpsAlarmBusUnderVoltagecurrentThe inverter bus voltage is too low.
1.3.6.1.4.1.850.1.3.3.3.32IdentitytlpUpsAlarmBusVoltageUnbalancedcurrentThe inverter bus voltage is not balanced.
1.3.6.1.4.1.850.1.3.3.3.33IdentitytlpUpsAlarmInverterSoftStartBadcurrentThe inverter bus voltage cannot reach desired voltage within a specified duration.
1.3.6.1.4.1.850.1.3.3.3.34IdentitytlpUpsAlarmInverterOverVoltagecurrentThe inverter voltage is too high.
1.3.6.1.4.1.850.1.3.3.3.35IdentitytlpUpsAlarmInverterUnderVoltagecurrentThe inverter voltage is too low.
1.3.6.1.4.1.850.1.3.3.3.36IdentitytlpUpsAlarmInverterCircuitBadcurrentThe inverter output is shorted.
1.3.6.1.4.1.850.1.3.3.3.37IdentitytlpUpsAlarmBatteryOverVoltagecurrentThe battery voltage is too high.
1.3.6.1.4.1.850.1.3.3.3.38IdentitytlpUpsAlarmBatteryUnderVoltagecurrentThe battery voltage is too low.
1.3.6.1.4.1.850.1.3.3.3.39IdentitytlpUpsAlarmSiteWiringFaultcurrentThe utility input wiring is faulty.
1.3.6.1.4.1.850.1.3.3.3.40IdentitytlpUpsAlarmOverTemperatureProtectioncurrentThe over temperature protection is activated.
1.3.6.1.4.1.850.1.3.3.3.41IdentitytlpUpsAlarmOverChargedcurrentThe UPS is over charged.
1.3.6.1.4.1.850.1.3.3.3.42IdentitytlpUpsAlarmEPOActivecurrentThe EPO is currently activate.
1.3.6.1.4.1.850.1.3.3.3.43IdentitytlpUpsAlarmBypassFrequencyBadcurrentThe bypass frequency is out of tolerance.
1.3.6.1.4.1.850.1.3.3.3.44IdentitytlpUpsAlarmExternalSmartBatteryAgeAboveThresholdcurrentOne or more external smart batteries have been determined to require replacement.
1.3.6.1.4.1.850.1.3.3.3.45IdentitytlpUpsAlarmExternalNonSmartBatteryAgeAboveThresholdcurrentOne or more external non-smart batteries have been determined to require replacement.
1.3.6.1.4.1.850.1.3.3.3.46IdentitytlpUpsAlarmSmartBatteryCommLostcurrentCommunications with the smart batteries was lost.
1.3.6.1.4.1.850.1.3.3.3.47IdentitytlpUpsAlarmLoadsNotAllOncurrentOne of more loads are not on.
1.3.6.1.4.1.850.1.3.3.4NodetlpPduAlarms
1.3.6.1.4.1.850.1.3.3.4.1IdentitytlpPduAlarmLoadLevelAboveThresholdcurrentThe load level is above the designated threshold.
1.3.6.1.4.1.850.1.3.3.4.2IdentitytlpPduAlarmInputBadcurrentAn input condition is out of tolerance.
1.3.6.1.4.1.850.1.3.3.4.3IdentitytlpPduAlarmOutputBadcurrentAn output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.850.1.3.3.4.4IdentitytlpPduAlarmOutputOverloadcurrentThe output load exceeds the pdu output capacity.
1.3.6.1.4.1.850.1.3.3.4.5IdentitytlpPduAlarmOutputOffcurrentThe output of the pdu is in the off state.
1.3.6.1.4.1.850.1.3.3.4.6NodetlpPduAlarmLoadOff
1.3.6.1.4.1.850.1.3.3.4.6.1IdentitytlpPduAlarmLoadOff01currentLoad 1 is off.
1.3.6.1.4.1.850.1.3.3.4.6.2IdentitytlpPduAlarmLoadOff02currentLoad 2 is off.
1.3.6.1.4.1.850.1.3.3.4.6.3IdentitytlpPduAlarmLoadOff03currentLoad 3 is off.
1.3.6.1.4.1.850.1.3.3.4.6.4IdentitytlpPduAlarmLoadOff04currentLoad 4 is off.
1.3.6.1.4.1.850.1.3.3.4.6.5IdentitytlpPduAlarmLoadOff05currentLoad 5 is off.
1.3.6.1.4.1.850.1.3.3.4.6.6IdentitytlpPduAlarmLoadOff06currentLoad 6 is off.
1.3.6.1.4.1.850.1.3.3.4.6.7IdentitytlpPduAlarmLoadOff07currentLoad 7 is off.
1.3.6.1.4.1.850.1.3.3.4.6.8IdentitytlpPduAlarmLoadOff08currentLoad 8 is off.
1.3.6.1.4.1.850.1.3.3.4.6.9IdentitytlpPduAlarmLoadOff09currentLoad 9 is off.
1.3.6.1.4.1.850.1.3.3.4.6.10IdentitytlpPduAlarmLoadOff10currentLoad 10 is off.
1.3.6.1.4.1.850.1.3.3.4.6.11IdentitytlpPduAlarmLoadOff11currentLoad 11 is off.
1.3.6.1.4.1.850.1.3.3.4.6.12IdentitytlpPduAlarmLoadOff12currentLoad 12 is off.
1.3.6.1.4.1.850.1.3.3.4.6.13IdentitytlpPduAlarmLoadOff13currentLoad 13 is off.
1.3.6.1.4.1.850.1.3.3.4.6.14IdentitytlpPduAlarmLoadOff14currentLoad 14 is off.
1.3.6.1.4.1.850.1.3.3.4.6.15IdentitytlpPduAlarmLoadOff15currentLoad 15 is off.
1.3.6.1.4.1.850.1.3.3.4.6.16IdentitytlpPduAlarmLoadOff16currentLoad 16 is off.
1.3.6.1.4.1.850.1.3.3.4.6.17IdentitytlpPduAlarmLoadOff17currentLoad 17 is off.
1.3.6.1.4.1.850.1.3.3.4.6.18IdentitytlpPduAlarmLoadOff18currentLoad 18 is off.
1.3.6.1.4.1.850.1.3.3.4.6.19IdentitytlpPduAlarmLoadOff19currentLoad 19 is off.
1.3.6.1.4.1.850.1.3.3.4.6.20IdentitytlpPduAlarmLoadOff20currentLoad 20 is off.
1.3.6.1.4.1.850.1.3.3.4.6.21IdentitytlpPduAlarmLoadOff21currentLoad 21 is off.
1.3.6.1.4.1.850.1.3.3.4.6.22IdentitytlpPduAlarmLoadOff22currentLoad 22 is off.
1.3.6.1.4.1.850.1.3.3.4.6.23IdentitytlpPduAlarmLoadOff23currentLoad 23 is off.
1.3.6.1.4.1.850.1.3.3.4.6.24IdentitytlpPduAlarmLoadOff24currentLoad 24 is off.
1.3.6.1.4.1.850.1.3.3.4.6.25IdentitytlpPduAlarmLoadOff25currentLoad 25 is off.
1.3.6.1.4.1.850.1.3.3.4.6.26IdentitytlpPduAlarmLoadOff26currentLoad 26 is off.
1.3.6.1.4.1.850.1.3.3.4.6.27IdentitytlpPduAlarmLoadOff27currentLoad 27 is off.
1.3.6.1.4.1.850.1.3.3.4.6.28IdentitytlpPduAlarmLoadOff28currentLoad 28 is off.
1.3.6.1.4.1.850.1.3.3.4.6.29IdentitytlpPduAlarmLoadOff29currentLoad 29 is off.
1.3.6.1.4.1.850.1.3.3.4.6.30IdentitytlpPduAlarmLoadOff30currentLoad 30 is off.
1.3.6.1.4.1.850.1.3.3.4.6.31IdentitytlpPduAlarmLoadOff31currentLoad 31 is off.
1.3.6.1.4.1.850.1.3.3.4.6.32IdentitytlpPduAlarmLoadOff32currentLoad 32 is off.
1.3.6.1.4.1.850.1.3.3.4.6.33IdentitytlpPduAlarmLoadOff33currentLoad 33 is off.
1.3.6.1.4.1.850.1.3.3.4.6.34IdentitytlpPduAlarmLoadOff34currentLoad 34 is off.
1.3.6.1.4.1.850.1.3.3.4.6.35IdentitytlpPduAlarmLoadOff35currentLoad 35 is off.
1.3.6.1.4.1.850.1.3.3.4.6.36IdentitytlpPduAlarmLoadOff36currentLoad 36 is off.
1.3.6.1.4.1.850.1.3.3.4.6.37IdentitytlpPduAlarmLoadOff37currentLoad 37 is off.
1.3.6.1.4.1.850.1.3.3.4.6.38IdentitytlpPduAlarmLoadOff38currentLoad 38 is off.
1.3.6.1.4.1.850.1.3.3.4.6.39IdentitytlpPduAlarmLoadOff39currentLoad 39 is off.
1.3.6.1.4.1.850.1.3.3.4.6.40IdentitytlpPduAlarmLoadOff40currentLoad 40 is off.
1.3.6.1.4.1.850.1.3.3.4.7NodetlpPduAlarmCircuitBreakerOpen
1.3.6.1.4.1.850.1.3.3.4.7.1IdentitytlpPduAlarmCircuitBreakerOpen01currentCircuit breaker 1 is open.
1.3.6.1.4.1.850.1.3.3.4.7.2IdentitytlpPduAlarmCircuitBreakerOpen02currentCircuit breaker 2 is open.
1.3.6.1.4.1.850.1.3.3.4.7.3IdentitytlpPduAlarmCircuitBreakerOpen03currentCircuit breaker 3 is open.
1.3.6.1.4.1.850.1.3.3.4.7.4IdentitytlpPduAlarmCircuitBreakerOpen04currentCircuit breaker 4 is open.
1.3.6.1.4.1.850.1.3.3.4.7.5IdentitytlpPduAlarmCircuitBreakerOpen05currentCircuit breaker 5 is open.
1.3.6.1.4.1.850.1.3.3.4.7.6IdentitytlpPduAlarmCircuitBreakerOpen06currentCircuit breaker 6 is open.
1.3.6.1.4.1.850.1.3.3.4.8NodetlpPduAlarmCurrentAboveThreshold
1.3.6.1.4.1.850.1.3.3.4.8.1IdentitytlpPduAlarmCurrentAboveThreshold1currentThe output current on phase 1 exceeds load limits.
1.3.6.1.4.1.850.1.3.3.4.8.2IdentitytlpPduAlarmCurrentAboveThreshold2currentThe output current on phase 2 exceeds load limits.
1.3.6.1.4.1.850.1.3.3.4.8.3IdentitytlpPduAlarmCurrentAboveThreshold3currentThe output current on phase 3 exceeds load limits.
1.3.6.1.4.1.850.1.3.3.4.9IdentitytlpPduAlarmLoadsNotAllOncurrentOne of more loads are not on.
1.3.6.1.4.1.850.1.3.3.5NodetlpEnvAlarms
1.3.6.1.4.1.850.1.3.3.5.1IdentitytlpEnvAlarmTemperatureBeyondLimitscurrentThe temperature exceeds limits.
1.3.6.1.4.1.850.1.3.3.5.2IdentitytlpEnvAlarmHumidityBeyondLimitscurrentThe humidity exceeds limits.
1.3.6.1.4.1.850.1.3.3.5.3NodetlpEnvAlarmInputContact
1.3.6.1.4.1.850.1.3.3.5.3.1IdentitytlpEnvAlarmInputContact01currentInput contact 1 is in alarm.
1.3.6.1.4.1.850.1.3.3.5.3.2IdentitytlpEnvAlarmInputContact02currentInput contact 2 is in alarm.
1.3.6.1.4.1.850.1.3.3.5.3.3IdentitytlpEnvAlarmInputContact03currentInput contact 3 is in alarm.
1.3.6.1.4.1.850.1.3.3.5.3.4IdentitytlpEnvAlarmInputContact04currentInput contact 4 is in alarm.
1.3.6.1.4.1.850.1.3.3.5.4NodetlpEnvAlarmOutputContact
1.3.6.1.4.1.850.1.3.3.5.4.1IdentitytlpEnvAlarmOutputContact01currentOutput contact 1 is in alarm.
1.3.6.1.4.1.850.1.3.3.5.4.2IdentitytlpEnvAlarmOutputContact02currentOutput contact 2 is in alarm.
1.3.6.1.4.1.850.1.3.3.5.4.3IdentitytlpEnvAlarmOutputContact03currentOutput contact 3 is in alarm.
1.3.6.1.4.1.850.1.3.3.5.4.4IdentitytlpEnvAlarmOutputContact04currentOutput contact 4 is in alarm.
1.3.6.1.4.1.850.1.3.3.6NodetlpAtsAlarms
1.3.6.1.4.1.850.1.3.3.6.1NodetlpAtsAlarmOutage
1.3.6.1.4.1.850.1.3.3.6.1.1IdentitytlpAtsAlarmSource1OutagecurrentInput on source 1 is not present. For atss with the designation of primary and secondary, this alarm denotes input on the primary source is not present.
1.3.6.1.4.1.850.1.3.3.6.1.2IdentitytlpAtsAlarmSource2OutagecurrentInput on source 2 is not present. For atss with the designation of primary and secondary, this alarm denotes input on the secondary source is not present.
1.3.6.1.4.1.850.1.3.3.6.2NodetlpAtsAlarmTemperature
1.3.6.1.4.1.850.1.3.3.6.2.1IdentitytlpAtsAlarmSystemTemperaturecurrentThe system temperature is out of tolerance.
1.3.6.1.4.1.850.1.3.3.6.2.2IdentitytlpAtsAlarmSource1TemperaturecurrentThe source 1 temperature is out of tolerance.
1.3.6.1.4.1.850.1.3.3.6.2.3IdentitytlpAtsAlarmSource2TemperaturecurrentThe source 2 temperature is out of tolerance.
1.3.6.1.4.1.850.1.3.3.6.3IdentitytlpAtsAlarmLoadLevelAboveThresholdcurrentThe load level is above the designated threshold.
1.3.6.1.4.1.850.1.3.3.6.4IdentitytlpAtsAlarmInputBadcurrentAn input condition is out of tolerance.
1.3.6.1.4.1.850.1.3.3.6.5IdentitytlpAtsAlarmOutputBadcurrentAn output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.850.1.3.3.6.6IdentitytlpAtsAlarmOutputOverloadcurrentThe output load exceeds the ats output capacity.
1.3.6.1.4.1.850.1.3.3.6.7IdentitytlpAtsAlarmOutputOffcurrentThe output of the ats is in the off state.
1.3.6.1.4.1.850.1.3.3.6.8NodetlpAtsAlarmLoadOff
1.3.6.1.4.1.850.1.3.3.6.8.1IdentitytlpAtsAlarmLoadOff01currentLoad 1 is off.
1.3.6.1.4.1.850.1.3.3.6.8.2IdentitytlpAtsAlarmLoadOff02currentLoad 2 is off.
1.3.6.1.4.1.850.1.3.3.6.8.3IdentitytlpAtsAlarmLoadOff03currentLoad 3 is off.
1.3.6.1.4.1.850.1.3.3.6.8.4IdentitytlpAtsAlarmLoadOff04currentLoad 4 is off.
1.3.6.1.4.1.850.1.3.3.6.8.5IdentitytlpAtsAlarmLoadOff05currentLoad 5 is off.
1.3.6.1.4.1.850.1.3.3.6.8.6IdentitytlpAtsAlarmLoadOff06currentLoad 6 is off.
1.3.6.1.4.1.850.1.3.3.6.8.7IdentitytlpAtsAlarmLoadOff07currentLoad 7 is off.
1.3.6.1.4.1.850.1.3.3.6.8.8IdentitytlpAtsAlarmLoadOff08currentLoad 8 is off.
1.3.6.1.4.1.850.1.3.3.6.8.9IdentitytlpAtsAlarmLoadOff09currentLoad 9 is off.
1.3.6.1.4.1.850.1.3.3.6.8.10IdentitytlpAtsAlarmLoadOff10currentLoad 10 is off.
1.3.6.1.4.1.850.1.3.3.6.8.11IdentitytlpAtsAlarmLoadOff11currentLoad 11 is off.
1.3.6.1.4.1.850.1.3.3.6.8.12IdentitytlpAtsAlarmLoadOff12currentLoad 12 is off.
1.3.6.1.4.1.850.1.3.3.6.8.13IdentitytlpAtsAlarmLoadOff13currentLoad 13 is off.
1.3.6.1.4.1.850.1.3.3.6.8.14IdentitytlpAtsAlarmLoadOff14currentLoad 14 is off.
1.3.6.1.4.1.850.1.3.3.6.8.15IdentitytlpAtsAlarmLoadOff15currentLoad 15 is off.
1.3.6.1.4.1.850.1.3.3.6.8.16IdentitytlpAtsAlarmLoadOff16currentLoad 16 is off.
1.3.6.1.4.1.850.1.3.3.6.8.17IdentitytlpAtsAlarmLoadOff17currentLoad 17 is off.
1.3.6.1.4.1.850.1.3.3.6.8.18IdentitytlpAtsAlarmLoadOff18currentLoad 18 is off.
1.3.6.1.4.1.850.1.3.3.6.8.19IdentitytlpAtsAlarmLoadOff19currentLoad 19 is off.
1.3.6.1.4.1.850.1.3.3.6.8.20IdentitytlpAtsAlarmLoadOff20currentLoad 20 is off.
1.3.6.1.4.1.850.1.3.3.6.8.21IdentitytlpAtsAlarmLoadOff21currentLoad 21 is off.
1.3.6.1.4.1.850.1.3.3.6.8.22IdentitytlpAtsAlarmLoadOff22currentLoad 22 is off.
1.3.6.1.4.1.850.1.3.3.6.8.23IdentitytlpAtsAlarmLoadOff23currentLoad 23 is off.
1.3.6.1.4.1.850.1.3.3.6.8.24IdentitytlpAtsAlarmLoadOff24currentLoad 24 is off.
1.3.6.1.4.1.850.1.3.3.6.8.25IdentitytlpAtsAlarmLoadOff25currentLoad 25 is off.
1.3.6.1.4.1.850.1.3.3.6.8.26IdentitytlpAtsAlarmLoadOff26currentLoad 26 is off.
1.3.6.1.4.1.850.1.3.3.6.8.27IdentitytlpAtsAlarmLoadOff27currentLoad 27 is off.
1.3.6.1.4.1.850.1.3.3.6.8.28IdentitytlpAtsAlarmLoadOff28currentLoad 28 is off.
1.3.6.1.4.1.850.1.3.3.6.8.29IdentitytlpAtsAlarmLoadOff29currentLoad 29 is off.
1.3.6.1.4.1.850.1.3.3.6.8.30IdentitytlpAtsAlarmLoadOff30currentLoad 30 is off.
1.3.6.1.4.1.850.1.3.3.6.8.31IdentitytlpAtsAlarmLoadOff31currentLoad 31 is off.
1.3.6.1.4.1.850.1.3.3.6.8.32IdentitytlpAtsAlarmLoadOff32currentLoad 32 is off.
1.3.6.1.4.1.850.1.3.3.6.8.33IdentitytlpAtsAlarmLoadOff33currentLoad 33 is off.
1.3.6.1.4.1.850.1.3.3.6.8.34IdentitytlpAtsAlarmLoadOff34currentLoad 34 is off.
1.3.6.1.4.1.850.1.3.3.6.8.35IdentitytlpAtsAlarmLoadOff35currentLoad 35 is off.
1.3.6.1.4.1.850.1.3.3.6.8.36IdentitytlpAtsAlarmLoadOff36currentLoad 36 is off.
1.3.6.1.4.1.850.1.3.3.6.8.37IdentitytlpAtsAlarmLoadOff37currentLoad 37 is off.
1.3.6.1.4.1.850.1.3.3.6.8.38IdentitytlpAtsAlarmLoadOff38currentLoad 38 is off.
1.3.6.1.4.1.850.1.3.3.6.8.39IdentitytlpAtsAlarmLoadOff39currentLoad 39 is off.
1.3.6.1.4.1.850.1.3.3.6.8.40IdentitytlpAtsAlarmLoadOff40currentLoad 40 is off.
1.3.6.1.4.1.850.1.3.3.6.9NodetlpAtsAlarmCircuitBreakerOpen
1.3.6.1.4.1.850.1.3.3.6.9.1IdentitytlpAtsAlarmCircuitBreakerOpen01currentCircuit breaker 1 is open.
1.3.6.1.4.1.850.1.3.3.6.9.2IdentitytlpAtsAlarmCircuitBreakerOpen02currentCircuit breaker 2 is open.
1.3.6.1.4.1.850.1.3.3.6.9.3IdentitytlpAtsAlarmCircuitBreakerOpen03currentCircuit breaker 3 is open.
1.3.6.1.4.1.850.1.3.3.6.9.4IdentitytlpAtsAlarmCircuitBreakerOpen04currentCircuit breaker 4 is open.
1.3.6.1.4.1.850.1.3.3.6.9.5IdentitytlpAtsAlarmCircuitBreakerOpen05currentCircuit breaker 5 is open.
1.3.6.1.4.1.850.1.3.3.6.9.6IdentitytlpAtsAlarmCircuitBreakerOpen06currentCircuit breaker 6 is open.
1.3.6.1.4.1.850.1.3.3.6.10NodetlpAtsAlarmCurrentAboveThreshold
1.3.6.1.4.1.850.1.3.3.6.10.1IdentitytlpAtsAlarmCurrentAboveThresholdA1currentThe output current on input source 1 phase 1 exceeds load limits.
1.3.6.1.4.1.850.1.3.3.6.10.2IdentitytlpAtsAlarmCurrentAboveThresholdA2currentThe output current on input source 1 phase 2 exceeds load limits.
1.3.6.1.4.1.850.1.3.3.6.10.3IdentitytlpAtsAlarmCurrentAboveThresholdA3currentThe output current on input source 1 phase 3 exceeds load limits.
1.3.6.1.4.1.850.1.3.3.6.10.4IdentitytlpAtsAlarmCurrentAboveThresholdB1currentThe output current on input source 2 phase 1 exceeds load limits.
1.3.6.1.4.1.850.1.3.3.6.10.5IdentitytlpAtsAlarmCurrentAboveThresholdB2currentThe output current on input source 2 phase 2 exceeds load limits.
1.3.6.1.4.1.850.1.3.3.6.10.6IdentitytlpAtsAlarmCurrentAboveThresholdB3currentThe output current on input source 2 phase 3 exceeds load limits.
1.3.6.1.4.1.850.1.3.3.6.11IdentitytlpAtsAlarmLoadsNotAllOncurrentOne of more loads are not on.
1.3.6.1.4.1.850.1.3.3.6.12IdentitytlpAtsAlarmGeneralFaultcurrentA general fault in the ats has been detected.
1.3.6.1.4.1.850.1.3.3.6.13NodetlpAtsAlarmVoltage
1.3.6.1.4.1.850.1.3.3.6.13.1IdentitytlpAtsAlarmOverVoltagecurrentThe input voltage is out of tolerance.
1.3.6.1.4.1.850.1.3.3.6.13.2IdentitytlpAtsAlarmSource1OverVoltagecurrentThe voltage on source 1 is out of tolerance.
1.3.6.1.4.1.850.1.3.3.6.13.3IdentitytlpAtsAlarmSource2OverVoltagecurrentThe voltage on source 2 is out of tolerance.
1.3.6.1.4.1.850.1.3.3.6.14NodetlpAtsAlarmFrequency
1.3.6.1.4.1.850.1.3.3.6.14.1IdentitytlpAtsAlarmSource1InvalidFrequencycurrentThe voltage on source 1 is out of tolerance.
1.3.6.1.4.1.850.1.3.3.6.14.2IdentitytlpAtsAlarmSource2InvalidFrequencycurrentThe voltage on source 2 is out of tolerance.
1.3.6.1.4.1.850.1.3.3.7NodetlpCoolingAlarms
1.3.6.1.4.1.850.1.3.3.7.1IdentitytlpCoolingAlarmSupplyAirSensorFaultcurrentThe supply air sensor is in fault.
1.3.6.1.4.1.850.1.3.3.7.2IdentitytlpCoolingAlarmReturnAirSensorFaultcurrentThe return air sensor is in fault.
1.3.6.1.4.1.850.1.3.3.7.3IdentitytlpCoolingAlarmCondenserInletAirSensorFaultcurrentThe condenser inlet air sensor is in fault.
1.3.6.1.4.1.850.1.3.3.7.4IdentitytlpCoolingAlarmCondenserOutletAirSensorFaultcurrentThe condenser outlet air sensor is in fault.
1.3.6.1.4.1.850.1.3.3.7.5IdentitytlpCoolingAlarmSuctionTemperatureSensorFaultcurrentThe suction temperature sensor is in fault.
1.3.6.1.4.1.850.1.3.3.7.6IdentitytlpCoolingAlarmEvaporatorTemperatureSensorFaultcurrentThe evaporator temperature sensor is in fault.
1.3.6.1.4.1.850.1.3.3.7.7IdentitytlpCoolingAlarmAirFilterCloggedcurrentThe air filter is clogged.
1.3.6.1.4.1.850.1.3.3.7.8IdentitytlpCoolingAlarmAirFilterRunHoursViolationcurrentThe air filter run hours was violated.
1.3.6.1.4.1.850.1.3.3.7.9IdentitytlpCoolingAlarmSuctionPressureSensorFaultcurrentThe suction pressure sensor is in fault.
1.3.6.1.4.1.850.1.3.3.7.10IdentitytlpCoolingAlarmInverterCommunicationsFaultcurrentThe inverter communications is in fault.
1.3.6.1.4.1.850.1.3.3.7.11IdentitytlpCoolingAlarmRemoteShutdownViaInputContactcurrentA remote shutdown was triggerd by an input contact.
1.3.6.1.4.1.850.1.3.3.7.12IdentitytlpCoolingAlarmCondensatePumpFaultcurrentThe condensate pump is in fault.
1.3.6.1.4.1.850.1.3.3.7.13IdentitytlpCoolingAlarmLowRefrigerantStartupFaultcurrentThe low refrigerant startup is in fault.
1.3.6.1.4.1.850.1.3.3.7.14IdentitytlpCoolingAlarmCondenserFanFaultcurrentThe condenser fan is in fault.
1.3.6.1.4.1.850.1.3.3.7.15IdentitytlpCoolingAlarmCondenserFailurecurrentThe condenser has failed.
1.3.6.1.4.1.850.1.3.3.7.16IdentitytlpCoolingAlarmEvaporatorCoolingFailurecurrentThe evaporator cooling is in fault.
1.3.6.1.4.1.850.1.3.3.7.17IdentitytlpCoolingAlarmReturnAirTempHighcurrentThe return air temperature is high.
1.3.6.1.4.1.850.1.3.3.7.18IdentitytlpCoolingAlarmSupplyAirTempHighcurrentThe supply air temperature is high.
1.3.6.1.4.1.850.1.3.3.7.19IdentitytlpCoolingAlarmEvaporatorFailurecurrentThe evaporator has failed.
1.3.6.1.4.1.850.1.3.3.7.20IdentitytlpCoolingAlarmEvaporatorFreezeUpcurrentThe evaporator is frozen.
1.3.6.1.4.1.850.1.3.3.7.21IdentitytlpCoolingAlarmDischargePressureHighcurrentThe discharge pressure is high.
1.3.6.1.4.1.850.1.3.3.7.22IdentitytlpCoolingAlarmPressureGaugeFailurecurrentThe pressure gauge has failed.
1.3.6.1.4.1.850.1.3.3.7.23IdentitytlpCoolingAlarmDischargePressurePersistentHighcurrentThe discharge pressure is persistently high.
1.3.6.1.4.1.850.1.3.3.7.24IdentitytlpCoolingAlarmSuctionPressureLowStartFailurecurrentCannot start due to low suction pressure.
1.3.6.1.4.1.850.1.3.3.7.25IdentitytlpCoolingAlarmSuctionPressureLowcurrentThe suction pressure is low.
1.3.6.1.4.1.850.1.3.3.7.26IdentitytlpCoolingAlarmSuctionPressurePersistentLowcurrentThe suction pressure is persistently low.
1.3.6.1.4.1.850.1.3.3.7.27IdentitytlpCoolingAlarmStartupLinePressureImbalancecurrentThe startup line pressure is in imbalance.
1.3.6.1.4.1.850.1.3.3.7.28IdentitytlpCoolingAlarmCompressorFailurecurrentThe compressor has failed.
1.3.6.1.4.1.850.1.3.3.7.29IdentitytlpCoolingAlarmCurrentLimitcurrentThe current is out of range.
1.3.6.1.4.1.850.1.3.3.7.30IdentitytlpCoolingAlarmWaterLeakcurrentWater is leaking.
1.3.6.1.4.1.850.1.3.3.7.31IdentitytlpCoolingAlarmFanUnderCurrentcurrentThe fan is under current.
1.3.6.1.4.1.850.1.3.3.7.32IdentitytlpCoolingAlarmFanOverCurrentcurrentThe fan is over current.
1.3.6.1.4.1.850.1.3.3.7.33IdentitytlpCoolingAlarmDischargePressureSensorFaultcurrentThe discharge pressure sensor is in fault.
1.3.6.1.4.1.850.1.3.3.7.34IdentitytlpCoolingAlarmWaterFullcurrentWater is Full.
1.3.6.1.4.1.850.1.3.3.7.35IdentitytlpCoolingAlarmAutoCoolingOncurrentAutomatic cooling was activated to lower the temperature below the remote set point.
1.3.6.1.4.1.850.1.3.3.7.36IdentitytlpCoolingAlarmPowerButtonPressedcurrentPower button was pressed on the front panel.
1.3.6.1.4.1.850.1.3.3.7.37IdentitytlpCoolingAlarmDisconnectedFromDevicecurrentThe device communications is disconnected.
1.3.6.1.4.1.850.1.3.3.8NodetlpKvmAlarms
1.3.6.1.4.1.850.1.3.3.9NodetlpRackTrackAlarms
1.3.6.1.4.1.850.1.3.3.10NodetlpSwitchAlarms
1.3.6.1.4.1.850.1.3.4NodetlpAlarmControl
1.3.6.1.4.1.850.1.3.4.1TabletlpAlarmControlTablenot-accessiblecurrentA list of alarm conditions supported for each device managed by this agent. This table contains zero, one, or many rows depending upon the number of available …
1.3.6.1.4.1.850.1.3.4.1.1RowtlpAlarmControlEntrynot-accessiblecurrentAn entry containing details for a particular alarm condition.
1.3.6.1.4.1.850.1.3.4.1.1.1ColumntlpAlarmControlIndexread-onlycurrentThe table row index for this alarm control entry for this device. The index of any one row represents the index of the alarm entry within the agent system. As …
1.3.6.1.4.1.850.1.3.4.1.1.2ColumntlpAlarmControlDescrread-onlycurrentA reference of the alarm description object. The object referenced should not be accessbile, but rather be used to provide a unique description for the alarm c…
1.3.6.1.4.1.850.1.3.4.1.1.3ColumntlpAlarmControlDetailread-onlycurrentA textual description of the alarm condition. This will be the same textual description of an alarm when in alarm as referenced by tlpAlarmDetail.
1.3.6.1.4.1.850.1.3.4.1.1.4ColumntlpAlarmControlSeverityread-writecurrentThe severity of this alarm, which can be configured as desired for each alarm condition. This will be the same severity used when in alarm as referenced by tlp…
1.3.6.1.4.1.850.1.4NodetlpNotify
1.3.6.1.4.1.850.1.4.1NodetlpNotifications
1.3.6.1.4.1.850.1.4.1.1NotificationtlpNotificationsAlarmEntryAddedcurrentThis notification is sent each time an alarm condition is inserted into the device alarm table, tlpAlarmTable.
1.3.6.1.4.1.850.1.4.1.2NotificationtlpNotificationsAlarmEntryRemovedcurrentThis notification is sent each time an alarm condition is removed from the device alarm table, tlpAlarmTable.
1.3.6.1.4.1.850.1.4.1.3NotificationtlpNotifySystemStartupcurrentUsed to inform another entity of an agent's startup. The varbinds that follow are: OBJ1 = tlpAgentType Obj1Value = The type of engine providing this data OBJ2 …
1.3.6.1.4.1.850.1.4.1.4NotificationtlpNotifySystemShutdowncurrentUsed to inform another entity of an agent's shutdown. The varbinds that follow are: OBJ1 = tlpAgentType Obj1Value = The type of engine providing this data OBJ2…
1.3.6.1.4.1.850.1.4.1.5NotificationtlpNotifySystemUpdatecurrentUsed to inform another entity of an engine's startup. The varbinds that follow are: OBJ1 = tlpAgentType Obj1Value = The type of engine providing this data OBJ2…