UEC-STARLINE-MIB

313 objects
MIB module for managing measurement and control devices produced by the Universal Electric Corporation.
Imported Objects
SNMPv2-CONFMODULE-COMPLIANCE NOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIenterprises Integer32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE
SNMPv2-TCDateAndTime DisplayString MacAddress
OIDNameAccessStatusDescription
1.3.6.1.4.1.35774IdentityuecStarlineMIB module for managing measurement and control devices produced by the Universal Electric Corporation.
1.3.6.1.4.1.35774.2Nodecpm
1.3.6.1.4.1.35774.2.1NodecpmAcMeter
1.3.6.1.4.1.35774.2.1.1NodecpmAcGeneral
1.3.6.1.4.1.35774.2.1.1.1ScalarcpmAcDeviceNameread-writecurrentThe name of the meter assigned by the user.
1.3.6.1.4.1.35774.2.1.1.2ScalarcpmAcDeviceLocationread-writecurrentA field for the user to describe the location of the device.
1.3.6.1.4.1.35774.2.1.1.3ScalarcpmAcDeviceIdread-writecurrentA field for the user to describe the device's identification.
1.3.6.1.4.1.35774.2.1.1.4ScalarcpmAcModelNumberread-onlycurrentThe factory set model number.
1.3.6.1.4.1.35774.2.1.1.5ScalarcpmAcSerialNumberread-onlycurrentThe factory set serial number.
1.3.6.1.4.1.35774.2.1.1.6ScalarcpmAcCatalogNumberread-onlycurrentThe factory set catalog number.
1.3.6.1.4.1.35774.2.1.1.7ScalarcpmAcFirmwareVersionread-onlycurrentA factory set string to define the firmware revision.
1.3.6.1.4.1.35774.2.1.1.8ScalarcpmAcCalibrationDateread-onlycurrentFactory set date of calibration.
1.3.6.1.4.1.35774.2.1.1.9ScalarcpmAcEnergyResetread-writecurrentEnergy reset. Set to 1 to issue reset energy command.
1.3.6.1.4.1.35774.2.1.1.10ScalarcpmAcGroupResetread-writecurrentReset group command: this is an 8 character hexadecimal value representing a 32-bit field of flags, of which only the least significant 4 are used. Set to 1 th…
1.3.6.1.4.1.35774.2.1.2NodecpmAcInterfaces
1.3.6.1.4.1.35774.2.1.2.1NodecpmAcEthernet
1.3.6.1.4.1.35774.2.1.2.1.1ScalarcpmAcEnetMacAddressread-onlycurrentThe factory set MAC address.
1.3.6.1.4.1.35774.2.1.2.1.2ScalarcpmAcEnetIpAddressread-onlycurrentThe currently assigned IP address.
1.3.6.1.4.1.35774.2.1.2.1.3ScalarcpmAcEnetIpNetmaskread-onlycurrentThe currently assigned IP subnet mask.
1.3.6.1.4.1.35774.2.1.2.1.4ScalarcpmAcEnetIpGatewayread-onlycurrentThe currently assigned gateway address.
1.3.6.1.4.1.35774.2.1.2.1.5ScalarcpmAcEnetEnableDHCPread-writecurrentFlag indicating if Static IP or DHCP should be used.
1.3.6.1.4.1.35774.2.1.2.1.6ScalarcpmAcEnetStaticIpAddressread-writecurrentThe IP address to use if not using DHCP.
1.3.6.1.4.1.35774.2.1.2.1.7ScalarcpmAcEnetStaticIpNetmaskread-writecurrentThe IP subnet mask to use if not using DHCP.
1.3.6.1.4.1.35774.2.1.2.1.8ScalarcpmAcEnetStaticIpGatewayread-writecurrentThe gateway address to use if not using DHCP.
1.3.6.1.4.1.35774.2.1.2.2NodecpmAcWifi
1.3.6.1.4.1.35774.2.1.2.2.1ScalarcpmAcWifiMacAddressread-onlycurrentThe factory set MAC address.
1.3.6.1.4.1.35774.2.1.2.2.2ScalarcpmAcWifiIpAddressread-onlycurrentThe currently assigned IP address.
1.3.6.1.4.1.35774.2.1.2.2.3ScalarcpmAcWifiIpNetmaskread-onlycurrentThe currently assigned IP subnet mask.
1.3.6.1.4.1.35774.2.1.2.2.4ScalarcpmAcWifiIpGatewayread-onlycurrentThe currently assigned gateway address.
1.3.6.1.4.1.35774.2.1.2.2.5ScalarcpmAcWifiEnableDHCPread-writecurrentFlag indicating if Static IP or DHCP should be used.
1.3.6.1.4.1.35774.2.1.2.2.6ScalarcpmAcWifiStaticIpAddressread-writecurrentThe IP address to use if not using DHCP.
1.3.6.1.4.1.35774.2.1.2.2.7ScalarcpmAcWifiStaticIpNetmaskread-writecurrentThe IP subnet mask to use if not using DHCP.
1.3.6.1.4.1.35774.2.1.2.2.8ScalarcpmAcWifiStaticIpGatewayread-writecurrentThe gateway address to use if not using DHCP.
1.3.6.1.4.1.35774.2.1.2.2.9ScalarcpmAcWifiSSIDread-writecurrentThe SSID (network name) of the wireless local area network (WLAN).
1.3.6.1.4.1.35774.2.1.2.2.10ScalarcpmAcWifiEncryptionTyperead-writecurrentThe type of encryption being used by the WLAN: none, wep, wpa, wpa2.
1.3.6.1.4.1.35774.2.1.2.3NodecpmAcModbus
1.3.6.1.4.1.35774.2.1.2.3.1ScalarcpmAcModbusAddressread-writecurrentA user given serial address used for Modbus.
1.3.6.1.4.1.35774.2.1.2.3.2ScalarcpmAcModbusBaudRateread-writecurrentUser selected baud rate of serial communications: 9600 or 19200.
1.3.6.1.4.1.35774.2.1.2.3.3ScalarcpmAcModbusStopBitsread-writecurrentUser selected number of stop bits: 1 or 2.
1.3.6.1.4.1.35774.2.1.2.3.4ScalarcpmAcModbusParityread-writecurrentUser selected parity: 0=even, 1=odd, 2=none.
1.3.6.1.4.1.35774.2.1.2.4TablecpmAcDigitalIonot-accessiblecurrentTable of Digital I/O line data.
1.3.6.1.4.1.35774.2.1.2.4.1RowcpmAcDigitalIoEntrynot-accessiblecurrentVariables pertaining to Digital I/Os.
1.3.6.1.4.1.35774.2.1.2.4.1.1ColumncpmAcDigitalIoIndexnot-accessiblecurrentThe index to the Digital I/O entry.
1.3.6.1.4.1.35774.2.1.2.4.1.2ColumncpmAcDigitalIoNameread-writecurrentThe Digital I/O name.
1.3.6.1.4.1.35774.2.1.2.4.1.3ColumncpmAcDigitalIoValueread-writecurrentThe current value of the digital I/O.
1.3.6.1.4.1.35774.2.1.2.4.1.4ColumncpmAcDigitalIoDirectionread-writecurrentThe direction of the digital I/O.
1.3.6.1.4.1.35774.2.1.2.4.1.5ColumncpmAcDigitalIoLevelread-writecurrentThe active level of the digital I/O.
1.3.6.1.4.1.35774.2.1.2.4.1.6ColumncpmAcDigitalIoAlarmread-writecurrentSet to generate an alarm on input.
1.3.6.1.4.1.35774.2.1.2.5NodecpmAcAnalogIo
1.3.6.1.4.1.35774.2.1.2.5.1ScalarcpmAc4to20maPortNameread-writecurrentThe name of the 4-20 ma port.
1.3.6.1.4.1.35774.2.1.2.5.2ScalarcpmAc4to20maValueread-onlycurrentThe value of the 4-20 ma port.
1.3.6.1.4.1.35774.2.1.3NodecpmAcProtocols
1.3.6.1.4.1.35774.2.1.3.1NodecpmAcSnmp
1.3.6.1.4.1.35774.2.1.3.1.1ScalarcpmAcSnmpTrapDestAddr1read-writecurrentA user set ip address for revceiving traps.
1.3.6.1.4.1.35774.2.1.3.1.2ScalarcpmAcSnmpTrapDestAddr2read-writecurrentA user set ip address for revceiving traps.
1.3.6.1.4.1.35774.2.1.3.2NodecpmAcEmail
1.3.6.1.4.1.35774.2.1.3.2.1ScalarcpmAcEmailFromAddressread-writecurrentA user set email address representing the originator of the alarm message.
1.3.6.1.4.1.35774.2.1.3.2.2ScalarcpmAcEmailToAddressread-writecurrentA user set email address representing the recipient of the alarm message.
1.3.6.1.4.1.35774.2.1.3.2.3ScalarcpmAcEmailServerread-writecurrentIP address of the email server.
1.3.6.1.4.1.35774.2.1.3.2.4ScalarcpmAcEmailPortread-writecurrentThe port used by the email server
1.3.6.1.4.1.35774.2.1.3.2.5ScalarcpmAcEmailAuthEnableread-writecurrent0 = Authentication Disabled, 1 = Authentication Enabled
1.3.6.1.4.1.35774.2.1.3.2.6ScalarcpmAcEmailLoginread-writecurrentThe user name required for login to the email server.
1.3.6.1.4.1.35774.2.1.3.2.7ScalarcpmAcEmailPasswordread-writecurrentThe password required for login to the email server.
1.3.6.1.4.1.35774.2.1.3.3NodecpmAcSntp
1.3.6.1.4.1.35774.2.1.3.3.1ScalarcpmAcSntpServerread-writecurrentIP address of the SNTP server.
1.3.6.1.4.1.35774.2.1.3.4NodecpmAcTelnet
1.3.6.1.4.1.35774.2.1.4NodecpmAcInfeed
1.3.6.1.4.1.35774.2.1.4.1ScalarcpmAcInfLineToNeutVoltAveread-onlycurrentThe enabled line-to-neutral voltages (1 to 3), cpmAcLineToNeutVoltage, summed together then divided by the number of enabled lines. = ((VL1N + VL2N + VL3N) / 3…
1.3.6.1.4.1.35774.2.1.4.2ScalarcpmAcInfLineToLineVoltAveread-onlycurrentThe enabled line-to-line voltages (1 to 3), cpmAcLineToLineVoltage, summed together then divided by the number of enabled lines. = ((VL1L2 + VL2L3 + VL3L1) / 3…
1.3.6.1.4.1.35774.2.1.4.3ScalarcpmAcInfLineCurrentAveread-onlycurrentThe enabled line currents (1 to 3), cpmAcInfLineCurrent, summed together then divided by the number of enabled lines. = ((I1 + I2 + I3) / 3) for 3-Phase
1.3.6.1.4.1.35774.2.1.4.4ScalarcpmAcInfTotLineCurrDemandread-writecurrentThe infeed total line current demand.
1.3.6.1.4.1.35774.2.1.4.5ScalarcpmAcInfTotLineCurrPeakDmdread-writecurrentThe highest cpmAcInfTotLineCurrDemand measured since the last operator reset of this value.
1.3.6.1.4.1.35774.2.1.4.6ScalarcpmAcInfDemandTimeread-writecurrentThe interval of time over which the demand is calculated for the infeed parameters.
1.3.6.1.4.1.35774.2.1.4.7ScalarcpmAcInfTotalActivePowerread-onlycurrentThe infeed total active power.
1.3.6.1.4.1.35774.2.1.4.8ScalarcpmAcInfPeakTotalActivePowerread-writecurrentThe highest infeed total active power measured since the last operator reset of this value.
1.3.6.1.4.1.35774.2.1.4.9ScalarcpmAcInfTotalActivePwrDemandread-writecurrentThe infeed total active power demand.
1.3.6.1.4.1.35774.2.1.4.10ScalarcpmAcInfPeakTotActPwrDemandread-writecurrentThe highest infeed total active power demand measured since the last operator reset of this value.
1.3.6.1.4.1.35774.2.1.4.11ScalarcpmAcInfTotalReactivePowerread-onlycurrentThe infeed total reactive power.
1.3.6.1.4.1.35774.2.1.4.12ScalarcpmAcInfTotReactivePwrDemandread-writecurrentThe infeed total reactive power demand.
1.3.6.1.4.1.35774.2.1.4.13ScalarcpmAcInfPeakTotReactPwrDmdread-writecurrentThe highest infeed total reactive power demand measured since the last operator reset of this value.
1.3.6.1.4.1.35774.2.1.4.14ScalarcpmAcInfTotalApparentPowerread-onlycurrentThe infeed total apparent power.
1.3.6.1.4.1.35774.2.1.4.15ScalarcpmAcInfTotApparentPwrDemandread-writecurrentThe infeed total apparent power demand.
1.3.6.1.4.1.35774.2.1.4.16ScalarcpmAcInfPeakTotApparPwrDmdread-writecurrentThe highest cpmAcInfTotApparentPwrDemand measured since the last operator reset of this value.
1.3.6.1.4.1.35774.2.1.4.17ScalarcpmAcInfTotalPowerFactorread-onlycurrentThe total power factor of the infeed.
1.3.6.1.4.1.35774.2.1.4.18ScalarcpmAcInfFrequencyread-onlycurrentThe frequency of the infeed.
1.3.6.1.4.1.35774.2.1.4.19ScalarcpmAcInfTotalEnergyread-onlycurrentThe total energy being consumed via the infeed, since the last operator reset of this cumulative value.
1.3.6.1.4.1.35774.2.1.4.20ScalarcpmAcInfLineCurrentRatingread-writecurrentThe maximum infeed line current allowed per the device rating.
1.3.6.1.4.1.35774.2.1.4.21ScalarcpmAcInfMeasuredNeutralCurrread-onlycurrentThe infeed measured neutral current.
1.3.6.1.4.1.35774.2.1.4.22ScalarcpmAcInfFrequencyMinread-writecurrentThe lowest cpmAcInfFrequency measured since the last operator reset of this value.
1.3.6.1.4.1.35774.2.1.4.23ScalarcpmAcInfFrequencyMaxread-writecurrentThe highest cpmAcInfFrequency measured since the last operator reset of this value.
1.3.6.1.4.1.35774.2.1.5TablecpmAcInfeedLinenot-accessiblecurrentTable of infeed line data.
1.3.6.1.4.1.35774.2.1.5.1RowcpmAcInfeedLineEntrynot-accessiblecurrentVariables pertaining to infeed line.
1.3.6.1.4.1.35774.2.1.5.1.1ColumncpmAcInfeedLineIndexread-onlycurrentThe index to the infeed line entry.
1.3.6.1.4.1.35774.2.1.5.1.3ColumncpmAcInfLineCurrentread-onlycurrentThe current measurement of infeed.
1.3.6.1.4.1.35774.2.1.5.1.4ColumncpmAcInfLineCurrentMinread-writecurrentThe minimum current measured on infeed.
1.3.6.1.4.1.35774.2.1.5.1.5ColumncpmAcInfLineCurrentMaxread-writecurrentThe maximum current measured on infeed.
1.3.6.1.4.1.35774.2.1.5.1.6ColumncpmAcInfLineCurrRatPctOfread-onlycurrentInfeed line current rating percent of = (current / rated current * 100).
1.3.6.1.4.1.35774.2.1.5.1.7ColumncpmAcInfLineCurrMinAlarmread-writecurrentThe minimum current threshold for alarm activiation.
1.3.6.1.4.1.35774.2.1.5.1.8ColumncpmAcInfLineCurrMaxAlarmread-writecurrentThe maximum current threshold for alarm activiation.
1.3.6.1.4.1.35774.2.1.5.1.9ColumncpmAcInfLineCurrDemandread-writecurrentThe current demand of this line.
1.3.6.1.4.1.35774.2.1.5.1.10ColumncpmAcInfLineCurrPeakDmdread-writecurrentThe highest cpmAcInfLineCurrDemand measured since the last operator reset of this value.
1.3.6.1.4.1.35774.2.1.6TablecpmAcInfeedPhasenot-accessiblecurrentTable of infeed phase data.
1.3.6.1.4.1.35774.2.1.6.1RowcpmAcInfeedPhaseEntrynot-accessiblecurrentVariables pertaining to infeed phase.
1.3.6.1.4.1.35774.2.1.6.1.1ColumncpmAcInfeedPhaseIndexread-onlycurrentThe index to the infeed phase entry.
1.3.6.1.4.1.35774.2.1.6.1.2ColumncpmAcLineToNeutVoltageread-onlycurrentThe current measurement of infeed.
1.3.6.1.4.1.35774.2.1.6.1.3ColumncpmAcLineToLineVoltageread-onlycurrentPhase A,B,C voltage.
1.3.6.1.4.1.35774.2.1.6.1.4ColumncpmAcLineToLineVoltMinread-writecurrentPhase A,B,C voltage minimum.
1.3.6.1.4.1.35774.2.1.6.1.5ColumncpmAcLineToLineVoltMaxread-writecurrentPhase A,B,C voltage maximum.
1.3.6.1.4.1.35774.2.1.6.1.6ColumncpmAcLinToLinVoltMinAlmread-writecurrentPhase A,B,C voltage minimum alarm threshold.
1.3.6.1.4.1.35774.2.1.6.1.7ColumncpmAcLinToLinVoltMaxAlmread-writecurrentPhase A,B,C voltage maximum alarm threshold.
1.3.6.1.4.1.35774.2.1.6.1.8ColumncpmAcInfPhasePowerFactorread-onlycurrentPhase A,B,C power factor.
1.3.6.1.4.1.35774.2.1.6.1.9ColumncpmAcInfPhaseApparentPwrread-onlycurrentPhase A,B,C apparent power.
1.3.6.1.4.1.35774.2.1.6.1.10ColumncpmAcInfPhaseActivePowerread-onlycurrentPhase A,B,C active power
1.3.6.1.4.1.35774.2.1.6.1.11ColumncpmAcInfPhasePeakActPwrread-writecurrentPhase A,B,C peak active power.
1.3.6.1.4.1.35774.2.1.6.1.12ColumncpmAcInfPhaseReactivePwrread-onlycurrentPhase A,B,C reactive power.
1.3.6.1.4.1.35774.2.1.6.1.13ColumncpmAcInfPhaseEnergyread-onlycurrentPhase A,B,C metered energy.
1.3.6.1.4.1.35774.2.1.6.1.14ColumncpmAcLineToNeutVoltMinread-writecurrentLine-to-neutral voltage minimum.
1.3.6.1.4.1.35774.2.1.6.1.15ColumncpmAcLineToNeutVoltMaxread-writecurrentLine-to-neutral voltage maximum.
1.3.6.1.4.1.35774.2.1.6.1.16ColumncpmAcLinToNeutVoltMinAlmread-writecurrentLine-to-neutral voltage minimum alarm threshold.
1.3.6.1.4.1.35774.2.1.6.1.17ColumncpmAcLinToNeutVoltMaxAlmread-writecurrentLine-to-neutral voltage maximum alarm threshold.
1.3.6.1.4.1.35774.2.1.7TablecpmAcOutletnot-accessiblecurrentTable of outlet data.
1.3.6.1.4.1.35774.2.1.7.1RowcpmAcOutletEntrynot-accessiblecurrentVariables pertaining to the outlet table.
1.3.6.1.4.1.35774.2.1.7.1.1ColumncpmAcOutletIndexread-onlycurrentThe index to the outlet entry.
1.3.6.1.4.1.35774.2.1.7.1.2ColumncpmAcOutletIdread-writecurrentThe name assigned to this outlet.
1.3.6.1.4.1.35774.2.1.7.1.3ColumncpmAcOtlLineCurrRatingread-onlycurrentThe rated current of this outlet.
1.3.6.1.4.1.35774.2.1.7.1.4ColumncpmAcOtlDemandTimeread-writecurrentThe interval of time over which the demand is calculated for the outlet parameters.
1.3.6.1.4.1.35774.2.1.7.1.5ColumncpmAcOtlTotalActivePowerread-onlycurrentThe total active power being supplied by this outlet.
1.3.6.1.4.1.35774.2.1.7.1.6ColumncpmAcOtlPeakTotActivePwrread-writecurrentThe peak total active power being supplied by this outlet.
1.3.6.1.4.1.35774.2.1.7.1.7ColumncpmAcOtlTotalReactivePwrread-onlycurrentThe total reactive power being supplied by this outlet.
1.3.6.1.4.1.35774.2.1.7.1.8ColumncpmAcOtlTotalApparentPwrread-onlycurrentThe total apparent power being supplied by this outlet.
1.3.6.1.4.1.35774.2.1.7.1.9ColumncpmAcOtlTotalPowerFactorread-onlycurrentThe total power factor of this outlet.
1.3.6.1.4.1.35774.2.1.7.1.10ColumncpmAcOtlTotalEnergyread-onlycurrentThe total energy supplied by this outlet, since the last operator reset of this cumulative value.
1.3.6.1.4.1.35774.2.1.7.1.11ColumncpmAcOtlCurrentMinAlarmread-writecurrentThe minumum outlet current alarm threshold. Current values below threshold will trigger an alarm.
1.3.6.1.4.1.35774.2.1.7.1.12ColumncpmAcOtlCurrentMaxAlarmread-writecurrentThe maximum outlet current alarm threshold. Current values above threshold will trigger an alarm.
1.3.6.1.4.1.35774.2.1.8TablecpmAcOutletLinenot-accessiblecurrentTable of outlet line data.
1.3.6.1.4.1.35774.2.1.8.1RowcpmAcOutletLineEntrynot-accessiblecurrentVariables pertaining to the outlet line table.
1.3.6.1.4.1.35774.2.1.8.1.1ColumncpmAcOutletOutletIndexread-onlycurrentThe index to the outlet entry.
1.3.6.1.4.1.35774.2.1.8.1.2ColumncpmAcOutletLineIndexread-onlycurrentThe index to the outlet line entry.
1.3.6.1.4.1.35774.2.1.8.1.3ColumncpmAcOtlPhaseIdread-writecurrentThe name assigned to this phase of the outlet.
1.3.6.1.4.1.35774.2.1.8.1.4ColumncpmAcOtlLineCurrentread-onlycurrentThe line current flowing through this outlet.
1.3.6.1.4.1.35774.2.1.8.1.5ColumncpmAcOtlLineCurrRatPctOfread-onlycurrentThe percent of rated line current flowing through this outlet.
1.3.6.1.4.1.35774.2.1.8.1.6ColumncpmAcOtlLineCurrDemandread-writecurrentThe current demand of this outlet.
1.3.6.1.4.1.35774.2.1.8.1.7ColumncpmAcOtlLineCurrPeakDmdread-writecurrentThe highest cpmAcOtlLineCurrDemand measured since the last operator reset of this value.
1.3.6.1.4.1.35774.2.1.8.1.8ColumncpmAcOtlLineCurrentMinread-writecurrentThe lowest cpmAcOtlLineCurrent measured since the last operator reset of this value.
1.3.6.1.4.1.35774.2.1.8.1.9ColumncpmAcOtlLineCurrentMaxread-writecurrentThe highest cpmAcOtlLineCurrent measured since the last operator reset of this value.
1.3.6.1.4.1.35774.2.1.9NodecpmAcAlarms
1.3.6.1.4.1.35774.2.1.9.1ScalarcpmAcInfeedAlarmStatusread-onlycurrentThe infeed alarm status. This is an 8 character hexadecimal value representing a 32-bit field of flags. All flags are normally 0. If an alarm condition occurs,…
1.3.6.1.4.1.35774.2.1.9.2ScalarcpmAcOutletAlarmStatusread-onlycurrentOutlet 1 through 4 alarm status. This is an 8 character hexadecimal value representing a 32-bit field of flags. All flags are normally 0. If an alarm condition…
1.3.6.1.4.1.35774.2.1.9.3ScalarcpmAcOutletAlarmStatus2read-onlycurrentOutlet 5 and 6 alarm status. This is an 8 character hexadecimal value representing a 32-bit field of flags. All flags are normally 0. If an alarm condition occ…
1.3.6.1.4.1.35774.2.1.9.4ScalarcpmAcTempAlarmStatusread-onlycurrentTemperature alarm status. This is an 8 character hexadecimal value representing a 32-bit field of flags. All flags are normally 0. If an alarm condition occurs…
1.3.6.1.4.1.35774.2.1.10NodecpmAcDiagnostics
1.3.6.1.4.1.35774.2.1.10.1ScalarcpmAcFirstErrorMessageread-onlycurrentThe oldest error message.
1.3.6.1.4.1.35774.2.1.10.2ScalarcpmAcLastErrorMessageread-onlycurrentThe most recent error message.
1.3.6.1.4.1.35774.2.1.11NodecpmAcTempMonitor
1.3.6.1.4.1.35774.2.1.11.1ScalarcpmAcEnclosureTempread-onlycurrentThe temperature inside the enclosure.
1.3.6.1.4.1.35774.2.1.11.2ScalarcpmAcEnclosureTempMaxread-writecurrentThe highest cpmAcEnclosureTemp measured since the last operator reset of this value.
1.3.6.1.4.1.35774.2.1.11.3ScalarcpmAcEncSysMaxTempAlmThrread-onlycurrentThe factory set enclosure system maximum temperature alarm threshold. Values above threshold will trigger an alarm.
1.3.6.1.4.1.35774.2.1.11.4ScalarcpmAcEncUsrMaxTempAlmThrread-writecurrentThe enclosure user maximum temperature alarm threshold. Values above threshold will trigger an alarm.
1.3.6.1.4.1.35774.2.1.11.5ScalarcpmAcBatVoltMinAlmThrread-onlycurrentThe factory set battery voltage minimum alarm threshold. Values below threshold will trigger an alarm.
1.3.6.1.4.1.35774.2.1.12TablecpmAcTempNodenot-accessiblecurrentTable of temperature node data.
1.3.6.1.4.1.35774.2.1.12.1RowcpmAcTempNodeEntrynot-accessiblecurrentVariables pertaining to the temperature node table.
1.3.6.1.4.1.35774.2.1.12.1.1ColumncpmAcNodeIndexread-onlycurrentThe index to the temperature node entry.
1.3.6.1.4.1.35774.2.1.12.1.2ColumncpmAcNodeIdread-writecurrentThe name assigned to this temperature node.
1.3.6.1.4.1.35774.2.1.12.1.3ColumncpmAcNodeTemperatureread-onlycurrentThe temperature at this node.
1.3.6.1.4.1.35774.2.1.12.1.4ColumncpmAcNodeTemperatureMaxread-writecurrentThe highest cpmAcNodeTemperature measured since the last operator reset of this value.
1.3.6.1.4.1.35774.2.1.12.1.5ColumncpmAcNodeSysMaxAlmThreshread-onlycurrentThe factory set system maximum temperature alarm threshold. Values above threshold will trigger an alarm.
1.3.6.1.4.1.35774.2.1.12.1.6ColumncpmAcNodeUsrMaxAlmThreshread-writecurrentThe user maximum temperature alarm threshold. Values above threshold will trigger an alarm.
1.3.6.1.4.1.35774.2.1.12.1.7ColumncpmAcNodeBatteryVoltageread-onlycurrentThe battery voltage of this temperature node.
1.3.6.1.4.1.35774.2.1.50NodecpmAcNotifications
1.3.6.1.4.1.35774.2.1.50.0NodecpmAcEvents
1.3.6.1.4.1.35774.2.1.50.0.1NotificationcpmAcInfOvCurrAssertEvcurrentAC CPM Infeed Over Current Assert Event
1.3.6.1.4.1.35774.2.1.50.0.2NotificationcpmAcInfOvCurrDeassertEvcurrentAC CPM Infeed Over Current Deassert Event
1.3.6.1.4.1.35774.2.1.50.0.3NotificationcpmAcInfUnCurrAssertEvcurrentAC CPM Infeed Under Current Assert Event
1.3.6.1.4.1.35774.2.1.50.0.4NotificationcpmAcInfUnCurrDeassertEvcurrentAC CPM Infeed Under Current Deassert Event
1.3.6.1.4.1.35774.2.1.50.0.5NotificationcpmAcInfOvVoltAssertEvcurrentAC CPM Infeed Over Voltage Assert Event
1.3.6.1.4.1.35774.2.1.50.0.6NotificationcpmAcInfOvVoltDeassertEvcurrentAC CPM Infeed Over Voltage Deassert Event
1.3.6.1.4.1.35774.2.1.50.0.7NotificationcpmAcInfUnVoltAssertEvcurrentAC CPM Infeed Under Voltage Assert Event
1.3.6.1.4.1.35774.2.1.50.0.8NotificationcpmAcInfUnVoltDeassertEvcurrentAC CPM Infeed Under Voltage Deassert Event
1.3.6.1.4.1.35774.2.1.50.0.9NotificationcpmAcOtlOvCurrAssertEvcurrentAC CPM Outlet Over Current Assert Event
1.3.6.1.4.1.35774.2.1.50.0.10NotificationcpmAcOtlOvCurrDeassertEvcurrentAC CPM Outlet Over Current Deassert Event
1.3.6.1.4.1.35774.2.1.50.0.11NotificationcpmAcOtlUnCurrAssertEvcurrentAC CPM Outlet Under Current Assert Event
1.3.6.1.4.1.35774.2.1.50.0.12NotificationcpmAcOtlUnCurrDeassertEvcurrentAC CPM Outlet Under Current Deassert Event
1.3.6.1.4.1.35774.2.1.50.0.13NotificationcpmAcOvTempAssertEvcurrentAC CPM Over Temperature Assert Event
1.3.6.1.4.1.35774.2.1.50.0.14NotificationcpmAcOvTempDeassertEvcurrentAC CPM Over Temperature Deassert Event
1.3.6.1.4.1.35774.2.1.50.0.15NotificationcpmAcBatVoltLowAssertEvcurrentAC CPM Battery Voltage Low Assert Event
1.3.6.1.4.1.35774.2.1.50.0.16NotificationcpmAcBatVoltLowDeassertEvcurrentAC CPM Battery Voltage Low Deassert Event
1.3.6.1.4.1.35774.2.2NodecpmDcMeter
1.3.6.1.4.1.35774.2.2.1NodecpmDcGeneral
1.3.6.1.4.1.35774.2.2.1.1ScalarcpmDcDeviceNameread-writecurrentThe name of the meter assigned by the user.
1.3.6.1.4.1.35774.2.2.1.2ScalarcpmDcDeviceLocationread-writecurrentA field for the user to describe the location of the device.
1.3.6.1.4.1.35774.2.2.1.3ScalarcpmDcDeviceIdread-writecurrentA field for the user to describe the device's identification.
1.3.6.1.4.1.35774.2.2.1.4ScalarcpmDcModelNumberread-onlycurrentThe factory set model number.
1.3.6.1.4.1.35774.2.2.1.5ScalarcpmDcSerialNumberread-onlycurrentThe factory set serial number.
1.3.6.1.4.1.35774.2.2.1.6ScalarcpmDcCatalogNumberread-onlycurrentThe factory set catalog number.
1.3.6.1.4.1.35774.2.2.1.7ScalarcpmDcFirmwareVersionread-onlycurrentA factory set string to define the firmware revision.
1.3.6.1.4.1.35774.2.2.1.8ScalarcpmDcEnergyResetread-writecurrentEnergy reset. Set to 1 to issue reset energy command.
1.3.6.1.4.1.35774.2.2.2NodecpmDcInterfaces
1.3.6.1.4.1.35774.2.2.2.1NodecpmDcEthernet
1.3.6.1.4.1.35774.2.2.2.1.1ScalarcpmDcEnetMacAddressread-onlycurrentThe factory set MAC address.
1.3.6.1.4.1.35774.2.2.2.1.2ScalarcpmDcEnetIpAddressread-onlycurrentThe currently assigned IP address.
1.3.6.1.4.1.35774.2.2.2.1.3ScalarcpmDcEnetIpNetmaskread-onlycurrentThe currently assigned IP subnet mask.
1.3.6.1.4.1.35774.2.2.2.1.4ScalarcpmDcEnetIpGatewayread-onlycurrentThe currently assigned gateway address.
1.3.6.1.4.1.35774.2.2.2.1.5ScalarcpmDcEnetEnableDHCPread-writecurrentFlag indicating if Static IP or DHCP should be used.
1.3.6.1.4.1.35774.2.2.2.1.6ScalarcpmDcEnetStaticIpAddressread-writecurrentThe IP address to use if not using DHCP.
1.3.6.1.4.1.35774.2.2.2.1.7ScalarcpmDcEnetStaticIpNetmaskread-writecurrentThe IP subnet mask to use if not using DHCP.
1.3.6.1.4.1.35774.2.2.2.1.8ScalarcpmDcEnetStaticIpGatewayread-writecurrentThe gateway address to use if not using DHCP.
1.3.6.1.4.1.35774.2.2.2.2NodecpmDcWifi
1.3.6.1.4.1.35774.2.2.2.2.1ScalarcpmDcWifiMacAddressread-onlycurrentThe factory set MAC address.
1.3.6.1.4.1.35774.2.2.2.2.2ScalarcpmDcWifiIpAddressread-onlycurrentThe currently assigned IP address.
1.3.6.1.4.1.35774.2.2.2.2.3ScalarcpmDcWifiIpNetmaskread-onlycurrentThe currently assigned IP subnet mask.
1.3.6.1.4.1.35774.2.2.2.2.4ScalarcpmDcWifiIpGatewayread-onlycurrentThe currently assigned gateway address.
1.3.6.1.4.1.35774.2.2.2.2.5ScalarcpmDcWifiEnableDHCPread-writecurrentFlag indicating if Static IP or DHCP should be used.
1.3.6.1.4.1.35774.2.2.2.2.6ScalarcpmDcWifiStaticIpAddressread-writecurrentThe IP address to use if not using DHCP.
1.3.6.1.4.1.35774.2.2.2.2.7ScalarcpmDcWifiStaticIpNetmaskread-writecurrentThe IP subnet mask to use if not using DHCP.
1.3.6.1.4.1.35774.2.2.2.2.8ScalarcpmDcWifiStaticIpGatewayread-writecurrentThe gateway address to use if not using DHCP.
1.3.6.1.4.1.35774.2.2.2.2.9ScalarcpmDcWifiSSIDread-writecurrentThe SSID (network name) of the wireless local area network (WLAN).
1.3.6.1.4.1.35774.2.2.2.2.10ScalarcpmDcWifiEncryptionTyperead-writecurrentThe type of encryption being used by the WLAN: none, wep, wpa, wpa2.
1.3.6.1.4.1.35774.2.2.2.3NodecpmDcModbus
1.3.6.1.4.1.35774.2.2.2.3.1ScalarcpmDcModbusAddressread-writecurrentA user given serial address used for Modbus.
1.3.6.1.4.1.35774.2.2.2.3.2ScalarcpmDcModbusBaudRateread-writecurrentUser selected baud rate of serial communications: 9600 or 19200.
1.3.6.1.4.1.35774.2.2.2.3.3ScalarcpmDcModbusStopBitsread-writecurrentUser selected number of stop bits: 1 or 2.
1.3.6.1.4.1.35774.2.2.2.3.4ScalarcpmDcModbusParityread-writecurrentUser selected parity: 0=even, 1=odd, 2=none.
1.3.6.1.4.1.35774.2.2.2.4TablecpmDcDigitalIonot-accessiblecurrentTable of Digital I/O line data.
1.3.6.1.4.1.35774.2.2.2.4.1RowcpmDcDigitalIoEntrynot-accessiblecurrentVariables pertaining to Digital I/Os.
1.3.6.1.4.1.35774.2.2.2.4.1.1ColumncpmDcDigitalIoIndexnot-accessiblecurrentThe index to the Digital I/O entry.
1.3.6.1.4.1.35774.2.2.2.4.1.2ColumncpmDcDigitalIoNameread-writecurrentThe Digital I/O name.
1.3.6.1.4.1.35774.2.2.2.4.1.3ColumncpmDcDigitalIoValueread-writecurrentThe current value of the digital I/O.
1.3.6.1.4.1.35774.2.2.2.4.1.4ColumncpmDcDigitalIoDirectionread-writecurrentThe direction of the digital I/O.
1.3.6.1.4.1.35774.2.2.2.4.1.5ColumncpmDcDigitalIoLevelread-writecurrentThe active level of the digital I/O.
1.3.6.1.4.1.35774.2.2.2.4.1.6ColumncpmDcDigitalIoAlarmread-writecurrentSet to generate an alarm on input.
1.3.6.1.4.1.35774.2.2.2.5NodecpmDcAnalogIo
1.3.6.1.4.1.35774.2.2.2.5.1ScalarcpmDc4to20maPortNameread-writecurrentThe name of the 4-20 ma port.
1.3.6.1.4.1.35774.2.2.2.5.2ScalarcpmDc4to20maValueread-onlycurrentThe value of the 4-20 ma port.
1.3.6.1.4.1.35774.2.2.3NodecpmDcProtocols
1.3.6.1.4.1.35774.2.2.3.1NodecpmDcSnmp
1.3.6.1.4.1.35774.2.2.3.1.1ScalarcpmDcSnmpTrapDestAddr1read-writecurrentA user set ip address for revceiving traps.
1.3.6.1.4.1.35774.2.2.3.1.2ScalarcpmDcSnmpTrapDestAddr2read-writecurrentA user set ip address for revceiving traps.
1.3.6.1.4.1.35774.2.2.3.2NodecpmDcEmail
1.3.6.1.4.1.35774.2.2.3.2.1ScalarcpmDcEmailFromAddressread-writecurrentA user set email address representing the originator of the alarm message.
1.3.6.1.4.1.35774.2.2.3.2.2ScalarcpmDcEmailToAddressread-writecurrentA user set email address representing the recipient of the alarm message.
1.3.6.1.4.1.35774.2.2.3.2.3ScalarcpmDcEmailServerread-writecurrentIP address of the email server.
1.3.6.1.4.1.35774.2.2.3.2.4ScalarcpmDcEmailPortread-writecurrentThe port used by the email server
1.3.6.1.4.1.35774.2.2.3.2.5ScalarcpmDcEmailAuthEnableread-writecurrent0 = Authentication Disabled, 1 = Authentication Enabled
1.3.6.1.4.1.35774.2.2.3.2.6ScalarcpmDcEmailLoginread-writecurrentThe user name required for login to the email server.
1.3.6.1.4.1.35774.2.2.3.2.7ScalarcpmDcEmailPasswordread-writecurrentThe password required for login to the email server.
1.3.6.1.4.1.35774.2.2.3.3NodecpmDcSntp
1.3.6.1.4.1.35774.2.2.3.3.1ScalarcpmDcSntpServerread-writecurrentIP address of the SNTP server.
1.3.6.1.4.1.35774.2.2.3.4NodecpmDcTelnet
1.3.6.1.4.1.35774.2.2.4NodecpmDcInfeed
1.3.6.1.4.1.35774.2.2.4.1ScalarcpmDcInfDemandTimeread-writecurrentThe interval of time over which the demand is calculated for the infeed parameters.
1.3.6.1.4.1.35774.2.2.4.2ScalarcpmDcInfCktCurrRatingread-writecurrentThe maximum infeed circuit current allowed per the device rating.
1.3.6.1.4.1.35774.2.2.5TablecpmDcInfCircuitnot-accessiblecurrentTable of infeed circuit data.
1.3.6.1.4.1.35774.2.2.5.1RowcpmDcInfCircuitEntrynot-accessiblecurrentVariables pertaining to infeed circuit.
1.3.6.1.4.1.35774.2.2.5.1.1ColumncpmDcInfeedCircuitIndexread-onlycurrentThe index to the infeed circuit entry.
1.3.6.1.4.1.35774.2.2.5.1.2ColumncpmDcCktVoltageread-onlycurrentCircuit voltage.
1.3.6.1.4.1.35774.2.2.5.1.3ColumncpmDcCktVoltageMinread-writecurrentCircuit voltage minimum.
1.3.6.1.4.1.35774.2.2.5.1.4ColumncpmDcCktVoltageMaxread-writecurrentCircuit voltage maximum.
1.3.6.1.4.1.35774.2.2.5.1.5ColumncpmDcCktVoltageMinAlarmread-writecurrentCircuit voltage minimum alarm threshold.
1.3.6.1.4.1.35774.2.2.5.1.6ColumncpmDcCktVoltageMaxAlarmread-writecurrentCircuit voltage maximum alarm threshold.
1.3.6.1.4.1.35774.2.2.5.1.7ColumncpmDcInfCktPowerread-onlycurrentInfeed circuit power
1.3.6.1.4.1.35774.2.2.5.1.8ColumncpmDcInfCktPeakPowerread-writecurrentInfeed circuit peak power.
1.3.6.1.4.1.35774.2.2.5.1.9ColumncpmDcInfCktEnergyDelivrdread-onlycurrentInfeed circuit energy delivered.
1.3.6.1.4.1.35774.2.2.5.1.10ColumncpmDcInfCktEnergyRcvdread-onlycurrentInfeed circuit energy received.
1.3.6.1.4.1.35774.2.2.5.1.11ColumncpmDcInfCktCurrentread-onlycurrentThe current measured on this infeed circuit.
1.3.6.1.4.1.35774.2.2.5.1.12ColumncpmDcInfCktCurrentMinread-writecurrentThe minimum current measured on this infeed circuit.
1.3.6.1.4.1.35774.2.2.5.1.13ColumncpmDcInfCktCurrentMaxread-writecurrentThe maximum current measured on this infeed circuit.
1.3.6.1.4.1.35774.2.2.5.1.14ColumncpmDcInfCktCurrRatPctOfread-onlycurrent(current / rated current * 100) for this infeed circuit.
1.3.6.1.4.1.35774.2.2.5.1.15ColumncpmDcInfCktCurrMinAlarmread-writecurrentThe minimum current threshold for alarm activiation.
1.3.6.1.4.1.35774.2.2.5.1.16ColumncpmDcInfCktCurrMaxAlarmread-writecurrentThe maximum current threshold for alarm activiation.
1.3.6.1.4.1.35774.2.2.5.1.17ColumncpmDcInfCktCurrDemandread-writecurrentThe current demand of this infeed circuit.
1.3.6.1.4.1.35774.2.2.5.1.18ColumncpmDcInfCktCurrPeakDmdread-writecurrentThe highest cpmDcInfCktCurrDemand measured since the last operator reset of this value.
1.3.6.1.4.1.35774.2.2.6TablecpmDcOutletnot-accessiblecurrentTable of outlet data.
1.3.6.1.4.1.35774.2.2.6.1RowcpmDcOutletEntrynot-accessiblecurrentVariables pertaining to the outlet table.
1.3.6.1.4.1.35774.2.2.6.1.1ColumncpmDcOutletIndexread-onlycurrentThe index to the outlet entry.
1.3.6.1.4.1.35774.2.2.6.1.2ColumncpmDcOutletIdread-writecurrentThe name assigned to this outlet.
1.3.6.1.4.1.35774.2.2.6.1.3ColumncpmDcOtlCktCurrRatingread-onlycurrentThe rated current of this outlet.
1.3.6.1.4.1.35774.2.2.6.1.4ColumncpmDcOtlDemandTimeread-writecurrentThe interval of time over which the demand is calculated for the outlet parameters.
1.3.6.1.4.1.35774.2.2.6.1.5ColumncpmDcOtlCurrentMinAlarmread-writecurrentThe minumum outlet current alarm threshold. Current values below threshold will trigger an alarm.
1.3.6.1.4.1.35774.2.2.6.1.6ColumncpmDcOtlCurrentMaxAlarmread-writecurrentThe maximun outlet current alarm threshold. Current values above threshold will trigger an alarm.
1.3.6.1.4.1.35774.2.2.7TablecpmDcOutletCircuitnot-accessiblecurrentTable of outlet circuit data.
1.3.6.1.4.1.35774.2.2.7.1RowcpmDcOutletCircuitEntrynot-accessiblecurrentVariables pertaining to the outlet circuit table.
1.3.6.1.4.1.35774.2.2.7.1.1ColumncpmDcOutletOutletIndexread-onlycurrentThe index to the outlet entry.
1.3.6.1.4.1.35774.2.2.7.1.2ColumncpmDcOutletCircuitIndexread-onlycurrentThe index to the outlet circuit entry.
1.3.6.1.4.1.35774.2.2.7.1.3ColumncpmDcOtlCktCurrentread-onlycurrentThe current flowing through this outlet circuit.
1.3.6.1.4.1.35774.2.2.7.1.4ColumncpmDcOtlCktCurrRatPctOfread-onlycurrentThe percent of rated current flowing through this outlet circuit.
1.3.6.1.4.1.35774.2.2.7.1.5ColumncpmDcOtlCktCurrentDemandread-writecurrentThe current demand of this outlet.
1.3.6.1.4.1.35774.2.2.7.1.6ColumncpmDcOtlCktCurrPeakDmdread-writecurrentThe highest cpmDcOtlCktCurrentDemand measured since the last operator reset of this value.
1.3.6.1.4.1.35774.2.2.7.1.7ColumncpmDcOtlCktCurrentMinread-writecurrentThe lowest cpmDcOtlCktCurrent measured since the last operator reset of this value.
1.3.6.1.4.1.35774.2.2.7.1.8ColumncpmDcOtlCktCurrentMaxread-writecurrentThe highest cpmDcOtlCktCurrent measured since the last operator reset of this value.
1.3.6.1.4.1.35774.2.2.7.1.9ColumncpmDcOtlCktPowerread-onlycurrentThe power being supplied by this outlet circuit.
1.3.6.1.4.1.35774.2.2.7.1.10ColumncpmDcOtlCktPeakPowerread-writecurrentThe peak power supplied by this outlet circuit.
1.3.6.1.4.1.35774.2.2.7.1.11ColumncpmDcOtlCktEnergyDelivrdread-onlycurrentThe total energy delivered by this outlet, since the last operator reset of this cumulative value.
1.3.6.1.4.1.35774.2.2.7.1.12ColumncpmDcOtlCktEnergyRcvdread-onlycurrentThe total energy received by this outlet, since the last operator reset of this cumulative value.
1.3.6.1.4.1.35774.2.2.8NodecpmDcAlarms
1.3.6.1.4.1.35774.2.2.8.1ScalarcpmDcInfeedAlarmStatusread-onlycurrentThe infeed alarm status. This is an 8 character hexadecimal value representing a 32-bit field of flags. All flags are normally 0. If an alarm condition occurs,…
1.3.6.1.4.1.35774.2.2.8.2ScalarcpmDcOutletAlarmStatusread-onlycurrentThe outlet alarm status. This is an 8 character hexadecimal value representing a 32-bit field of flags. All flags are normally 0. If an alarm condition occurs,…
1.3.6.1.4.1.35774.2.2.9NodecpmDcDiagnostics
1.3.6.1.4.1.35774.2.2.9.1ScalarcpmDcFirstErrorMessageread-onlycurrentThe oldest error message.
1.3.6.1.4.1.35774.2.2.9.2ScalarcpmDcLastErrorMessageread-onlycurrentThe most recent error message.
1.3.6.1.4.1.35774.2.2.50NodecpmDcNotifications
1.3.6.1.4.1.35774.2.2.50.0NodecpmDcEvents
1.3.6.1.4.1.35774.2.2.50.0.1NotificationcpmDcInfOvCurrAssertEvcurrent
1.3.6.1.4.1.35774.2.2.50.0.2NotificationcpmDcInfOvCurrDeassertEvcurrent
1.3.6.1.4.1.35774.2.2.50.0.3NotificationcpmDcInfUnCurrAssertEvcurrent
1.3.6.1.4.1.35774.2.2.50.0.4NotificationcpmDcInfUnCurrDeassertEvcurrent
1.3.6.1.4.1.35774.2.2.50.0.5NotificationcpmDcInfOvVoltAssertEvcurrent
1.3.6.1.4.1.35774.2.2.50.0.6NotificationcpmDcInfOvVoltDeassertEvcurrent
1.3.6.1.4.1.35774.2.2.50.0.7NotificationcpmDcInfUnVoltAssertEvcurrent
1.3.6.1.4.1.35774.2.2.50.0.8NotificationcpmDcInfUnVoltDeassertEvcurrent
1.3.6.1.4.1.35774.2.2.50.0.9NotificationcpmDcOtlOvCurrAssertEvcurrent
1.3.6.1.4.1.35774.2.2.50.0.10NotificationcpmDcOtlOvCurrDeassertEvcurrent
1.3.6.1.4.1.35774.2.2.50.0.11NotificationcpmDcOtlUnCurrAssertEvcurrent
1.3.6.1.4.1.35774.2.2.50.0.12NotificationcpmDcOtlUnCurrDeassertEvcurrent