This is the MIB module for the UNIFLAIR UNCDZ device.
Imported Objects
SNMPv2-CONFOBJECT-GROUP
SNMPv2-MIBsysContact sysLocation sysName
SNMPv2-SMIenterprises Integer32 MODULE-IDENTITY OBJECT-TYPE
OIDNameAccessStatusDescription
1.3.6.1.4.1.9839Nodecarel
1.3.6.1.4.1.9839.1Nodesystm
1.3.6.1.4.1.9839.1.1ScalaragentReleaseread-onlycurrentRelease of the Agent.
1.3.6.1.4.1.9839.1.2ScalaragentCoderead-onlycurrentCode of the Agent. 2=pCOWeb.
1.3.6.1.4.1.9839.2Nodeinstruments
1.3.6.1.4.1.9839.2.0NodepCOWebInfo
1.3.6.1.4.1.9839.2.0.10NodepCOStatusgroup
1.3.6.1.4.1.9839.2.0.10.1ScalarpCOId1-Statusread-onlycurrentStatus of pCOId1. 0=Offline, 1=Init, 2=Online
1.3.6.1.4.1.9839.2.0.11NodepCOErrorsNumbergroup
1.3.6.1.4.1.9839.2.0.11.1ScalarpCOId1-ErrorsNumberread-onlycurrentNumber of Communication Errors from pCOId1 to pCOWeb.
1.3.6.1.4.1.9839.2.1Identityuncdz-MIBThis is the MIB module for the UNIFLAIR UNCDZ device.
1.3.6.1.4.1.9839.2.1.1NodedigitalObjects
1.3.6.1.4.1.9839.2.1.1.1Scalarvent-onread-onlycurrentSystem On (Fan)
1.3.6.1.4.1.9839.2.1.1.2Scalarcompressore1read-onlycurrentCompressor 1
1.3.6.1.4.1.9839.2.1.1.3Scalarcompressore2read-onlycurrentCompressor 2
1.3.6.1.4.1.9839.2.1.1.4Scalarcompressore3read-onlycurrentCompressor 3
1.3.6.1.4.1.9839.2.1.1.5Scalarcompressore4read-onlycurrentCompressor 4
1.3.6.1.4.1.9839.2.1.1.6Scalarout-h1read-onlycurrentHeating 1
1.3.6.1.4.1.9839.2.1.1.7Scalarout-h2read-onlycurrentHeating 2
1.3.6.1.4.1.9839.2.1.1.8Scalarout-h3read-onlycurrentHeating 3
1.3.6.1.4.1.9839.2.1.1.9Scalargas-caldo-onread-onlycurrentHot Gas Coil
1.3.6.1.4.1.9839.2.1.1.10Scalaron-deumread-onlycurrentDehumidification
1.3.6.1.4.1.9839.2.1.1.11Scalarpowerread-onlycurrentHumidification
1.3.6.1.4.1.9839.2.1.1.12Scalarmal-accessread-onlycurrentTampering Alarm
1.3.6.1.4.1.9839.2.1.1.13Scalarmal-ataread-onlycurrentAlarm: Room High Temperature
1.3.6.1.4.1.9839.2.1.1.14Scalarmal-btaread-onlycurrentAlarm: Room Low Temperature
1.3.6.1.4.1.9839.2.1.1.15Scalarmal-auaread-onlycurrentAlarm: Room High Humidity
1.3.6.1.4.1.9839.2.1.1.16Scalarmal-buaread-onlycurrentAlarm: Room Low Humidity
1.3.6.1.4.1.9839.2.1.1.17Scalarmal-eapread-onlycurrentAlarm: Room High/Low Temp./Humid.(Ext. Devices)
1.3.6.1.4.1.9839.2.1.1.18Scalarmal-filterread-onlycurrentAlarm: Clogged Filter
1.3.6.1.4.1.9839.2.1.1.19Scalarmal-floodread-onlycurrentAlarm: Water Leakage Detected
1.3.6.1.4.1.9839.2.1.1.20Scalarmal-fluxread-onlycurrentAlarm: Loss of Air Flow
1.3.6.1.4.1.9839.2.1.1.21Scalarmal-heaterread-onlycurrentAlarm: Heater Overheating
1.3.6.1.4.1.9839.2.1.1.22Scalarmal-hp1read-onlycurrentAlarm: High Pressure 1
1.3.6.1.4.1.9839.2.1.1.23Scalarmal-hp2read-onlycurrentAlarm: High Pressure 2
1.3.6.1.4.1.9839.2.1.1.24Scalarmal-lp1read-onlycurrentAlarm: Low Pressure 1
1.3.6.1.4.1.9839.2.1.1.25Scalarmal-lp2read-onlycurrentAlarm: Low Pressure 2
1.3.6.1.4.1.9839.2.1.1.26Scalarmal-phaseread-onlycurrentAlarm: Wrong phase sequence
1.3.6.1.4.1.9839.2.1.1.27Scalarmal-smokeread-onlycurrentAlarm: SMOKE-FIRE DETECTED
1.3.6.1.4.1.9839.2.1.1.28Scalarmal-lanread-onlycurrentAlarm: Interrupted LAN
1.3.6.1.4.1.9839.2.1.1.29Scalarmal-hcurrread-onlycurrentHumidifier Alarm: High Current
1.3.6.1.4.1.9839.2.1.1.30Scalarmal-nopowerread-onlycurrentHumidifier Alarm: Power Loss
1.3.6.1.4.1.9839.2.1.1.31Scalarmal-nowaterread-onlycurrentHumidifier Alarm: Water Loss
1.3.6.1.4.1.9839.2.1.1.32Scalarmal-cw-dhread-onlycurrentAlarm: Chilled Water Temp. too High for Dehumidification
1.3.6.1.4.1.9839.2.1.1.33Scalarmal-tc-cwread-onlycurrentAlarm: CW Valve Failure or Water Flow too Low
1.3.6.1.4.1.9839.2.1.1.34Scalarmal-wflowread-onlycurrentAlarm: Loss of Water flow
1.3.6.1.4.1.9839.2.1.1.35Scalarmal-whtread-onlycurrentAlarm: High chilled water temp.
1.3.6.1.4.1.9839.2.1.1.36Scalarmal-sonda-taread-onlycurrentAlarm: Room air Sensor Failure/Disconnected
1.3.6.1.4.1.9839.2.1.1.37Scalarmal-sonda-tacread-onlycurrentAlarm: Hot water Sensor Failure/Disconnected
1.3.6.1.4.1.9839.2.1.1.38Scalarmal-sonda-tcread-onlycurrentAlarm: Condensing water Sensor Failure/Disconnect.
1.3.6.1.4.1.9839.2.1.1.39Scalarmal-sonda-teread-onlycurrentAlarm: Outdoor temp. Sensor Failure/Disconnected
1.3.6.1.4.1.9839.2.1.1.40Scalarmal-sonda-tmread-onlycurrentAlarm: Delivery temp. Sensor Failure/Disconnected
1.3.6.1.4.1.9839.2.1.1.41Scalarmal-sonda-uaread-onlycurrentAlarm: Rel. Humidity Sensor Failure/Disconnected
1.3.6.1.4.1.9839.2.1.1.42Scalarmal-ore-compr1read-onlycurrentService Alarm: Compressor 1 hour counter threshold
1.3.6.1.4.1.9839.2.1.1.43Scalarmal-ore-compr2read-onlycurrentService Alarm: Compressor 2 hour counter threshold
1.3.6.1.4.1.9839.2.1.1.44Scalarmal-ore-compr3read-onlycurrentService Alarm: Compressor 3 hour counter threshold
1.3.6.1.4.1.9839.2.1.1.45Scalarmal-ore-compr4read-onlycurrentService Alarm: Compressor 4 hour counter threshold
1.3.6.1.4.1.9839.2.1.1.46Scalarmal-ore-filtroread-onlycurrentService Alarm: Air Filter hour counter threshold
1.3.6.1.4.1.9839.2.1.1.47Scalarmal-ore-risc1read-onlycurrentService Alarm: Heater 1 hour counter threshold
1.3.6.1.4.1.9839.2.1.1.48Scalarmal-ore-risc2read-onlycurrentService Alarm: Heater 2 hour counter threshold
1.3.6.1.4.1.9839.2.1.1.49Scalarmal-ore-umidread-onlycurrentService Alarm: Humidifier hour counter threshold
1.3.6.1.4.1.9839.2.1.1.50Scalarmal-ore-unitread-onlycurrentService Alarm: Unit hour counter threshold
1.3.6.1.4.1.9839.2.1.1.51Scalarglb-alread-onlycurrentGeneral Alarm
1.3.6.1.4.1.9839.2.1.1.52Scalaror-al-2levread-onlycurrent2nd Level Alarm
1.3.6.1.4.1.9839.2.1.1.53Scalarrange-t-extread-onlycurrentOutdoor Temp. Sensor Fitted
1.3.6.1.4.1.9839.2.1.1.54Scalarrange-t-circread-onlycurrentClosed Circuit (or Chilled) Water Temperature Sensor Fitted
1.3.6.1.4.1.9839.2.1.1.55Scalarrange-t-manread-onlycurrentDelivery Temp. Sensor Fitted
1.3.6.1.4.1.9839.2.1.1.56Scalarrange-t-acread-onlycurrentHot water temp. Sensor Fitted
1.3.6.1.4.1.9839.2.1.1.57Scalarumid-alread-onlycurrentHumidifier general alarm
1.3.6.1.4.1.9839.2.1.1.58Scalarrange-u-ambread-onlycurrentRelative Humidity Sensor Fitted
1.3.6.1.4.1.9839.2.1.1.60Scalark-sysonread-writecurrentUnit Remote Switch-On/Off Control
1.3.6.1.4.1.9839.2.1.1.61Scalarxs-res-alread-writecurrentBuzzer and Alarm Remote Reset Control
1.3.6.1.4.1.9839.2.1.1.63Scalarsleep-moderead-writecurrentSet Back Mode (Sleep Mode)
1.3.6.1.4.1.9839.2.1.1.64Scalartest-smread-writecurrentSet Back mode: Cyclical Start of Fan
1.3.6.1.4.1.9839.2.1.1.65Scalarab-mediathread-writecurrentUsage of T+ H Values: Local (0) / Mean (1)
1.3.6.1.4.1.9839.2.1.1.66Scalarustdby1-2read-writecurrentNo. Of Stand-by Units: one (0) / two (1)
1.3.6.1.4.1.9839.2.1.1.67Scalaremergread-onlycurrentUnit in Emergency operation
1.3.6.1.4.1.9839.2.1.2NodeanalogObjects
1.3.6.1.4.1.9839.2.1.2.1Scalartemp-ambread-onlycurrentRoom Temperature
1.3.6.1.4.1.9839.2.1.2.2Scalartemp-extread-onlycurrentOutdoor Temperature
1.3.6.1.4.1.9839.2.1.2.3Scalartemp-mandread-onlycurrentDelivery Air Temperature
1.3.6.1.4.1.9839.2.1.2.4Scalartemp-circread-onlycurrentClosed Circuit (or Chilled) Water Temperature
1.3.6.1.4.1.9839.2.1.2.5Scalartemp-acread-onlycurrentHot Water Temperature
1.3.6.1.4.1.9839.2.1.2.6Scalarumid-ambread-onlycurrentRoom Relative Humidity
1.3.6.1.4.1.9839.2.1.2.7Scalart-setread-writecurrentCooling Set Point
1.3.6.1.4.1.9839.2.1.2.8Scalart-diffread-writecurrentCooling Prop.Band
1.3.6.1.4.1.9839.2.1.2.9Scalart-set-cread-writecurrentHeating Set point
1.3.6.1.4.1.9839.2.1.2.10Scalart-diff-cread-writecurrentHeating Prop.Band
1.3.6.1.4.1.9839.2.1.2.11Scalarht-setread-writecurrentRoom High Temp. Alarm Threshold
1.3.6.1.4.1.9839.2.1.2.12Scalarlt-setread-writecurrentRoom Low Temp. Alarm Threshold
1.3.6.1.4.1.9839.2.1.2.13Scalart-set-smread-writecurrentSetback Mode: Cooling Set Point
1.3.6.1.4.1.9839.2.1.2.14Scalart-set-c-smread-writecurrentSetback Mode: Heating Set Point
1.3.6.1.4.1.9839.2.1.2.15Scalart-cw-dhread-writecurrentCW Set Point to Start Dehumidification Cycle
1.3.6.1.4.1.9839.2.1.2.16Scalarhtset-cwread-writecurrentCW High Temperature Alarm Threshold
1.3.6.1.4.1.9839.2.1.2.17Scalart-set-cwread-writecurrentCW Set Point to Start CW Operating Mode (TC only)
1.3.6.1.4.1.9839.2.1.2.18Scalart-rc-esread-writecurrentRad-cooler Set Point in E.S. Mode (ES Only)
1.3.6.1.4.1.9839.2.1.2.19Scalart-rc-estread-writecurrentRad-cooler Set Point in DX Mode (ES Only)
1.3.6.1.4.1.9839.2.1.2.20Scalarrampa-valvread-onlycurrent0-10V Ramp 1 Value (CW Valve Ramp)
1.3.6.1.4.1.9839.2.1.2.21Scalaranaout2read-onlycurrent0-10V Ramp 2 Value (HW Valve/Rad Cooler Ramp)
1.3.6.1.4.1.9839.2.1.2.22Scalarsteam-productionread-onlycurrentHumidifier: steam capacity
1.3.6.1.4.1.9839.2.1.2.23Scalart-set-lmread-writecurrentDelivery Air Temperature Limit Set Point
1.3.6.1.4.1.9839.2.1.2.24Scalardelta-lmread-writecurrentT+H Values: Mean/Local Diff. (aut. Changeover)
1.3.6.1.4.1.9839.2.1.3NodeintegerObjects
1.3.6.1.4.1.9839.2.1.3.1Scalarore-filtroread-onlycurrentAir Filter Working Houres
1.3.6.1.4.1.9839.2.1.3.2Scalarore-unitread-onlycurrentUnit Working Houres
1.3.6.1.4.1.9839.2.1.3.3Scalarore-compr1read-onlycurrentCompressor 1 Working Houres
1.3.6.1.4.1.9839.2.1.3.4Scalarore-compr2read-onlycurrentCompressor 2 Working Houres
1.3.6.1.4.1.9839.2.1.3.5Scalarore-compr3read-onlycurrentCompressor 3 Working Houres
1.3.6.1.4.1.9839.2.1.3.6Scalarore-compr4read-onlycurrentCompressor 4 Working Houres
1.3.6.1.4.1.9839.2.1.3.7Scalarore-heat1read-onlycurrentHeater 1 Working Houres
1.3.6.1.4.1.9839.2.1.3.8Scalarore-heat2read-onlycurrentHeater 2 Working Houres
1.3.6.1.4.1.9839.2.1.3.9Scalarore-umidread-onlycurrentHumidifier Working Houres
1.3.6.1.4.1.9839.2.1.3.12Scalarhdiffread-writecurrentDehumidification Proportional Band
1.3.6.1.4.1.9839.2.1.3.13Scalarhu-diffread-writecurrentHumidification Proportional Band
1.3.6.1.4.1.9839.2.1.3.14Scalarhh-setread-writecurrentHigh Relative Humidity Alarm Threshold
1.3.6.1.4.1.9839.2.1.3.15Scalarlh-setread-writecurrentLow Relative Humidity Alarm Threshold
1.3.6.1.4.1.9839.2.1.3.16Scalarhsetread-writecurrentDehumidification Set Point
1.3.6.1.4.1.9839.2.1.3.17Scalarhset-smread-writecurrentSetback Mode: Dehumidification Set Point
1.3.6.1.4.1.9839.2.1.3.18Scalarhu-setread-writecurrentHumidification Set Point
1.3.6.1.4.1.9839.2.1.3.19Scalarhu-set-smread-writecurrentSetback Mode: Humidification Set Point
1.3.6.1.4.1.9839.2.1.3.20Scalarrestart-delayread-writecurrentRestart Delay
1.3.6.1.4.1.9839.2.1.3.21Scalarregul-delayread-writecurrentRegulation Start Transitory
1.3.6.1.4.1.9839.2.1.3.22Scalartime-lowpread-writecurrentLow Pressure Delay
1.3.6.1.4.1.9839.2.1.3.23Scalaralarm-delayread-writecurrentRoom T+H Alarm Delay
1.3.6.1.4.1.9839.2.1.3.24Scalarexc-timeread-writecurrentAnti-Hunting Constant of Room Regulation
1.3.6.1.4.1.9839.2.1.3.25Scalart-std-byread-writecurrentStand-by Cycle Base Time
1.3.6.1.4.1.9839.2.1.3.27Scalarlan-unitread-writecurrentTotal of units connected in LAN
1.3.6.1.4.1.9839.2.1.3.28Scalarciclo-smread-writecurrentSet Back Mode: Fan Cyclical Start Interval