UNCDZ-MIB
128 objects
This is the MIB module for the UNIFLAIR UNCDZ device.
Imported Objects
| SNMPv2-CONF | OBJECT-GROUP |
| SNMPv2-MIB | sysContact sysLocation sysName |
| SNMPv2-SMI | enterprises Integer32 MODULE-IDENTITY OBJECT-TYPE |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.9839 | Nodecarel | |||
| 1.3.6.1.4.1.9839.1 | Nodesystm | |||
| 1.3.6.1.4.1.9839.1.1 | ScalaragentRelease | read-only | current | Release of the Agent. |
| 1.3.6.1.4.1.9839.1.2 | ScalaragentCode | read-only | current | Code of the Agent. 2=pCOWeb. |
| 1.3.6.1.4.1.9839.2 | Nodeinstruments | |||
| 1.3.6.1.4.1.9839.2.0 | NodepCOWebInfo | |||
| 1.3.6.1.4.1.9839.2.0.10 | NodepCOStatusgroup | |||
| 1.3.6.1.4.1.9839.2.0.10.1 | ScalarpCOId1-Status | read-only | current | Status of pCOId1. 0=Offline, 1=Init, 2=Online |
| 1.3.6.1.4.1.9839.2.0.11 | NodepCOErrorsNumbergroup | |||
| 1.3.6.1.4.1.9839.2.0.11.1 | ScalarpCOId1-ErrorsNumber | read-only | current | Number of Communication Errors from pCOId1 to pCOWeb. |
| 1.3.6.1.4.1.9839.2.1 | Identityuncdz-MIB | This is the MIB module for the UNIFLAIR UNCDZ device. | ||
| 1.3.6.1.4.1.9839.2.1.1 | NodedigitalObjects | |||
| 1.3.6.1.4.1.9839.2.1.1.1 | Scalarvent-on | read-only | current | System On (Fan) |
| 1.3.6.1.4.1.9839.2.1.1.2 | Scalarcompressore1 | read-only | current | Compressor 1 |
| 1.3.6.1.4.1.9839.2.1.1.3 | Scalarcompressore2 | read-only | current | Compressor 2 |
| 1.3.6.1.4.1.9839.2.1.1.4 | Scalarcompressore3 | read-only | current | Compressor 3 |
| 1.3.6.1.4.1.9839.2.1.1.5 | Scalarcompressore4 | read-only | current | Compressor 4 |
| 1.3.6.1.4.1.9839.2.1.1.6 | Scalarout-h1 | read-only | current | Heating 1 |
| 1.3.6.1.4.1.9839.2.1.1.7 | Scalarout-h2 | read-only | current | Heating 2 |
| 1.3.6.1.4.1.9839.2.1.1.8 | Scalarout-h3 | read-only | current | Heating 3 |
| 1.3.6.1.4.1.9839.2.1.1.9 | Scalargas-caldo-on | read-only | current | Hot Gas Coil |
| 1.3.6.1.4.1.9839.2.1.1.10 | Scalaron-deum | read-only | current | Dehumidification |
| 1.3.6.1.4.1.9839.2.1.1.11 | Scalarpower | read-only | current | Humidification |
| 1.3.6.1.4.1.9839.2.1.1.12 | Scalarmal-access | read-only | current | Tampering Alarm |
| 1.3.6.1.4.1.9839.2.1.1.13 | Scalarmal-ata | read-only | current | Alarm: Room High Temperature |
| 1.3.6.1.4.1.9839.2.1.1.14 | Scalarmal-bta | read-only | current | Alarm: Room Low Temperature |
| 1.3.6.1.4.1.9839.2.1.1.15 | Scalarmal-aua | read-only | current | Alarm: Room High Humidity |
| 1.3.6.1.4.1.9839.2.1.1.16 | Scalarmal-bua | read-only | current | Alarm: Room Low Humidity |
| 1.3.6.1.4.1.9839.2.1.1.17 | Scalarmal-eap | read-only | current | Alarm: Room High/Low Temp./Humid.(Ext. Devices) |
| 1.3.6.1.4.1.9839.2.1.1.18 | Scalarmal-filter | read-only | current | Alarm: Clogged Filter |
| 1.3.6.1.4.1.9839.2.1.1.19 | Scalarmal-flood | read-only | current | Alarm: Water Leakage Detected |
| 1.3.6.1.4.1.9839.2.1.1.20 | Scalarmal-flux | read-only | current | Alarm: Loss of Air Flow |
| 1.3.6.1.4.1.9839.2.1.1.21 | Scalarmal-heater | read-only | current | Alarm: Heater Overheating |
| 1.3.6.1.4.1.9839.2.1.1.22 | Scalarmal-hp1 | read-only | current | Alarm: High Pressure 1 |
| 1.3.6.1.4.1.9839.2.1.1.23 | Scalarmal-hp2 | read-only | current | Alarm: High Pressure 2 |
| 1.3.6.1.4.1.9839.2.1.1.24 | Scalarmal-lp1 | read-only | current | Alarm: Low Pressure 1 |
| 1.3.6.1.4.1.9839.2.1.1.25 | Scalarmal-lp2 | read-only | current | Alarm: Low Pressure 2 |
| 1.3.6.1.4.1.9839.2.1.1.26 | Scalarmal-phase | read-only | current | Alarm: Wrong phase sequence |
| 1.3.6.1.4.1.9839.2.1.1.27 | Scalarmal-smoke | read-only | current | Alarm: SMOKE-FIRE DETECTED |
| 1.3.6.1.4.1.9839.2.1.1.28 | Scalarmal-lan | read-only | current | Alarm: Interrupted LAN |
| 1.3.6.1.4.1.9839.2.1.1.29 | Scalarmal-hcurr | read-only | current | Humidifier Alarm: High Current |
| 1.3.6.1.4.1.9839.2.1.1.30 | Scalarmal-nopower | read-only | current | Humidifier Alarm: Power Loss |
| 1.3.6.1.4.1.9839.2.1.1.31 | Scalarmal-nowater | read-only | current | Humidifier Alarm: Water Loss |
| 1.3.6.1.4.1.9839.2.1.1.32 | Scalarmal-cw-dh | read-only | current | Alarm: Chilled Water Temp. too High for Dehumidification |
| 1.3.6.1.4.1.9839.2.1.1.33 | Scalarmal-tc-cw | read-only | current | Alarm: CW Valve Failure or Water Flow too Low |
| 1.3.6.1.4.1.9839.2.1.1.34 | Scalarmal-wflow | read-only | current | Alarm: Loss of Water flow |
| 1.3.6.1.4.1.9839.2.1.1.35 | Scalarmal-wht | read-only | current | Alarm: High chilled water temp. |
| 1.3.6.1.4.1.9839.2.1.1.36 | Scalarmal-sonda-ta | read-only | current | Alarm: Room air Sensor Failure/Disconnected |
| 1.3.6.1.4.1.9839.2.1.1.37 | Scalarmal-sonda-tac | read-only | current | Alarm: Hot water Sensor Failure/Disconnected |
| 1.3.6.1.4.1.9839.2.1.1.38 | Scalarmal-sonda-tc | read-only | current | Alarm: Condensing water Sensor Failure/Disconnect. |
| 1.3.6.1.4.1.9839.2.1.1.39 | Scalarmal-sonda-te | read-only | current | Alarm: Outdoor temp. Sensor Failure/Disconnected |
| 1.3.6.1.4.1.9839.2.1.1.40 | Scalarmal-sonda-tm | read-only | current | Alarm: Delivery temp. Sensor Failure/Disconnected |
| 1.3.6.1.4.1.9839.2.1.1.41 | Scalarmal-sonda-ua | read-only | current | Alarm: Rel. Humidity Sensor Failure/Disconnected |
| 1.3.6.1.4.1.9839.2.1.1.42 | Scalarmal-ore-compr1 | read-only | current | Service Alarm: Compressor 1 hour counter threshold |
| 1.3.6.1.4.1.9839.2.1.1.43 | Scalarmal-ore-compr2 | read-only | current | Service Alarm: Compressor 2 hour counter threshold |
| 1.3.6.1.4.1.9839.2.1.1.44 | Scalarmal-ore-compr3 | read-only | current | Service Alarm: Compressor 3 hour counter threshold |
| 1.3.6.1.4.1.9839.2.1.1.45 | Scalarmal-ore-compr4 | read-only | current | Service Alarm: Compressor 4 hour counter threshold |
| 1.3.6.1.4.1.9839.2.1.1.46 | Scalarmal-ore-filtro | read-only | current | Service Alarm: Air Filter hour counter threshold |
| 1.3.6.1.4.1.9839.2.1.1.47 | Scalarmal-ore-risc1 | read-only | current | Service Alarm: Heater 1 hour counter threshold |
| 1.3.6.1.4.1.9839.2.1.1.48 | Scalarmal-ore-risc2 | read-only | current | Service Alarm: Heater 2 hour counter threshold |
| 1.3.6.1.4.1.9839.2.1.1.49 | Scalarmal-ore-umid | read-only | current | Service Alarm: Humidifier hour counter threshold |
| 1.3.6.1.4.1.9839.2.1.1.50 | Scalarmal-ore-unit | read-only | current | Service Alarm: Unit hour counter threshold |
| 1.3.6.1.4.1.9839.2.1.1.51 | Scalarglb-al | read-only | current | General Alarm |
| 1.3.6.1.4.1.9839.2.1.1.52 | Scalaror-al-2lev | read-only | current | 2nd Level Alarm |
| 1.3.6.1.4.1.9839.2.1.1.53 | Scalarrange-t-ext | read-only | current | Outdoor Temp. Sensor Fitted |
| 1.3.6.1.4.1.9839.2.1.1.54 | Scalarrange-t-circ | read-only | current | Closed Circuit (or Chilled) Water Temperature Sensor Fitted |
| 1.3.6.1.4.1.9839.2.1.1.55 | Scalarrange-t-man | read-only | current | Delivery Temp. Sensor Fitted |
| 1.3.6.1.4.1.9839.2.1.1.56 | Scalarrange-t-ac | read-only | current | Hot water temp. Sensor Fitted |
| 1.3.6.1.4.1.9839.2.1.1.57 | Scalarumid-al | read-only | current | Humidifier general alarm |
| 1.3.6.1.4.1.9839.2.1.1.58 | Scalarrange-u-amb | read-only | current | Relative Humidity Sensor Fitted |
| 1.3.6.1.4.1.9839.2.1.1.60 | Scalark-syson | read-write | current | Unit Remote Switch-On/Off Control |
| 1.3.6.1.4.1.9839.2.1.1.61 | Scalarxs-res-al | read-write | current | Buzzer and Alarm Remote Reset Control |
| 1.3.6.1.4.1.9839.2.1.1.63 | Scalarsleep-mode | read-write | current | Set Back Mode (Sleep Mode) |
| 1.3.6.1.4.1.9839.2.1.1.64 | Scalartest-sm | read-write | current | Set Back mode: Cyclical Start of Fan |
| 1.3.6.1.4.1.9839.2.1.1.65 | Scalarab-mediath | read-write | current | Usage of T+ H Values: Local (0) / Mean (1) |
| 1.3.6.1.4.1.9839.2.1.1.66 | Scalarustdby1-2 | read-write | current | No. Of Stand-by Units: one (0) / two (1) |
| 1.3.6.1.4.1.9839.2.1.1.67 | Scalaremerg | read-only | current | Unit in Emergency operation |
| 1.3.6.1.4.1.9839.2.1.2 | NodeanalogObjects | |||
| 1.3.6.1.4.1.9839.2.1.2.1 | Scalartemp-amb | read-only | current | Room Temperature |
| 1.3.6.1.4.1.9839.2.1.2.2 | Scalartemp-ext | read-only | current | Outdoor Temperature |
| 1.3.6.1.4.1.9839.2.1.2.3 | Scalartemp-mand | read-only | current | Delivery Air Temperature |
| 1.3.6.1.4.1.9839.2.1.2.4 | Scalartemp-circ | read-only | current | Closed Circuit (or Chilled) Water Temperature |
| 1.3.6.1.4.1.9839.2.1.2.5 | Scalartemp-ac | read-only | current | Hot Water Temperature |
| 1.3.6.1.4.1.9839.2.1.2.6 | Scalarumid-amb | read-only | current | Room Relative Humidity |
| 1.3.6.1.4.1.9839.2.1.2.7 | Scalart-set | read-write | current | Cooling Set Point |
| 1.3.6.1.4.1.9839.2.1.2.8 | Scalart-diff | read-write | current | Cooling Prop.Band |
| 1.3.6.1.4.1.9839.2.1.2.9 | Scalart-set-c | read-write | current | Heating Set point |
| 1.3.6.1.4.1.9839.2.1.2.10 | Scalart-diff-c | read-write | current | Heating Prop.Band |
| 1.3.6.1.4.1.9839.2.1.2.11 | Scalarht-set | read-write | current | Room High Temp. Alarm Threshold |
| 1.3.6.1.4.1.9839.2.1.2.12 | Scalarlt-set | read-write | current | Room Low Temp. Alarm Threshold |
| 1.3.6.1.4.1.9839.2.1.2.13 | Scalart-set-sm | read-write | current | Setback Mode: Cooling Set Point |
| 1.3.6.1.4.1.9839.2.1.2.14 | Scalart-set-c-sm | read-write | current | Setback Mode: Heating Set Point |
| 1.3.6.1.4.1.9839.2.1.2.15 | Scalart-cw-dh | read-write | current | CW Set Point to Start Dehumidification Cycle |
| 1.3.6.1.4.1.9839.2.1.2.16 | Scalarhtset-cw | read-write | current | CW High Temperature Alarm Threshold |
| 1.3.6.1.4.1.9839.2.1.2.17 | Scalart-set-cw | read-write | current | CW Set Point to Start CW Operating Mode (TC only) |
| 1.3.6.1.4.1.9839.2.1.2.18 | Scalart-rc-es | read-write | current | Rad-cooler Set Point in E.S. Mode (ES Only) |
| 1.3.6.1.4.1.9839.2.1.2.19 | Scalart-rc-est | read-write | current | Rad-cooler Set Point in DX Mode (ES Only) |
| 1.3.6.1.4.1.9839.2.1.2.20 | Scalarrampa-valv | read-only | current | 0-10V Ramp 1 Value (CW Valve Ramp) |
| 1.3.6.1.4.1.9839.2.1.2.21 | Scalaranaout2 | read-only | current | 0-10V Ramp 2 Value (HW Valve/Rad Cooler Ramp) |
| 1.3.6.1.4.1.9839.2.1.2.22 | Scalarsteam-production | read-only | current | Humidifier: steam capacity |
| 1.3.6.1.4.1.9839.2.1.2.23 | Scalart-set-lm | read-write | current | Delivery Air Temperature Limit Set Point |
| 1.3.6.1.4.1.9839.2.1.2.24 | Scalardelta-lm | read-write | current | T+H Values: Mean/Local Diff. (aut. Changeover) |
| 1.3.6.1.4.1.9839.2.1.3 | NodeintegerObjects | |||
| 1.3.6.1.4.1.9839.2.1.3.1 | Scalarore-filtro | read-only | current | Air Filter Working Houres |
| 1.3.6.1.4.1.9839.2.1.3.2 | Scalarore-unit | read-only | current | Unit Working Houres |
| 1.3.6.1.4.1.9839.2.1.3.3 | Scalarore-compr1 | read-only | current | Compressor 1 Working Houres |
| 1.3.6.1.4.1.9839.2.1.3.4 | Scalarore-compr2 | read-only | current | Compressor 2 Working Houres |
| 1.3.6.1.4.1.9839.2.1.3.5 | Scalarore-compr3 | read-only | current | Compressor 3 Working Houres |
| 1.3.6.1.4.1.9839.2.1.3.6 | Scalarore-compr4 | read-only | current | Compressor 4 Working Houres |
| 1.3.6.1.4.1.9839.2.1.3.7 | Scalarore-heat1 | read-only | current | Heater 1 Working Houres |
| 1.3.6.1.4.1.9839.2.1.3.8 | Scalarore-heat2 | read-only | current | Heater 2 Working Houres |
| 1.3.6.1.4.1.9839.2.1.3.9 | Scalarore-umid | read-only | current | Humidifier Working Houres |
| 1.3.6.1.4.1.9839.2.1.3.12 | Scalarhdiff | read-write | current | Dehumidification Proportional Band |
| 1.3.6.1.4.1.9839.2.1.3.13 | Scalarhu-diff | read-write | current | Humidification Proportional Band |
| 1.3.6.1.4.1.9839.2.1.3.14 | Scalarhh-set | read-write | current | High Relative Humidity Alarm Threshold |
| 1.3.6.1.4.1.9839.2.1.3.15 | Scalarlh-set | read-write | current | Low Relative Humidity Alarm Threshold |
| 1.3.6.1.4.1.9839.2.1.3.16 | Scalarhset | read-write | current | Dehumidification Set Point |
| 1.3.6.1.4.1.9839.2.1.3.17 | Scalarhset-sm | read-write | current | Setback Mode: Dehumidification Set Point |
| 1.3.6.1.4.1.9839.2.1.3.18 | Scalarhu-set | read-write | current | Humidification Set Point |
| 1.3.6.1.4.1.9839.2.1.3.19 | Scalarhu-set-sm | read-write | current | Setback Mode: Humidification Set Point |
| 1.3.6.1.4.1.9839.2.1.3.20 | Scalarrestart-delay | read-write | current | Restart Delay |
| 1.3.6.1.4.1.9839.2.1.3.21 | Scalarregul-delay | read-write | current | Regulation Start Transitory |
| 1.3.6.1.4.1.9839.2.1.3.22 | Scalartime-lowp | read-write | current | Low Pressure Delay |
| 1.3.6.1.4.1.9839.2.1.3.23 | Scalaralarm-delay | read-write | current | Room T+H Alarm Delay |
| 1.3.6.1.4.1.9839.2.1.3.24 | Scalarexc-time | read-write | current | Anti-Hunting Constant of Room Regulation |
| 1.3.6.1.4.1.9839.2.1.3.25 | Scalart-std-by | read-write | current | Stand-by Cycle Base Time |
| 1.3.6.1.4.1.9839.2.1.3.27 | Scalarlan-unit | read-write | current | Total of units connected in LAN |
| 1.3.6.1.4.1.9839.2.1.3.28 | Scalarciclo-sm | read-write | current | Set Back Mode: Fan Cyclical Start Interval |