MIB Viewer

TRIPPUPS1-MIB

93 objects
No module-level DESCRIPTION found.
Imported Objects
RFC-1215TRAP-TYPE
RFC1155-SMICounter enterprises Gauge IpAddress NetworkAddress OBJECT-TYPE TimeTicks
RFC1213-MIBDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.850Nodetripplite
1.3.6.1.4.1.850.1NodetrippUPS1
1.3.6.1.4.1.850.1.1Nodeups
1.3.6.1.4.1.850.1.1.1NodeupsIdent
1.3.6.1.4.1.850.1.1.1.1ScalarupsIdentManufacturerread-onlymandatoryThe name of the UPS manufacturer.
1.3.6.1.4.1.850.1.1.1.2ScalarupsIdentModelread-onlymandatoryThe UPS Model designation.
1.3.6.1.4.1.850.1.1.1.3ScalarupsIdentUPSSoftwareVersionread-onlymandatoryThe UPS Firmware software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.
1.3.6.1.4.1.850.1.1.1.4ScalarupsIdentAgentSoftwareVersionread-onlymandatoryThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.
1.3.6.1.4.1.850.1.1.1.5ScalarupsIdentNameread-writemandatoryA string identifying the UPS. This object should be set by the administrator.
1.3.6.1.4.1.850.1.1.1.6ScalarupsIdentAttachedDevicesread-writemandatoryA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.
1.3.6.1.4.1.850.1.1.2NodeupsBattery
1.3.6.1.4.1.850.1.1.2.1ScalarupsBatteryStatusread-onlymandatoryThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the batteries are fully charged. A value of bat…
1.3.6.1.4.1.850.1.1.2.2ScalarupsSecondsOnBatteryread-onlymandatoryIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.850.1.1.2.3ScalarupsEstimatedMinutesRemainingread-onlymandatoryAn estimate of the time to battery charge depletion under the present load conditions if the utility power were to be lost and remain off. UNITS - minutes
1.3.6.1.4.1.850.1.1.2.4ScalarupsBatteryChargeRemainingread-onlymandatoryThe estimate of the battery charge remaining expressed as a percent of full charge.
1.3.6.1.4.1.850.1.1.2.5ScalarupsBatteryVoltageread-onlymandatoryThe magnitude of the present battery voltage. UNITS 0.1 Volt DC.
1.3.6.1.4.1.850.1.1.2.7ScalarupsBatteryTemperatureread-onlymandatoryThe ambient temperature at or near the UPS Battery. UNITS degrees Centigrade
1.3.6.1.4.1.850.1.1.3NodeupsInput
1.3.6.1.4.1.850.1.1.3.1ScalarupsInputFrequencyread-onlymandatoryThe present input frequency. UNITS 0.1 Hertz
1.3.6.1.4.1.850.1.1.3.2ScalarupsInputLineBadsread-onlymandatoryA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer.
1.3.6.1.4.1.850.1.1.3.3ScalarupsInputNumLinesread-onlymandatoryThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.
1.3.6.1.4.1.850.1.1.3.4ScalarupsInputVoltread-onlymandatoryThe magnitude of the present input voltage. UNITS RMS Volts
1.3.6.1.4.1.850.1.1.3.5TableupsInputTablenot-accessiblemandatoryA list of input table entries. The number of entries is given by the value of upsInputNumLines.
1.3.6.1.4.1.850.1.1.3.5.1RowupsInputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.850.1.1.3.5.1.1ColumnupsInputLineIndexread-onlymandatoryThe input line identifier.
1.3.6.1.4.1.850.1.1.3.5.1.2ColumnupsInputVoltageread-onlymandatoryThe magnitude of the present input voltage. UNITS RMS Volts
1.3.6.1.4.1.850.1.1.4NodeupsOutput
1.3.6.1.4.1.850.1.1.4.1ScalarupsOutputSourceread-onlymandatoryThe present source of output power.
1.3.6.1.4.1.850.1.1.4.2ScalarupsOutputFrequencyread-onlymandatoryThe present output frequency. UNITS 0.1 Hertz
1.3.6.1.4.1.850.1.1.4.3ScalarupsOutputNumLinesread-onlymandatoryThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.
1.3.6.1.4.1.850.1.1.4.4ScalarupsOutputPercLoadread-onlymandatoryThe percentage of true power capacity presently being used. UNITS percent
1.3.6.1.4.1.850.1.1.4.5TableupsOutputTablenot-accessiblemandatoryA list of output table entries. The number of entries is given by the value of upsOutputNumLines.
1.3.6.1.4.1.850.1.1.4.5.1RowupsOutputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output line.
1.3.6.1.4.1.850.1.1.4.5.1.1ColumnupsOutputLineIndexread-onlymandatoryThe output line identifier.
1.3.6.1.4.1.850.1.1.4.5.1.2ColumnupsOutputVoltageread-onlymandatoryThe present output voltage. UNITS RMS Volts
1.3.6.1.4.1.850.1.1.4.5.1.3ColumnupsOutputCurrentread-onlymandatoryThe present output mandatory. UNITS 0.1 Amp
1.3.6.1.4.1.850.1.1.4.5.1.4ColumnupsOutputPowerread-onlymandatoryThe present output true power. UNITS Watts
1.3.6.1.4.1.850.1.1.4.5.1.5ColumnupsOutputPercentLoadread-onlymandatoryThe percentage of true power capacity presently being used. UNITS percent
1.3.6.1.4.1.850.1.1.6NodeupsAlarm
1.3.6.1.4.1.850.1.1.6.1ScalarupsAlarmsPresentread-onlymandatoryThe present number of active alarm conditions.
1.3.6.1.4.1.850.1.1.6.2ScalarupsAlarmIDread-onlymandatoryA unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.4.1.850.1.1.6.3ScalarupsAlarmDESCRread-onlymandatoryA reference to an alarm description object. The object references should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.850.1.1.6.4TableupsAlarmTablenot-accessiblemandatoryA list of alarm table entries. The table consists of zero, one, or may rows at any moment, depending upon the number of alarm conditions in effect. The table i…
1.3.6.1.4.1.850.1.1.6.4.1RowupsAlarmEntrynot-accessiblemandatoryAn entry containing information applicable to a particular alarm.
1.3.6.1.4.1.850.1.1.6.4.1.1ColumnupsAlarmIdread-onlymandatoryA unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.4.1.850.1.1.6.4.1.2ColumnupsAlarmDescrread-onlymandatoryA reference to an alarm description object. The object references should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.850.1.1.6.4.1.3ColumnupsAlarmTimeread-onlymandatoryThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumable existed before ag…
1.3.6.1.4.1.850.1.1.7NodeupsWellKnownAlarms
1.3.6.1.4.1.850.1.1.7.1ScalarupsAlarmBatteryBadread-onlymandatoryOne or more batteries have been determined to require replacement.
1.3.6.1.4.1.850.1.1.7.2ScalarupsAlarmOnBatteryread-onlymandatoryThe UPS is drawing power from the batteries.
1.3.6.1.4.1.850.1.1.7.3ScalarupsAlarmLowBatteryread-onlymandatoryThe remaining battery run-time is less than or equal to upsConfigMinutesRemaining.
1.3.6.1.4.1.850.1.1.7.4ScalarupsAlarmDepletedBatteryread-onlymandatoryThe UPS will be unable to sustain the present load when and if the utility power is lost.
1.3.6.1.4.1.850.1.1.7.5ScalarupsAlarmTempBadread-onlymandatoryA temperature is out of tolerance.
1.3.6.1.4.1.850.1.1.7.6ScalarupsAlarmOutputOverloadread-onlymandatoryThe output load exceeds the UPS output capacity.
1.3.6.1.4.1.850.1.1.7.7ScalarupsAlarmOutputOffAsRequestedread-onlymandatoryThe UPS has shutdown as commanded, i.e., the output is off.
1.3.6.1.4.1.850.1.1.7.8ScalarupsAlarmUpsOutputOffread-onlymandatoryThe UPS is in the off state.
1.3.6.1.4.1.850.1.1.7.9ScalarupsAlarmDiagnosticTestFailedread-onlymandatoryThe result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.850.1.1.7.10ScalarupsAlarmCommunicationsLostread-onlymandatoryA problem has been encountered in the communications between the agent and the UPS.
1.3.6.1.4.1.850.1.1.7.11ScalarupsAlarmShutdownPendingread-onlymandatoryA upsShutdownAfterDelay countdown is underway.
1.3.6.1.4.1.850.1.1.7.12ScalarupsAlarmShutdownImminentread-onlymandatoryA upsShutdownAfterDelay countdown is underway.
1.3.6.1.4.1.850.1.1.7.13ScalarupsAlarmTestInProgressread-onlymandatoryA upsShutdownAfterDelay countdown is underway.
1.3.6.1.4.1.850.1.1.8NodeupsTest
1.3.6.1.4.1.850.1.1.8.1ScalarupsTestIdread-writemandatoryThe test named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of test, including the well known tests identified in this document…
1.3.6.1.4.1.850.1.1.8.2ScalarupsTestResultsSummaryread-onlymandatoryThe results of the mandatory or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) are self-documenting. The val…
1.3.6.1.4.1.850.1.1.9NodeupsControl
1.3.6.1.4.1.850.1.1.9.1ScalarupsShutdownTyperead-writemandatorySetting this object will start the output after the indicated number of seconds. Setting this object to 0 will cause the UPS to start the output immediately. I…
1.3.6.1.4.1.850.1.1.9.2ScalarupsShutdownAfterDelayread-writemandatorySetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShhutdownType at the time of shutd…
1.3.6.1.4.1.850.1.1.9.3ScalarupsStartupAfterDelayread-writemandatorySetting this object will start the output after the indicated number of seconds, includeing starting the UPS, if necessary. Setting this object to 0 will cause…
1.3.6.1.4.1.850.1.1.9.4ScalarupsRebootDurationread-writemandatorySetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of the upsShutdownType at th…
1.3.6.1.4.1.850.1.1.9.5ScalarupsAutoRestartread-writemandatorySetting this object to 'on' will cause the UPS system to restart after a shutdown if/when utility power is present.
1.3.6.1.4.1.850.1.1.10NodeupsConfig
1.3.6.1.4.1.850.1.1.10.11ScalarupsConfigInputVoltageHighread-writemandatoryIf the value of the input voltage (in Volts) exceeds this value, a utilityVoltageHigh trap will be triggered.
1.3.6.1.4.1.850.1.1.10.12ScalarupsConfigInputVoltageLowread-writemandatoryIf the value of the input voltage (in Volts) falls below this value, a utilityVoltageLow trap will be triggered.
1.3.6.1.4.1.850.1.1.10.13ScalarupsConfigOutputPercLoadHighread-writemandatoryIf the value of the output percent load exceeds this value, a upsOverload trap will be triggered.
1.3.6.1.4.1.850.1.1.10.14ScalarupsConfigBatteryPercLowread-writemandatoryIf the value of the battery percent capacity falls below this value, a lowBattery trap will be triggered.
1.3.6.1.4.1.850.1.1.10.15ScalarupsConfigBatteryTemperatureHighread-writemandatoryIf the value of the battery temperature exceeds this value, a batteryTemperatureHigh trap will be triggered.
1.3.6.1.4.1.850.5NodeupsOnBatteryThe UPS is on battery.
1.3.6.1.4.1.850.6NodepowerRestoredUtility power has been restored.
1.3.6.1.4.1.850.7NodelowBatteryThe UPS batteries are low and will soon be exhausted.
1.3.6.1.4.1.850.8NodereturnFromLowBatteryThe UPS has returned from a low battery condition.
1.3.6.1.4.1.850.9NodecommunicationEstablishedCommunication with the UPS has been established. This trap will be sent each time there is a transition from a power off condition to a power on condition.
1.3.6.1.4.1.850.10NodecommunicationLostCommunication with the UPS has been lost.
1.3.6.1.4.1.850.11NodeupsOverloadThe UPS has sensed a load greater than the value of the upsConfigOutputPercLoadHigh MIB variable.
1.3.6.1.4.1.850.12NodeupsDiagnosticsFailedThe UPS failed its self-test.
1.3.6.1.4.1.850.13NodeupsDiagnosticsPassedThe UPS passed its internal self-test.
1.3.6.1.4.1.850.14NodeutilityVoltageHighThe UPS input voltage greater than or equal to the value of the upsConfigInputVoltageHigh MIB variable.
1.3.6.1.4.1.850.15NodeutilityVoltageLowThe UPS input voltage is less than or equal to the value of the upsConfigInputVoltageLow MIB variable.
1.3.6.1.4.1.850.16NodeutilityVoltageReturnToNormalThe UPS has returned from a utility voltage high or low condition.
1.3.6.1.4.1.850.17NodebatteryTemperatureHighThe UPS battery temperature has exceeded the value of the upsConfigBatteryTemperatureHigh MIB variable.
1.3.6.1.4.1.850.18NodeshutdownPendingA UPS shutdown countdown is underway.
1.3.6.1.4.1.850.19NodeupsSleepingThe output of the UPS has been turned off.
1.3.6.1.4.1.850.20NodeupsWokeupThe output of the UPS has been turned on.
1.3.6.1.4.1.850.21NodeupsBatteryNeedsReplacementThe UPS battery needs to be replaced.