MIB Viewer

UPS-MIB

150 objects
The MIB module to describe Uninterruptible Power Supplies.
Imported Objects
SNMPv2-CONFMODULE-COMPLIANCE OBJECT-GROUP
SNMPv2-SMICounter32 Gauge32 Integer32 mib-2 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-IDENTITY OBJECT-TYPE
SNMPv2-TCAutonomousType DisplayString TestAndIncr TEXTUAL-CONVENTION TimeInterval TimeStamp
OIDNameAccessStatusDescription
1.3.6.1.2.1.33IdentityupsMIBThe MIB module to describe Uninterruptible Power Supplies.
1.3.6.1.2.1.33.1NodeupsObjects
1.3.6.1.2.1.33.1.1NodeupsIdent
1.3.6.1.2.1.33.1.1.1ScalarupsIdentManufacturerread-onlycurrentThe name of the UPS manufacturer.
1.3.6.1.2.1.33.1.1.2ScalarupsIdentModelread-onlycurrentThe UPS Model designation.
1.3.6.1.2.1.33.1.1.3ScalarupsIdentUPSSoftwareVersionread-onlycurrentThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.
1.3.6.1.2.1.33.1.1.4ScalarupsIdentAgentSoftwareVersionread-onlycurrentThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.
1.3.6.1.2.1.33.1.1.5ScalarupsIdentNameread-writecurrentA string identifying the UPS. This object should be set by the administrator.
1.3.6.1.2.1.33.1.1.6ScalarupsIdentAttachedDevicesread-writecurrentA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.
1.3.6.1.2.1.33.1.2NodeupsBattery
1.3.6.1.2.1.33.1.2.1ScalarupsBatteryStatusread-onlycurrentThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfi…
1.3.6.1.2.1.33.1.2.2ScalarupsSecondsOnBatteryread-onlycurrentIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.2.1.33.1.2.3ScalarupsEstimatedMinutesRemainingread-onlycurrentAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.2.1.33.1.2.4ScalarupsEstimatedChargeRemainingread-onlycurrentAn estimate of the battery charge remaining expressed as a percent of full charge.
1.3.6.1.2.1.33.1.2.5ScalarupsBatteryVoltageread-onlycurrentThe magnitude of the present battery voltage.
1.3.6.1.2.1.33.1.2.6ScalarupsBatteryCurrentread-onlycurrentThe present battery current.
1.3.6.1.2.1.33.1.2.7ScalarupsBatteryTemperatureread-onlycurrentThe ambient temperature at or near the UPS Battery casing.
1.3.6.1.2.1.33.1.3NodeupsInput
1.3.6.1.2.1.33.1.3.1ScalarupsInputLineBadsread-onlycurrentA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i…
1.3.6.1.2.1.33.1.3.2ScalarupsInputNumLinesread-onlycurrentThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.
1.3.6.1.2.1.33.1.3.3TableupsInputTablenot-accessiblecurrentA list of input table entries. The number of entries is given by the value of upsInputNumLines.
1.3.6.1.2.1.33.1.3.3.1RowupsInputEntrynot-accessiblecurrentAn entry containing information applicable to a particular input line.
1.3.6.1.2.1.33.1.3.3.1.1ColumnupsInputLineIndexnot-accessiblecurrentThe input line identifier.
1.3.6.1.2.1.33.1.3.3.1.2ColumnupsInputFrequencyread-onlycurrentThe present input frequency.
1.3.6.1.2.1.33.1.3.3.1.3ColumnupsInputVoltageread-onlycurrentThe magnitude of the present input voltage.
1.3.6.1.2.1.33.1.3.3.1.4ColumnupsInputCurrentread-onlycurrentThe magnitude of the present input current.
1.3.6.1.2.1.33.1.3.3.1.5ColumnupsInputTruePowerread-onlycurrentThe magnitude of the present input true power.
1.3.6.1.2.1.33.1.4NodeupsOutput
1.3.6.1.2.1.33.1.4.1ScalarupsOutputSourceread-onlycurrentThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.2.1.33.1.4.2ScalarupsOutputFrequencyread-onlycurrentThe present output frequency.
1.3.6.1.2.1.33.1.4.3ScalarupsOutputNumLinesread-onlycurrentThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.
1.3.6.1.2.1.33.1.4.4TableupsOutputTablenot-accessiblecurrentA list of output table entries. The number of entries is given by the value of upsOutputNumLines.
1.3.6.1.2.1.33.1.4.4.1RowupsOutputEntrynot-accessiblecurrentAn entry containing information applicable to a particular output line.
1.3.6.1.2.1.33.1.4.4.1.1ColumnupsOutputLineIndexnot-accessiblecurrentThe output line identifier.
1.3.6.1.2.1.33.1.4.4.1.2ColumnupsOutputVoltageread-onlycurrentThe present output voltage.
1.3.6.1.2.1.33.1.4.4.1.3ColumnupsOutputCurrentread-onlycurrentThe present output current.
1.3.6.1.2.1.33.1.4.4.1.4ColumnupsOutputPowerread-onlycurrentThe present output true power.
1.3.6.1.2.1.33.1.4.4.1.5ColumnupsOutputPercentLoadread-onlycurrentThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent…
1.3.6.1.2.1.33.1.5NodeupsBypass
1.3.6.1.2.1.33.1.5.1ScalarupsBypassFrequencyread-onlycurrentThe present bypass frequency.
1.3.6.1.2.1.33.1.5.2ScalarupsBypassNumLinesread-onlycurrentThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
1.3.6.1.2.1.33.1.5.3TableupsBypassTablenot-accessiblecurrentA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.
1.3.6.1.2.1.33.1.5.3.1RowupsBypassEntrynot-accessiblecurrentAn entry containing information applicable to a particular bypass input.
1.3.6.1.2.1.33.1.5.3.1.1ColumnupsBypassLineIndexnot-accessiblecurrentThe bypass line identifier.
1.3.6.1.2.1.33.1.5.3.1.2ColumnupsBypassVoltageread-onlycurrentThe present bypass voltage.
1.3.6.1.2.1.33.1.5.3.1.3ColumnupsBypassCurrentread-onlycurrentThe present bypass current.
1.3.6.1.2.1.33.1.5.3.1.4ColumnupsBypassPowerread-onlycurrentThe present true power conveyed by the bypass.
1.3.6.1.2.1.33.1.6NodeupsAlarm
1.3.6.1.2.1.33.1.6.1ScalarupsAlarmsPresentread-onlycurrentThe present number of active alarm conditions.
1.3.6.1.2.1.33.1.6.2TableupsAlarmTablenot-accessiblecurrentA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.2.1.33.1.6.2.1RowupsAlarmEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.
1.3.6.1.2.1.33.1.6.2.1.1ColumnupsAlarmIdnot-accessiblecurrentA unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.2.1.33.1.6.2.1.2ColumnupsAlarmDescrread-onlycurrentA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.2.1.33.1.6.2.1.3ColumnupsAlarmTimeread-onlycurrentThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag…
1.3.6.1.2.1.33.1.6.3NodeupsWellKnownAlarms
1.3.6.1.2.1.33.1.6.3.1IdentityupsAlarmBatteryBadcurrentOne or more batteries have been determined to require replacement.
1.3.6.1.2.1.33.1.6.3.2IdentityupsAlarmOnBatterycurrentThe UPS is drawing power from the batteries.
1.3.6.1.2.1.33.1.6.3.3IdentityupsAlarmLowBatterycurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
1.3.6.1.2.1.33.1.6.3.4IdentityupsAlarmDepletedBatterycurrentThe UPS will be unable to sustain the present load when and if the utility power is lost.
1.3.6.1.2.1.33.1.6.3.5IdentityupsAlarmTempBadcurrentA temperature is out of tolerance.
1.3.6.1.2.1.33.1.6.3.6IdentityupsAlarmInputBadcurrentAn input condition is out of tolerance.
1.3.6.1.2.1.33.1.6.3.7IdentityupsAlarmOutputBadcurrentAn output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.2.1.33.1.6.3.8IdentityupsAlarmOutputOverloadcurrentThe output load exceeds the UPS output capacity.
1.3.6.1.2.1.33.1.6.3.9IdentityupsAlarmOnBypasscurrentThe Bypass is presently engaged on the UPS.
1.3.6.1.2.1.33.1.6.3.10IdentityupsAlarmBypassBadcurrentThe Bypass is out of tolerance.
1.3.6.1.2.1.33.1.6.3.11IdentityupsAlarmOutputOffAsRequestedcurrentThe UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.2.1.33.1.6.3.12IdentityupsAlarmUpsOffAsRequestedcurrentThe entire UPS has shutdown as commanded.
1.3.6.1.2.1.33.1.6.3.13IdentityupsAlarmChargerFailedcurrentAn uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.2.1.33.1.6.3.14IdentityupsAlarmUpsOutputOffcurrentThe output of the UPS is in the off state.
1.3.6.1.2.1.33.1.6.3.15IdentityupsAlarmUpsSystemOffcurrentThe UPS system is in the off state.
1.3.6.1.2.1.33.1.6.3.16IdentityupsAlarmFanFailurecurrentThe failure of one or more fans in the UPS has been detected.
1.3.6.1.2.1.33.1.6.3.17IdentityupsAlarmFuseFailurecurrentThe failure of one or more fuses has been detected.
1.3.6.1.2.1.33.1.6.3.18IdentityupsAlarmGeneralFaultcurrentA general fault in the UPS has been detected.
1.3.6.1.2.1.33.1.6.3.19IdentityupsAlarmDiagnosticTestFailedcurrentThe result of the last diagnostic test indicates a failure.
1.3.6.1.2.1.33.1.6.3.20IdentityupsAlarmCommunicationsLostcurrentA problem has been encountered in the communications between the agent and the UPS.
1.3.6.1.2.1.33.1.6.3.21IdentityupsAlarmAwaitingPowercurrentThe UPS output is off and the UPS is awaiting the return of input power.
1.3.6.1.2.1.33.1.6.3.22IdentityupsAlarmShutdownPendingcurrentA upsShutdownAfterDelay countdown is underway.
1.3.6.1.2.1.33.1.6.3.23IdentityupsAlarmShutdownImminentcurrentThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.
1.3.6.1.2.1.33.1.6.3.24IdentityupsAlarmTestInProgresscurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.2.1.33.1.7NodeupsTest
1.3.6.1.2.1.33.1.7.1ScalarupsTestIdread-writecurrentThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this docu…
1.3.6.1.2.1.33.1.7.2ScalarupsTestSpinLockread-writecurrentA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress a…
1.3.6.1.2.1.33.1.7.3ScalarupsTestResultsSummaryread-onlycurrentThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test complete…
1.3.6.1.2.1.33.1.7.4ScalarupsTestResultsDetailread-onlycurrentAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.
1.3.6.1.2.1.33.1.7.5ScalarupsTestStartTimeread-onlycurrentThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of…
1.3.6.1.2.1.33.1.7.6ScalarupsTestElapsedTimeread-onlycurrentThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of …
1.3.6.1.2.1.33.1.7.7NodeupsWellKnownTests
1.3.6.1.2.1.33.1.7.7.1IdentityupsTestNoTestsInitiatedcurrentNo tests have been initiated and no test is in progress.
1.3.6.1.2.1.33.1.7.7.2IdentityupsTestAbortTestInProgresscurrentThe test in progress is to be aborted / the test in progress was aborted.
1.3.6.1.2.1.33.1.7.7.3IdentityupsTestGeneralSystemsTestcurrentThe manufacturer's standard test of UPS device systems.
1.3.6.1.2.1.33.1.7.7.4IdentityupsTestQuickBatteryTestcurrentA test that is sufficient to determine if the battery needs replacement.
1.3.6.1.2.1.33.1.7.7.5IdentityupsTestDeepBatteryCalibrationcurrentThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high deg…
1.3.6.1.2.1.33.1.8NodeupsControl
1.3.6.1.2.1.33.1.8.1ScalarupsShutdownTyperead-writecurrentThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach…
1.3.6.1.2.1.33.1.8.2ScalarupsShutdownAfterDelayread-writecurrentSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdo…
1.3.6.1.2.1.33.1.8.3ScalarupsStartupAfterDelayread-writecurrentSetting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause …
1.3.6.1.2.1.33.1.8.4ScalarupsRebootWithDurationread-writecurrentSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the ti…
1.3.6.1.2.1.33.1.8.5ScalarupsAutoRestartread-writecurrentSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutd…
1.3.6.1.2.1.33.1.9NodeupsConfig
1.3.6.1.2.1.33.1.9.1ScalarupsConfigInputVoltageread-writecurrentThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a v…
1.3.6.1.2.1.33.1.9.2ScalarupsConfigInputFreqread-writecurrentThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is no…
1.3.6.1.2.1.33.1.9.3ScalarupsConfigOutputVoltageread-writecurrentThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a …
1.3.6.1.2.1.33.1.9.4ScalarupsConfigOutputFreqread-writecurrentThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is n…
1.3.6.1.2.1.33.1.9.5ScalarupsConfigOutputVAread-onlycurrentThe magnitude of the nominal Volt-Amp rating.
1.3.6.1.2.1.33.1.9.6ScalarupsConfigOutputPowerread-onlycurrentThe magnitude of the nominal true power rating.
1.3.6.1.2.1.33.1.9.7ScalarupsConfigLowBattTimeread-writecurrentThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the …
1.3.6.1.2.1.33.1.9.8ScalarupsConfigAudibleStatusread-writecurrentThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this …
1.3.6.1.2.1.33.1.9.9ScalarupsConfigLowVoltageTransferPointread-writecurrentThe minimum input line voltage allowed before the UPS system transfers to battery backup.
1.3.6.1.2.1.33.1.9.10ScalarupsConfigHighVoltageTransferPointread-writecurrentThe maximum line voltage allowed before the UPS system transfers to battery backup.
1.3.6.1.2.1.33.2NodeupsTraps
1.3.6.1.2.1.33.2.1NotificationupsTrapOnBatterycurrentThe UPS is operating on battery power. This trap is persistent and is resent at one minute intervals until the UPS either turns off or is no longer running on …
1.3.6.1.2.1.33.2.2NotificationupsTrapTestCompletedcurrentThis trap is sent upon completion of a UPS diagnostic test.
1.3.6.1.2.1.33.2.3NotificationupsTrapAlarmEntryAddedcurrentThis trap is sent each time an alarm is inserted into to the alarm table. It is sent on the insertion of all alarms except for upsAlarmOnBattery and upsAlarmTe…
1.3.6.1.2.1.33.2.4NotificationupsTrapAlarmEntryRemovedcurrentThis trap is sent each time an alarm is removed from the alarm table. It is sent on the removal of all alarms except for upsAlarmTestInProgress.
1.3.6.1.2.1.33.3NodeupsConformance
1.3.6.1.2.1.33.3.1NodeupsCompliances
1.3.6.1.2.1.33.3.1.1ComplianceupsSubsetComplianceread-onlycurrentThe compliance statement for UPSs that only support the two-contact communication protocol.
1.3.6.1.2.1.33.3.1.2ComplianceupsBasicComplianceread-onlycurrentThe compliance statement for UPSs that support full-featured functions, such as control.
1.3.6.1.2.1.33.3.1.3ComplianceupsFullComplianceread-onlycurrentThe compliance statement for UPSs that support advanced full-featured functions.
1.3.6.1.2.1.33.3.2NodeupsGroups
1.3.6.1.2.1.33.3.2.1NodeupsSubsetGroups
1.3.6.1.2.1.33.3.2.1.1GroupupsSubsetIdentGroupcurrentThe upsSubsetIdentGroup defines objects which are common across all UPSs which meet subset compliance. Most devices which conform to the upsSubsetIdentGroup wi…
1.3.6.1.2.1.33.3.2.1.2GroupupsSubsetBatteryGroupcurrentThe upsSubsetBatteryGroup defines the objects that are common to battery groups of two-contact UPSs.
1.3.6.1.2.1.33.3.2.1.3GroupupsSubsetInputGroupcurrentThe upsSubsetInputGroup defines the objects that are common to the Input groups of two-contact UPSs.
1.3.6.1.2.1.33.3.2.1.4GroupupsSubsetOutputGroupcurrentThe upsSubsetOutputGroup defines the objects that are common to the Output groups of two-contact UPSs.
1.3.6.1.2.1.33.3.2.1.6GroupupsSubsetAlarmGroupcurrentThe upsSubsetAlarmGroup defines the objects that are common to the Alarm groups of two-contact UPSs.
1.3.6.1.2.1.33.3.2.1.8GroupupsSubsetControlGroupcurrentThe upsSubsetControlGroup defines the objects that are common to the Control groups of two-contact UPSs.
1.3.6.1.2.1.33.3.2.1.9GroupupsSubsetConfigGroupcurrentThe upsSubsetConfigGroup defines the objects that are common to the Config groups of two-contact UPSs.
1.3.6.1.2.1.33.3.2.2NodeupsBasicGroups
1.3.6.1.2.1.33.3.2.2.1GroupupsBasicIdentGroupcurrentThe upsBasicIdentGroup defines objects which are common to the Ident group of compliant UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.2.2GroupupsBasicBatteryGroupcurrentThe upsBasicBatteryGroup defines the objects that are common to the battery groups of compliant UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.2.3GroupupsBasicInputGroupcurrentThe upsBasicInputGroup defines the objects that are common to the Input groups of compliant UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.2.4GroupupsBasicOutputGroupcurrentThe upsBasicOutputGroup defines the objects that are common to the Output groups of compliant UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.2.5GroupupsBasicBypassGroupcurrentThe upsBasicBypassGroup defines the objects that are common to the Bypass groups of compliant UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.2.6GroupupsBasicAlarmGroupcurrentThe upsBasicAlarmGroup defines the objects that are common to the Alarm groups of compliant UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.2.7GroupupsBasicTestGroupcurrentThe upsBasicTestGroup defines the objects that are common to the Test groups of compliant UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.2.8GroupupsBasicControlGroupcurrentThe upsBasicControlGroup defines the objects that are common to the Control groups of compliant UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.2.9GroupupsBasicConfigGroupcurrentThe upsBasicConfigGroup defines the objects that are common to the Config groups of UPSs which support basic functions.
1.3.6.1.2.1.33.3.2.3NodeupsFullGroups
1.3.6.1.2.1.33.3.2.3.1GroupupsFullIdentGroupcurrentThe upsFullIdentGroup defines objects which are common to the Ident group of fully compliant UPSs.
1.3.6.1.2.1.33.3.2.3.2GroupupsFullBatteryGroupcurrentThe upsFullBatteryGroup defines the objects that are common to the battery groups of fully compliant UPSs.
1.3.6.1.2.1.33.3.2.3.3GroupupsFullInputGroupcurrentThe upsFullInputGroup defines the objects that are common to the Input groups of fully compliant UPSs.
1.3.6.1.2.1.33.3.2.3.4GroupupsFullOutputGroupcurrentThe upsFullOutputGroup defines the objects that are common to the Output groups of fully compliant UPSs.
1.3.6.1.2.1.33.3.2.3.5GroupupsFullBypassGroupcurrentThe upsFullBypassGroup defines the objects that are common to the Bypass groups of fully compliant UPSs.
1.3.6.1.2.1.33.3.2.3.6GroupupsFullAlarmGroupcurrentThe upsFullAlarmGroup defines the objects that are common to the Alarm groups of fully compliant UPSs.
1.3.6.1.2.1.33.3.2.3.7GroupupsFullTestGroupcurrentThe upsFullTestGroup defines the objects that are common to the Test groups of fully compliant UPSs.
1.3.6.1.2.1.33.3.2.3.8GroupupsFullControlGroupcurrentThe upsFullControlGroup defines the objects that are common to the Control groups of fully compliant UPSs.
1.3.6.1.2.1.33.3.2.3.9GroupupsFullConfigGroupcurrentThe upsFullConfigGroup defines the objects that are common to the Config groups of fully compliant UPSs.
Type Definitions
NameSyntaxStatusDescription
NonNegativeIntegerINTEGER (0..2147483647)currentThis data type is a non-negative value.
PositiveIntegerINTEGER (1..2147483647)currentThis data type is a non-zero and non-negative value.