UPS2-MIB

80 objects
No module-level DESCRIPTION found.
Imported Objects
CTRON-MIB-NAMESctUPS
RFC-1212OBJECT-TYPE
RFC1213-MIBDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.52.4.1.1.10.1NodeupsSystem
1.3.6.1.4.1.52.4.1.1.10.1.1ScalarupsNumUPSsread-onlymandatoryThe number of UPSs available.
1.3.6.1.4.1.52.4.1.1.10.2NodeupsId
1.3.6.1.4.1.52.4.1.1.10.2.1TableupsIdTablenot-accessiblemandatoryA list of identification table entries. The number of entries is given by the value of upsNumUPSs.
1.3.6.1.4.1.52.4.1.1.10.2.1.1RowupsIdEntrynot-accessiblemandatoryAn entry containing objects for a particular UPS.
1.3.6.1.4.1.52.4.1.1.10.2.1.1.1ColumnupsIndexread-onlymandatoryA unique value which identifies a particular UPS.
1.3.6.1.4.1.52.4.1.1.10.2.1.1.2ColumnupsNameread-writemandatoryThe UPS's name. A maximum of 8 characters may be specified. This object is initialized to the UPS's model name.
1.3.6.1.4.1.52.4.1.1.10.2.1.1.3ColumnupsModelTyperead-onlymandatoryThe UPS's base model type.
1.3.6.1.4.1.52.4.1.1.10.2.1.1.4ColumnupsFwVersionread-onlymandatoryThe UPS's firmware version.
1.3.6.1.4.1.52.4.1.1.10.2.1.1.5ColumnupsSerialNumberread-onlymandatoryThe UPS's serial number as set at the factory.
1.3.6.1.4.1.52.4.1.1.10.2.1.1.6ColumnupsManufDateread-onlymandatoryThe UPS's date of manufacture in the format mm/dd/yy.
1.3.6.1.4.1.52.4.1.1.10.3NodeupsBattery
1.3.6.1.4.1.52.4.1.1.10.3.1TableupsBatteryTablenot-accessiblemandatoryA list of battery table entries. The number of entries is given by the value of upsNumUPSs.
1.3.6.1.4.1.52.4.1.1.10.3.1.1RowupsBatteryEntrynot-accessiblemandatoryAn entry containing objects for a particular UPS.
1.3.6.1.4.1.52.4.1.1.10.3.1.1.1ColumnupsBatteryCapacityread-onlymandatoryThe UPS's remaining battery capacity expressed as a percent of the fully charged condition. The value of this object is the actual percentage * 10 (that is, to…
1.3.6.1.4.1.52.4.1.1.10.3.1.1.2ColumnupsBatteryVoltageread-onlymandatoryThe UPS's present battery voltage. The value of this object is the actual voltage * 100 (that is, to determine the actual voltage, divide the value of this obj…
1.3.6.1.4.1.52.4.1.1.10.3.1.1.3ColumnupsBatteryTestread-writemandatoryThis object may be written to initiate testing of the UPS's battery packs. Reading this object will always return a 0.
1.3.6.1.4.1.52.4.1.1.10.3.1.1.4ColumnupsBatteryTestResultread-onlymandatoryThe result of the last battery test performed.
1.3.6.1.4.1.52.4.1.1.10.3.1.1.5ColumnupsRunTimeCalibrationread-writemandatoryThis object may be written to initiate or terminate the test used to calibrate the returned run time value. This test will only run if battery capacity is 100%…
1.3.6.1.4.1.52.4.1.1.10.3.1.1.6ColumnupsEstimatedRunTimeRemainingread-onlymandatoryThe UPS's estimated remaining run time in minutes. The UPS may be queried when operating in the on-line, bypass, or on-battery modes of operation. The run time…
1.3.6.1.4.1.52.4.1.1.10.3.1.1.7ColumnupsTransferCauseread-onlymandatoryThe reason for the most recent transfer to on-battery operation.
1.3.6.1.4.1.52.4.1.1.10.3.1.1.8ColumnupsBatteryTestTimeread-writemandatoryThe frequency of execution of the UPS's automatic battery test. The test may be run immediately upon startup, upon startup and every 7 days thereafter, upon st…
1.3.6.1.4.1.52.4.1.1.10.3.1.1.9ColumnupsLowBatteryWarningread-writemandatoryThe interval between activation of the UPS's low battery alarm warnings and shutdown of the UPS.
1.3.6.1.4.1.52.4.1.1.10.4NodeupsInput
1.3.6.1.4.1.52.4.1.1.10.4.1TableupsInputTablenot-accessiblemandatoryA list of input table entries. The number of entries is given by the value of upsNumUPSs.
1.3.6.1.4.1.52.4.1.1.10.4.1.1RowupsInputEntrynot-accessiblemandatoryAn entry containing objects for a particular UPS.
1.3.6.1.4.1.52.4.1.1.10.4.1.1.1ColumnupsInputUtilityVoltageread-onlymandatoryThe UPS's utility voltage version.
1.3.6.1.4.1.52.4.1.1.10.4.1.1.2ColumnupsInputVoltageread-onlymandatoryThe UPS's measured utility input voltage. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of th…
1.3.6.1.4.1.52.4.1.1.10.4.1.1.3ColumnupsInputFailureSensitivityread-writemandatoryThe sensitivity of the UPS to rapid changes in utility voltage (e.g., blackouts, spikes, or notches) or abnormal changes in utility frequency.
1.3.6.1.4.1.52.4.1.1.10.4.1.1.4ColumnupsInputMaxVoltageread-onlymandatoryThe UPS's maximum input voltage recorded since this object was last read. The value of this object is the actual voltage * 10 (that is, to determine the actual…
1.3.6.1.4.1.52.4.1.1.10.4.1.1.5ColumnupsInputMinVoltageread-onlymandatoryThe UPS's minimum input voltage recorded since this object was last read. The value of this object is the actual voltage * 10 (that is, to determine the actual…
1.3.6.1.4.1.52.4.1.1.10.4.1.1.6ColumnupsInputFrequencyread-onlymandatoryThe UPS's present internal operating frequency in Hz. The value of this object is the actual frequency * 100 (that is, to determine the actual frequency, divid…
1.3.6.1.4.1.52.4.1.1.10.5NodeupsOutput
1.3.6.1.4.1.52.4.1.1.10.5.1TableupsOutputTablenot-accessiblemandatoryA list of output table entries. The number of entries is given by the value of upsNumUPSs.
1.3.6.1.4.1.52.4.1.1.10.5.1.1RowupsOutputEntrynot-accessiblemandatoryAn entry containing objects for a particular UPS.
1.3.6.1.4.1.52.4.1.1.10.5.1.1.1ColumnupsOutputVoltageread-onlymandatoryThe measured UPS output voltage. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object…
1.3.6.1.4.1.52.4.1.1.10.5.1.1.2ColumnupsOutputUtilityVoltageread-writemandatoryThe UPS's current on-battery output voltage setting (valid for 220/230/240 Vac version UPSs only). For other version UPSs, reading this object will always retu…
1.3.6.1.4.1.52.4.1.1.10.5.1.1.3ColumnupsOutputPowerread-onlymandatoryThe UPS's output load represented as a percentage of full rated load in Watts. The value of this object is the actual percentage * 10 (that is, to determine th…
1.3.6.1.4.1.52.4.1.1.10.6NodeupsStatus
1.3.6.1.4.1.52.4.1.1.10.6.1TableupsStatusTablenot-accessiblemandatoryA list of status table entries. The number of entries is given by the value of upsNumUPSs.
1.3.6.1.4.1.52.4.1.1.10.6.1.1RowupsStatusEntrynot-accessiblemandatoryAn entry containing objects for a particular UPS.
1.3.6.1.4.1.52.4.1.1.10.6.1.1.1ColumnupsStatusOperationalread-onlymandatoryThis object contains 8 bits of information about the current operational status of the UPS. The bits are encoded as follows: BIT 7: 1=replace battery condition…
1.3.6.1.4.1.52.4.1.1.10.6.1.1.2ColumnupsStatusFaultread-onlymandatoryThis object contains 8 bits of information about the current fault conditions of the UPS. The bits are encoded as follows: BIT 7: 1=UPS fault - internal temper…
1.3.6.1.4.1.52.4.1.1.10.6.1.1.3ColumnupsStatusTempread-onlymandatoryThe UPS's present internal operating temperature in degrees Fahrenheit. The value of this object is the actual temperature * 10 (that is, to determine the actu…
1.3.6.1.4.1.52.4.1.1.10.7NodeupsConfig
1.3.6.1.4.1.52.4.1.1.10.7.1TableupsConfigTablenot-accessiblemandatoryA list of configuration table entries. The number of entries is given by the value of upsNumUPSs.
1.3.6.1.4.1.52.4.1.1.10.7.1.1RowupsConfigEntrynot-accessiblemandatoryAn entry containing objects for a particular UPS.
1.3.6.1.4.1.52.4.1.1.10.7.1.1.1ColumnupsConfigAlarmread-writemandatoryThe UPS's current audible alarm setting. The alarm may be set to activate immediately upon utility failure and for low battery condition, to activate 30 second…
1.3.6.1.4.1.52.4.1.1.10.7.1.1.2ColumnupsConfigRestoreDefaultsread-writemandatoryThis object may be written to force the UPS to restore the factory default settings for most of the UPS's customizable parameters. Reading this object will alw…
1.3.6.1.4.1.52.4.1.1.10.8NodeupsExtMeas
1.3.6.1.4.1.52.4.1.1.10.8.1TableupsExtMeasTablenot-accessiblemandatoryA list of external measurement table entries. The number of entries is the number of available UPSs to which External Measurement Units are attached.
1.3.6.1.4.1.52.4.1.1.10.8.1.1RowupsExtMeasEntrynot-accessiblemandatoryAn entry containing objects for a particular UPS.
1.3.6.1.4.1.52.4.1.1.10.8.1.1.1ColumnupsExtMeasFwVersionread-onlymandatoryThe External Measurement Unit's firmware version letter.
1.3.6.1.4.1.52.4.1.1.10.8.1.1.2ColumnupsExtMeasTempread-onlymandatoryThe local ambient temperature in degrees Fahrenheit as measured by the External Measurement Unit. The value of this object is the actual temperature * 100 (tha…
1.3.6.1.4.1.52.4.1.1.10.8.1.1.3ColumnupsExtMeasHumidityread-onlymandatoryThe local ambient relative humidity in percent as measured by the External Measurement Unit. The value of this object is the actual humidity * 10 (that is, to …
1.3.6.1.4.1.52.4.1.1.10.8.1.1.4ColumnupsExtMeasAlarmStatusread-onlymandatoryThis object contains 8 bits of information about the current alarm status of the External Measurement Unit. The bits are encoded as follows: BIT 7: 1=Upper tem…
1.3.6.1.4.1.52.4.1.1.10.8.1.1.5ColumnupsExtMeasMaxTempread-writemandatoryThe upper temperature limit at which an alarm will be sent.
1.3.6.1.4.1.52.4.1.1.10.8.1.1.6ColumnupsExtMeasMinTempread-writemandatoryThe lower temperature limit at which an alarm will be sent.
1.3.6.1.4.1.52.4.1.1.10.8.1.1.7ColumnupsExtMeasMaxHumidityread-writemandatoryThe upper humidity limit at which an alarm will be sent.
1.3.6.1.4.1.52.4.1.1.10.8.1.1.8ColumnupsExtMeasMinHumidityread-writemandatoryThe lower humidity limit at which an alarm will be sent.
1.3.6.1.4.1.52.4.1.1.10.8.1.1.9ColumnupsExtMeasContact1AlarmControlread-writemandatoryThe alarm enable state for the External Measurement Unit's contact input channel #1. If enabled, an alarm will be sent when contact input channel #1 has change…
1.3.6.1.4.1.52.4.1.1.10.8.1.1.10ColumnupsExtMeasContact2AlarmControlread-writemandatoryThe alarm enable state for the External Measurement Unit's contact input channel #2. If enabled, an alarm will be sent when contact input channel #2 has change…
1.3.6.1.4.1.52.4.1.1.10.8.1.1.11ColumnupsExtMeasContact3AlarmControlread-writemandatoryThe alarm enable state for the External Measurement Unit's contact input channel #3. If enabled, an alarm will be sent when contact input channel #3 has change…
1.3.6.1.4.1.52.4.1.1.10.8.1.1.12ColumnupsExtMeasContact4AlarmControlread-writemandatoryThe alarm enable state for the External Measurement Unit's contact input channel #4. If enabled, an alarm will be sent when contact input channel #4 has change…
1.3.6.1.4.1.52.4.1.1.10.8.1.1.13ColumnupsExtMeasMaxTempAlarmControlread-writemandatoryThe alarm enable state for the External Measurement Unit's upper temperature limit. If enabled, an alarm will be sent when the ambient temperature rises above …
1.3.6.1.4.1.52.4.1.1.10.8.1.1.14ColumnupsExtMeasMinTempAlarmControlread-writemandatoryThe alarm enable state for the External Measurement Unit's lower temperature limit. If enabled, an alarm will be sent when the ambient temperature falls below …
1.3.6.1.4.1.52.4.1.1.10.8.1.1.15ColumnupsExtMeasMaxHumidityAlarmControlread-writemandatoryThe alarm enable state for the External Measurement Unit's upper humidity limit. If enabled, an alarm will be sent when the ambient relative humidity rises abo…
1.3.6.1.4.1.52.4.1.1.10.8.1.1.16ColumnupsExtMeasMinHumidityAlarmControlread-writemandatoryThe alarm enable state for the External Measurement Unit's lower humidity limit. If enabled, an alarm will be sent when the ambient relative humidity falls bel…
1.3.6.1.4.1.52.4.1.1.10.9NodeupsAddlFuncs
1.3.6.1.4.1.52.4.1.1.10.9.1TableupsAddlFuncsTablenot-accessiblemandatoryA list of additional functions table entries. The number of entries is the number of available UPSs which are capable of supporting these additional functions.
1.3.6.1.4.1.52.4.1.1.10.9.1.1RowupsAddlFuncsEntrynot-accessiblemandatoryAn entry containing objects for a particular UPS.
1.3.6.1.4.1.52.4.1.1.10.9.1.1.1ColumnupsAddlFuncsNumBatteryPacksread-onlymandatoryThe number of battery pack units connected to the UPS.
1.3.6.1.4.1.52.4.1.1.10.9.1.1.2ColumnupsAddlFuncsNumBadBatteryPacksread-onlymandatoryThe number of bad (faulty) battery pack units connected to the UPS.
1.3.6.1.4.1.52.4.1.1.10.9.1.1.3ColumnupsAddlFuncsOutputCurrentread-onlymandatoryThe true rms load current drawn from the UPS. The value of this object is the actual amperage * 100 (that is, to determine the actual amperage, divide the valu…
1.3.6.1.4.1.52.4.1.1.10.9.1.1.4ColumnupsAddlFuncsOutputApparentPowerread-onlymandatoryThe UPS's output load represented as a percentage of full rated load in Volt-Amps. The value of this object is the actual percentage * 10 (that is, to determin…
1.3.6.1.4.1.52.4.1.1.10.9.1.1.5ColumnupsAddlFuncsStatusOperationalread-onlymandatoryThis object contains 8 bits of information about the current operational status of the UPS. The bits are encoded as follows: BIT 7: 1=UPS ready to power load u…
1.3.6.1.4.1.52.4.1.1.10.9.1.1.6ColumnupsAddlFuncsStatusFaultread-onlymandatoryThis object contains 8 bits of information about the current fault conditions of the UPS. The bits are encoded as follows: BIT 7: reserved for future use BIT 6…
1.3.6.1.4.1.52.4.1.1.10.9.1.1.7ColumnupsAddlFuncsConfigPasswordread-writemandatoryThe password that controls access to the UPS's LCD display. A maximum of 4 characters may be entered.
1.3.6.1.4.1.52.4.1.1.10.9.1.1.8ColumnupsAddlFuncsConfigDisableread-writemandatoryThis object may be written to immediately shut down the UPS, requiring a manual reset. Reading this object will always return a 0.
1.3.6.1.4.1.52.4.1.1.10.9.1.1.9ColumnupsAddlFuncsConfigBypassread-writemandatoryThis object may be written to cause the UPS to transfer to or from the bypass mode. Reading this object will always return a 0.