MIB Viewer

VALERE-DC-POWER-MIB

295 objects
MIB Version 0.8 Need description here. History Add table to retrieve module inventory info MIB Version 0.7 Dec 1, 05 Fixed HP Openview error Fixed warnings generated by MG-SOFT Add table to retrieve rectifier inventory info MIB Version 0.6 Feb 10, 2004 Added additional traps. Defined Ringers and other modules. Feb 08, 2003 Changed vpwrTrapDestinationTable to vpwrTrapTable Corrected entry for vpwrTrapTable to be VpwrTrapTableEntry This fixes errors generated by MG-SOFT mib compiler. Oct 30, 2002 initial release - version 0.4
Imported Objects
RFC1213-MIBsysUpTime
SNMPv2-CONFMODULE-COMPLIANCE OBJECT-GROUP
SNMPv2-SMICounter32 enterprises Gauge32 Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-IDENTITY OBJECT-TYPE
SNMPv2-TCAutonomousType DisplayString TestAndIncr TEXTUAL-CONVENTION TimeInterval TimeStamp
OIDNameAccessStatusDescription
1.3.6.1.4.1.13858IdentityvpwrDcPowerMgtMIB Version 0.8 Need description here. History Add table to retrieve module inventory info MIB Version 0.7 Dec 1, 05 Fixed HP Openview error Fixed warnings gen…
1.3.6.1.4.1.13858.1NodevpwrDcPowerProducts
1.3.6.1.4.1.13858.2NodevpwrDcPowerSystem
1.3.6.1.4.1.13858.2.1NodevpwrSystemIdentGroup
1.3.6.1.4.1.13858.2.1.1ScalarvpwrIdentManufacturerread-onlycurrentThe name of the DC Power manufacturer.
1.3.6.1.4.1.13858.2.1.2ScalarvpwrIdentModelread-onlycurrentThe DC Power Model designation.
1.3.6.1.4.1.13858.2.1.3ScalarvpwrIdentControllerVersionread-onlycurrentThe hardware/firmware version(s). This variable may or may not have the same value as vpwrIdentAgentSoftwareVersion.
1.3.6.1.4.1.13858.2.1.4ScalarvpwrIdentAgentSoftwareVersionread-onlycurrentThe SNMP agent software version. This variable may or may not have the same value as vpwrIdentControllerFirmwareVersion.
1.3.6.1.4.1.13858.2.1.5ScalarvpwrIdentNameread-writecurrentA string identifying the system. This object should be set by the administrator.
1.3.6.1.4.1.13858.2.1.6TablevpwrSystemIdentTablenot-accessiblecurrentThis table describes shelves and modules that make up the sysetm.
1.3.6.1.4.1.13858.2.1.6.1RowvpwrSystemIdentEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.
1.3.6.1.4.1.13858.2.1.6.1.1ColumnvpwrBayIndexread-onlycurrentIdentifies Bay number that this module belongs to. The possible values are 1 through 16 limited by vpwrSystemShelfCapacity.
1.3.6.1.4.1.13858.2.1.6.1.2ColumnvpwrModuleIndexread-onlycurrentThis object identifies the module by its position in the shelf. Module numbering is left to right starting with module 1. So, the module in the first slot has …
1.3.6.1.4.1.13858.2.1.6.1.3ColumnvpwrModuleOIDread-onlycurrentIt indicates the type of the module by specifiying its OID
1.3.6.1.4.1.13858.2.1.6.1.4ColumnvpwrModuleCurrentread-onlycurrentThe meaning of this object depends upon the module type which is indicated by vpwrModuleOID as follows - Current for Rectifier module. - Not Applicable for LVD…
1.3.6.1.4.1.13858.2.1.6.1.5ColumnvpwrModuleOperStatusread-onlycurrentThis object indicates current over all status of the module.
1.3.6.1.4.1.13858.2.1.6.1.6ColumnvpwrModuleCapacityread-onlycurrentThe meaning of this object depends upon the module type which is indicated by vpwrModuleOID as follows - Capacity for Rectifier module. - Not Applicable for LV…
1.3.6.1.4.1.13858.2.2NodevpwrSystemConfigGroup
1.3.6.1.4.1.13858.2.2.1ScalarvpwrSystemTempCompensationread-writecurrentThis parameter enables/disables temperature compensation.
1.3.6.1.4.1.13858.2.2.2ScalarvpwrSystemTempCompStartTemperatureread-writecurrentThe temperature at which temperature compensation becomes active.
1.3.6.1.4.1.13858.2.2.3ScalarvpwrSystemTempCompStopVoltageread-writecurrentWhen temperature compensation is active, vpwrSystemTempCompStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage to…
1.3.6.1.4.1.13858.2.2.4ScalarvpwrSystemTempCompensationSloperead-writecurrentThe rate at which float voltage is changed, within the specified limits, when temperature compensation is active.
1.3.6.1.4.1.13858.2.2.5ScalarvpwrSystemThermalSenseTyperead-writecurrentThis parameter selects the temperature sensing point for temperature compensation (in)activation.
1.3.6.1.4.1.13858.2.2.6ScalarvpwrSystemHVAlarmSetpointread-writecurrentSystem High voltage alarm voltage setting.
1.3.6.1.4.1.13858.2.2.7ScalarvpwrSystemBDAlarmSetpointread-writecurrentSystem Battery Discharge voltage setting.
1.3.6.1.4.1.13858.2.2.8ScalarvpwrSystemInternalTempLThresholdread-writecurrentTemperature value at which temperature compensation inactive (clear) trap would be sent if temperature compensation was active when this value is reached.
1.3.6.1.4.1.13858.2.2.9ScalarvpwrSystemInternalTempUThresholdread-writecurrentTemperature value at which temperature compensation active (set) trap would be sent.
1.3.6.1.4.1.13858.2.3NodevpwrSystemParameterGroup
1.3.6.1.4.1.13858.2.3.1ScalarvpwrSystemShelfCapacityread-onlycurrentIt describes the maximum number of shelves that can/are controlled by the controller. Each shelf is uniquely numbered in the range from 1 to vpwrShelfCapacity.
1.3.6.1.4.1.13858.2.3.2ScalarvpwrSystemVoltageread-onlycurrentThe current system voltage.
1.3.6.1.4.1.13858.2.3.3ScalarvpwrSystemCurrentread-onlycurrentThe current system current.
1.3.6.1.4.1.13858.2.3.4ScalarvpwrSystemControllerStateread-onlycurrentCurrent System state as shown on the enhanced display.
1.3.6.1.4.1.13858.2.3.5ScalarvpwrSystemInternalTemperatureread-onlycurrentThe current controller internal temperature.
1.3.6.1.4.1.13858.2.3.6ScalarvpwrSystemTempCompensationStateread-onlycurrentActive or Inactive. Applicable only if temperature compensation is enabled. This means that the controller is temperature compensating the float voltage.
1.3.6.1.4.1.13858.2.3.7ScalarvpwrSystemTyperead-onlycurrentThis parameter describes the type of the system being managed. This object is set by Valere Power Inc.
1.3.6.1.4.1.13858.2.4NodevpwrSystemPanelIdentGroup
1.3.6.1.4.1.13858.2.4.1TablevpwrPanelIdentTablenot-accessiblecurrentThis table describes shelves and modules that make up the panels.
1.3.6.1.4.1.13858.2.4.1.1RowvpwrPanelIdentEntrynot-accessiblecurrentAn entry containing information applicable to a particular panel making up the system.
1.3.6.1.4.1.13858.2.4.1.1.1ColumnvpwrPanelBayIndexread-onlycurrentIdentifies bay number that this module belongs to. The possible values are 1 through 16, starting from the top.
1.3.6.1.4.1.13858.2.4.1.1.2ColumnvpwrPanelModuleIndexread-onlycurrentThis object identifies the module within the panel. The orentation of modules within the panel is mappable.
1.3.6.1.4.1.13858.2.4.1.1.3ColumnvpwrPanelModuleOIDread-onlycurrentIt indicates the type of the module by specifiying its OID
1.3.6.1.4.1.13858.2.4.1.1.4ColumnvpwrPanelModuleCurrentread-onlycurrentThis is the Current of the first shunt of the module.
1.3.6.1.4.1.13858.2.4.1.1.5ColumnvpwrPanelModuleOperStatusread-onlycurrentThis object indicates over all status of the module.
1.3.6.1.4.1.13858.2.4.1.1.6ColumnvpwrPanelModuleCapacityread-onlycurrentThis is the overall Capacity of the module and is for reference only.
1.3.6.1.4.1.13858.2.5NodevpwrSystemBayctrlIdentGroup
1.3.6.1.4.1.13858.2.5.1TablevpwrBayctrlIdentTablenot-accessiblecurrentThis table describes bay controllers that make up the system.
1.3.6.1.4.1.13858.2.5.1.1RowvpwrBayctrlIdentEntrynot-accessiblecurrentAn entry containing information applicable to a particular bay controller making up the system.
1.3.6.1.4.1.13858.2.5.1.1.1ColumnvpwrBayctrlIndexread-onlycurrentIdentifies bay number that this module belongs to. The possible values are 0 through 15, starting from the top.
1.3.6.1.4.1.13858.2.5.1.1.2ColumnvpwrBayctrlOIDread-onlycurrentIt indicates the type of the module by specifiying its OID
1.3.6.1.4.1.13858.2.5.1.1.3ColumnvpwrBayctrlCurrentread-onlycurrentThis is the total output Current of the bay
1.3.6.1.4.1.13858.2.5.1.1.4ColumnvpwrBayctrlOperStatusread-onlycurrentThis object indicates over all status of the bay
1.3.6.1.4.1.13858.2.5.1.1.5ColumnvpwrBayctrlCapacityread-onlycurrentThis is the overall Capacity of the bay and is for reference only.
1.3.6.1.4.1.13858.3NodevpwrDcPowerRectifier
1.3.6.1.4.1.13858.3.1NodevpwrRectifierConfigGroup
1.3.6.1.4.1.13858.3.1.1ScalarvpwrRectifierFVSetpointread-writecurrentSystem Float Voltage setting
1.3.6.1.4.1.13858.3.1.2ScalarvpwrRectifierHVSDSetpointread-writecurrentSystem High Voltage Shutdown voltage setting
1.3.6.1.4.1.13858.3.1.3ScalarvpwrRectifierCurrentLimitAdminStateread-writecurrentThis parameter allows enabling or disabling boost.
1.3.6.1.4.1.13858.3.1.4ScalarvpwrRectifierCurrentLimitread-writecurrentRectifier current limit setpoint
1.3.6.1.4.1.13858.3.2NodevpwrRectifierAlarmGroup
1.3.6.1.4.1.13858.3.2.1IdentityvpwrRectAlarmDCFailcurrent
1.3.6.1.4.1.13858.3.2.2IdentityvpwrRectAlarmBoostFailcurrent
1.3.6.1.4.1.13858.3.2.3IdentityvpwrRectAlarmACFailcurrent
1.3.6.1.4.1.13858.3.2.4IdentityvpwrRectAlarmHVSDcurrent
1.3.6.1.4.1.13858.3.2.5IdentityvpwrRectAlarmFanFailcurrent
1.3.6.1.4.1.13858.3.2.6IdentityvpwrRectAlarmAmbTempcurrent
1.3.6.1.4.1.13858.3.2.7IdentityvpwrRectAlarmIntTempcurrent
1.3.6.1.4.1.13858.3.2.8IdentityvpwrRectAlarmISharecurrent
1.3.6.1.4.1.13858.3.2.9IdentityvpwrRectAlarmUVcurrent
1.3.6.1.4.1.13858.3.2.10IdentityvpwrRectAlarmLowVoltagecurrent
1.3.6.1.4.1.13858.3.2.11IdentityvpwrRectAlarmReservedcurrent
1.3.6.1.4.1.13858.3.2.12IdentityvpwrRectAlarmDCEnablecurrent
1.3.6.1.4.1.13858.3.2.13IdentityvpwrRectAlarmRemoteShutdowncurrent
1.3.6.1.4.1.13858.3.2.14IdentityvpwrRectAlarmModDisableShutdowncurrent
1.3.6.1.4.1.13858.3.2.15IdentityvpwrRectAlarmShortPinShutdowncurrent
1.3.6.1.4.1.13858.3.2.16IdentityvpwrRectAlarmBoostCommcurrent
1.3.6.1.4.1.13858.3.3NodevpwrRectifierTestGroup
1.3.6.1.4.1.13858.4NodevpwrDcPowerLvd
1.3.6.1.4.1.13858.4.1NodevpwrLvdConfigGroup
1.3.6.1.4.1.13858.4.1.1ScalarvpwrLvdWarningSetpointread-writecurrentLVD Warning voltage setpoint.
1.3.6.1.4.1.13858.4.1.2ScalarvpwrLvdDisconnectSetpointread-writecurrentLVD disconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.3ScalarvpwrLvdReconnectSetpointread-writecurrentLVD Reconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.4ScalarvpwrLvdReconnectDelayTimerread-writecurrentThe delay time, in seconds, before LVD is reconnected
1.3.6.1.4.1.13858.4.1.5TablevpwrLvdContactorConfigTablenot-accessiblecurrentThis table describes shelves and modules that make up the sysetm.
1.3.6.1.4.1.13858.4.1.5.1RowvpwrLvdContactorConfigEntrynot-accessiblecurrentAn entry containing information applicable to a particular module making up the system.
1.3.6.1.4.1.13858.4.1.5.1.1ColumnvpwrLvdContactorIndexread-onlycurrentcontactor index
1.3.6.1.4.1.13858.4.1.5.1.2ColumnvpwrLvdContactorWarningSetpointread-writecurrentLVD Warning voltage setpoint.
1.3.6.1.4.1.13858.4.1.5.1.3ColumnvpwrLvdContactorDisconnectSetpointread-writecurrentLVD disconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.5.1.4ColumnvpwrLvdContactorReconnectSetpointread-writecurrentLVD Reconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.5.1.5ColumnvpwrLvdContactorReconnectDelayTimerread-writecurrentThe delay time, in seconds, before LVD is reconnected
1.3.6.1.4.1.13858.4.1.5.1.6ColumnvpwrLvdContactorStateread-writecurrentThe delay time, in seconds, before LVD is reconnected
1.3.6.1.4.1.13858.4.2NodevpwrLvdAlarmGroup
1.3.6.1.4.1.13858.4.2.1IdentityvpwrLvdAlarmContactorOpencurrentContactor open
1.3.6.1.4.1.13858.4.2.2IdentityvpwrLvdAlarmCBOpencurrentCircuit Breaker open
1.3.6.1.4.1.13858.4.2.3IdentityvpwrTrapLvdFuseOpencurrentFuse open
1.3.6.1.4.1.13858.4.2.4IdentityvpwrLvdAlarmWarningcurrentPlant Voltage below warning threshold
1.3.6.1.4.1.13858.4.3NodevpwrLvdTestGroup
1.3.6.1.4.1.13858.5NodevpwrDcPowerTest
1.3.6.1.4.1.13858.6NodevpwrDcPowerModuleIdent
1.3.6.1.4.1.13858.6.1TablevpwrModuleIdentTablenot-accessiblecurrentThis table describes shelves and modules that make up the sysetm.
1.3.6.1.4.1.13858.6.1.1RowvpwrModuleIdentEntrynot-accessiblecurrentAn entry containing information applicable to a particular Module.
1.3.6.1.4.1.13858.6.1.1.1ColumnvpwrModuleSerialNumberread-onlycurrentSerial Number of the module
1.3.6.1.4.1.13858.6.1.1.2ColumnvpwrModuleModelNumberread-onlycurrentModel Number of the module.
1.3.6.1.4.1.13858.6.1.1.3ColumnvpwrModuleFwVersionread-onlycurrentFirmware version of the module.
1.3.6.1.4.1.13858.6.1.1.4ColumnvpwrModuleTestDateread-onlycurrentDate when the module was last tested.
1.3.6.1.4.1.13858.6.1.1.5ColumnvpwrModuleOperHoursread-onlycurrentCumulative Operating Hours.
1.3.6.1.4.1.13858.6.2TablevpwrPanelModuleIdentTablenot-accessiblecurrentThis table describes shelves and modules that make up the sysetm.
1.3.6.1.4.1.13858.6.2.1RowvpwrPanelModuleIdentEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.
1.3.6.1.4.1.13858.6.2.1.1ColumnvpwrPanelModuleSerialNumberread-onlycurrentSerial Number of the module
1.3.6.1.4.1.13858.6.2.1.2ColumnvpwrPanelModuleModelNumberread-onlycurrentModel Number of the module.
1.3.6.1.4.1.13858.6.2.1.3ColumnvpwrPanelModuleFwVersionread-onlycurrentFirmware version of the module.
1.3.6.1.4.1.13858.6.2.1.4ColumnvpwrPanelModuleTestDateread-onlycurrentDate when the module was last tested.
1.3.6.1.4.1.13858.6.2.1.5ColumnvpwrPanelModuleOperHoursread-onlycurrentCumulative Operating Hours.
1.3.6.1.4.1.13858.6.3TablevpwrBayctrlModuleIdentTablenot-accessiblecurrentThis table describes bay controllers that make up the sysetm.
1.3.6.1.4.1.13858.6.3.1RowvpwrBayctrlModuleIdentEntrynot-accessiblecurrentAn entry containing information applicable to a particular bay controller.
1.3.6.1.4.1.13858.6.3.1.1ColumnvpwrBayctrlSerialNumberread-onlycurrentSerial Number of the bay controller
1.3.6.1.4.1.13858.6.3.1.2ColumnvpwrBayctrlModelNumberread-onlycurrentModel Number of the bay controller.
1.3.6.1.4.1.13858.6.3.1.3ColumnvpwrBayctrlFwVersionread-onlycurrentFirmware version of the bay controller.
1.3.6.1.4.1.13858.6.3.1.4ColumnvpwrBayctrlTestDateread-onlycurrentDate when the bayctrl was last tested.
1.3.6.1.4.1.13858.6.3.1.5ColumnvpwrBayctrlOperHoursread-onlycurrentCumulative Operating Hours.
1.3.6.1.4.1.13858.7NodevpwrDcPowerBatteryGroup
1.3.6.1.4.1.13858.7.1NodevpwrBatteryTempGroup
1.3.6.1.4.1.13858.7.1.1TablevpwrBatteryTempTablenot-accessiblecurrentThis table describes battery temperature probes.
1.3.6.1.4.1.13858.7.1.1.1RowvpwrBatteryTempEntrynot-accessiblecurrentAn entry containing information applicable to a particular temperature probe.
1.3.6.1.4.1.13858.7.1.1.1.1ColumnvpwrBatteryTempIndexread-onlycurrentIndex into temperature table
1.3.6.1.4.1.13858.7.1.1.1.2ColumnvpwrBatteryTempNameread-writecurrentA string identifying probe location.
1.3.6.1.4.1.13858.7.1.1.1.3ColumnvpwrBatteryTempread-onlycurrentCurrent temperature as recorded by the probe.
1.3.6.1.4.1.13858.7.1.2ScalarvpwrBatteryTempLThresholdread-writecurrentTemperature value at which a clear trap would be sent. All three battery temperature must be at or below this value to trigger this trap.
1.3.6.1.4.1.13858.7.1.3ScalarvpwrBatteryTempUThresholdread-writecurrentTemperature value at which a set trap would be sent. Any one of the three battery temperatures at or exceeding this limit would trigger the trap.
1.3.6.1.4.1.13858.7.1.4ScalarbatteryTempCompensationread-writecurrentThis parameter enables/disables temperature compensation.
1.3.6.1.4.1.13858.7.1.5ScalarbatteryTempCompHighStartTemperatureread-writecurrentThe temperature at which temperature compensation becomes active.
1.3.6.1.4.1.13858.7.1.6ScalarbatteryTempCompHighStopVoltageread-writecurrentWhen temperature compensation is active, batteryTempCompHighStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage t…
1.3.6.1.4.1.13858.7.1.7ScalarbatteryTempCompHighSloperead-writecurrentThe rate at which float voltage is changed, within the specified limits, when temperature compensation is active.
1.3.6.1.4.1.13858.7.1.8ScalarbatteryTempCompLowStartTemperatureread-writecurrentThe temperature at which temperature compensation becomes active.
1.3.6.1.4.1.13858.7.1.9ScalarbatteryTempCompLowStopVoltageread-writecurrentWhen temperature compensation is active, batteryTempCompLowStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage to…
1.3.6.1.4.1.13858.7.1.10ScalarbatteryTempCompLowSloperead-writecurrentThe rate at which float voltage is changed, within the specified limits, when temperature compensation is active.
1.3.6.1.4.1.13858.7.1.11ScalarbatteryTempCompRunawayTemperatureread-writecurrentThe temperature at which system voltage will be set to batteryTempCompRunawayStopVoltage.
1.3.6.1.4.1.13858.7.1.12ScalarbatteryTempCompRunawayStopVoltageread-writecurrentWhen temperature compensation is enabled, float voltage will be reduced to batteryTempCompRunawayStopVoltage if temperature reaches batteryTempCompRunawayTempe…
1.3.6.1.4.1.13858.7.1.13ScalarbatteryTempCompSenseSourceread-writecurrentThis parameter selects the temperature sensing point for temperature compensation (in)activation.
1.3.6.1.4.1.13858.7.1.14ScalarbatteryTempCompRunawayStateread-onlycurrentThis parameter selects the temperature sensing point for temperature compensation (in)activation.
1.3.6.1.4.1.13858.7.1.15TablethermalProbeTablenot-accessiblecurrentThis table describes battery temperature probes.
1.3.6.1.4.1.13858.7.1.15.1RowthermalProbeEntrynot-accessiblecurrentAn entry containing information applicable to a particular temperature probe.
1.3.6.1.4.1.13858.7.1.15.1.1ColumnthermalProbeStateread-onlycurrentState of thermal probe.
1.3.6.1.4.1.13858.7.2NodevpwrBatteryCurrentGroup
1.3.6.1.4.1.13858.7.2.1ScalarvpwrBatteryCurrentLimitAdminStateread-writecurrentThis parameter allows enabling or disabling battery current limit.
1.3.6.1.4.1.13858.7.2.2ScalarvpwrBattetyCurrentLimitValueread-writecurrent
1.3.6.1.4.1.13858.7.2.3ScalarvpwrBattetyCurrentValueread-onlycurrent
1.3.6.1.4.1.13858.7.3NodevpwrBatteryBoostGroup
1.3.6.1.4.1.13858.7.3.1ScalarvpwrBoostAdminStateread-writecurrentThis parameter allows enabling or disabling boost.
1.3.6.1.4.1.13858.7.3.2ScalarvpwrBoostVoltageread-writecurrent
1.3.6.1.4.1.13858.7.3.3ScalarvpwrBoostDurationread-writecurrent
1.3.6.1.4.1.13858.7.3.4ScalarvpwrBoostOperStateread-writecurrentThis parameter allows starting or stoping boost if it is enabled.
1.3.6.1.4.1.13858.7.4NodevpwrBatteryDischargeTestGroup
1.3.6.1.4.1.13858.7.4.1ScalarvpwrBDTAdminStateread-writecurrentEnable /Disable Battery Discharge Test execution.
1.3.6.1.4.1.13858.7.4.2ScalarvpwrBDTDurationread-writecurrent
1.3.6.1.4.1.13858.7.4.3ScalarvpwrBDTAlarmVoltageread-writecurrent
1.3.6.1.4.1.13858.7.4.4ScalarvpwrBDTAbortVoltageread-writecurrent
1.3.6.1.4.1.13858.7.4.5ScalarvpwrBDTAlarmCoefficientread-writecurrent
1.3.6.1.4.1.13858.7.4.6ScalarvpwrBDTOperStateread-writecurrentStart/Stop Battery Discharge Test execution.
1.3.6.1.4.1.13858.7.4.7ScalarvpwrBDTClearAlarmread-writecurrentClears any active bdt alarm.
1.3.6.1.4.1.13858.8NodevpwrDcPowerAlarmGroup
1.3.6.1.4.1.13858.8.1ScalarvpwrAlarmsPresentread-onlycurrentThe present number of active alarm conditions.
1.3.6.1.4.1.13858.8.2TablevpwrAlarmTablenot-accessiblecurrentA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.13858.8.2.1RowvpwrAlarmEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.
1.3.6.1.4.1.13858.8.2.1.1ColumnvpwrAlarmIndexread-onlycurrentIdentifies the alarm associated with the module. It is unique on per module type basis. For example, multiple rectifiers can have the same alarm and therefore …
1.3.6.1.4.1.13858.8.2.1.2ColumnvpwrAlarmDescrread-onlycurrentA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.13858.8.2.1.3ColumnvpwrAlarmTimeread-onlycurrentThe value of sysUpTime when the alarm condition was detected.
1.3.6.1.4.1.13858.8.3TablesysRelayConfigTablenot-accessiblecurrentThis table describes battery temperature probes.
1.3.6.1.4.1.13858.8.3.1RowsysRelayConfigEntrynot-accessiblecurrentAn entry containing information applicable to a particular temperature probe.
1.3.6.1.4.1.13858.8.3.1.1ColumnsysRelayIndexread-onlycurrentIndex into temperature table
1.3.6.1.4.1.13858.8.3.1.2ColumnsysRelayDefaultNameread-onlycurrentA string identifying probe location.
1.3.6.1.4.1.13858.8.3.1.3ColumnsysRelayCustomNameread-writecurrentA string identifying probe location.
1.3.6.1.4.1.13858.8.3.1.4ColumnsysRelayAlarmSeverityread-writecurrentCurrent temperature as recorded by the probe.
1.3.6.1.4.1.13858.8.4TablesysAlarmConfigTablenot-accessiblecurrentThis table describes battery temperature probes.
1.3.6.1.4.1.13858.8.4.1RowsysAlarmConfigEntrynot-accessiblecurrentAn entry containing information applicable to a particular temperature probe.
1.3.6.1.4.1.13858.8.4.1.1ColumnsysAlarmIndexread-onlycurrentIndex into temperature table
1.3.6.1.4.1.13858.8.4.1.2ColumnsysAlarmDefaultNameread-onlycurrentA string identifying probe location.
1.3.6.1.4.1.13858.8.4.1.3ColumnsysAlarmCustomNameread-writecurrentA string identifying probe location.
1.3.6.1.4.1.13858.8.4.1.4ColumnsysAlarmSeverityread-writecurrentAlarm Severity as denoted by Major and Minor Alarm Mask
1.3.6.1.4.1.13858.8.4.1.5ColumnsysAlarmToRelayMappingread-writecurrentNo additional mapping = 0 Map to Relay A = 1 Map to Relay B = 2 Map to Relay C = 4 Map to Relay D = 8 Map to Relay E = 16 Map to Relay F = 32 Map to Relay A an…
1.3.6.1.4.1.13858.8.4.1.6ColumnsysAlarmOperStatusread-onlycurrentIndicates current alarm status
1.3.6.1.4.1.13858.8.5TablesysAuxAlarmConfigTablenot-accessiblecurrentThis table describes battery temperature probes.
1.3.6.1.4.1.13858.8.5.1RowsysAuxAlarmConfigEntrynot-accessiblecurrentAn entry containing information applicable to a particular temperature probe.
1.3.6.1.4.1.13858.8.5.1.1ColumnsysAuxAlarmIndexread-onlycurrentIndex into temperature table
1.3.6.1.4.1.13858.8.5.1.2ColumnsysAuxAlarmDefaultNameread-onlycurrentA string identifying probe location.
1.3.6.1.4.1.13858.8.5.1.3ColumnsysAuxAlarmCustomNameread-writecurrentA string identifying probe location.
1.3.6.1.4.1.13858.8.5.1.4ColumnsysAuxAlarmSeverityread-writecurrentAux Alarm Severity
1.3.6.1.4.1.13858.8.5.1.5ColumnsysAuxAlarmToRelayMappingread-writecurrentNo additional mapping = 0 Map to Relay A = 1 Map to Relay B = 2 Map to Relay C = 4 Map to Relay D = 8 Map to Relay E = 16 Map to Relay F = 32 Map to Relay A an…
1.3.6.1.4.1.13858.8.5.1.6ColumnsysAuxAlarmPolarityread-writecurrentCurrent temperature as recorded by the probe.
1.3.6.1.4.1.13858.8.5.1.7ColumnsysAuxAlarmOperStatusread-onlycurrentIndicates current alarm status
1.3.6.1.4.1.13858.8.6ScalarsysAlarmComFailStateread-writecurrentEnable/Disable generation of comm fail alarm.
1.3.6.1.4.1.13858.8.7ScalarsysAlarmIShareStateread-writecurrentEnable/Disable generation of current share alarm.
1.3.6.1.4.1.13858.8.8ScalarsysAlarmRedundancyStateread-writecurrentEnable/Disable generation of redundancy alarm.
1.3.6.1.4.1.13858.9NodevpwrDcPowerSnmpConfig
1.3.6.1.4.1.13858.9.1TablevpwrTrapTablenot-accessiblecurrentA list of possible trap destinations depending upon the criticality of the trap.
1.3.6.1.4.1.13858.9.1.1RowvpwrTrapEntrynot-accessiblecurrentAn entry containing information applicable to a particular trap destination.
1.3.6.1.4.1.13858.9.1.1.1ColumnvpwrTrapIpIndexread-onlycurrentTrap Entry Index
1.3.6.1.4.1.13858.9.1.1.2ColumnvpwrTrapIpAddressread-writecurrentTrap destination IP Address
1.3.6.1.4.1.13858.9.1.1.3ColumnvpwrTrapCriticalityread-writecurrentCriticality of traps sent to this IP Address
1.3.6.1.4.1.13858.9.2ScalarvpwrReadCommunityStringread-writecurrentThis allows setting password to be able to do Get operations
1.3.6.1.4.1.13858.9.3ScalarvpwrWriteCommunityStringread-writecurrentThis allows setting password to be able to do Get and Set operations. The read-access is not allowed in the actual implementation.
1.3.6.1.4.1.13858.9.4ScalarvpwrTrapCommunityStringread-writecurrentThis allows setting community string required for the trap to be accepted at the destination.
1.3.6.1.4.1.13858.10NodevpwrDcPowerTraps
1.3.6.1.4.1.13858.10.1NodevpwrTrapPowerMajorAlarmMajor Alarm
1.3.6.1.4.1.13858.10.2NodevpwrTrapPowerMinorAlarmMinor Alarm
1.3.6.1.4.1.13858.10.3NodevpwrTrapACFAlarmAC Fail Alarm
1.3.6.1.4.1.13858.10.4NodevpwrTrapHVAlarmHigh Voltage Warning Alarm
1.3.6.1.4.1.13858.10.5NodevpwrTrapHVSDAlarmHigh Voltage Shutdown Alarm
1.3.6.1.4.1.13858.10.6NodevpwrTrapBDAlarmBattery on Discharge Alarm
1.3.6.1.4.1.13858.10.7NodevpwrTrapLVDWarningAlarmLVD Warning Alarm
1.3.6.1.4.1.13858.10.8NodevpwrTrapLVDOpenAlarmLVD Open Alarm
1.3.6.1.4.1.13858.10.9NodevpwrTrapDistAlarmDistribution Open Alarm
1.3.6.1.4.1.13858.10.10NodevpwrTrapAuxAlarmAuxiliary System Alarm
1.3.6.1.4.1.13858.10.11NodevpwrTrapSystemRedundancyAlarmSystem Redundant Capacity Alarm
1.3.6.1.4.1.13858.10.12NodevpwrTrapIShareAlarmRectifier Current Share Alarm
1.3.6.1.4.1.13858.10.13NodevpwrTrapModuleFailAlarmSingle Rectifier Fail Alarm
1.3.6.1.4.1.13858.10.14NodevpwrTrapMultipleModuleFailAlarmMultiple Rectifier Fail Alarm
1.3.6.1.4.1.13858.10.15NodevpwrTrapModuleCommAlarmModule Communication Alarm
1.3.6.1.4.1.13858.10.16NodevpwrTrapSystemOverTemperatureAlarmSystem Over Temperature Alarm
1.3.6.1.4.1.13858.10.17NodevpwrTrapSystemOKSYSTEM OK - No Active Alarms
1.3.6.1.4.1.13858.10.18NodevpwrTrapModuleInsertedA new module has been inserted into the system.
1.3.6.1.4.1.13858.10.19NodevpwrTrapModuleRemovedA module has been removed from the system.
1.3.6.1.4.1.13858.10.20NodevpwrTrapThermalCompActiveThermal compensation has become active.
1.3.6.1.4.1.13858.10.21NodevpwrTrapThermalCompInactiveThermal compensation has been de-activated.
1.3.6.1.4.1.13858.10.22NodevpwrTrapInternalTempAlarmSetInternal Temperature upper threshold exceeded.
1.3.6.1.4.1.13858.10.23NodevpwrTrapInternalTempAlarmClearedInternal Temperature within limits
1.3.6.1.4.1.13858.10.24NodevpwrTrapBatteryTempAlarmSetAt least one Battery Temperature exceeded upper threshold.
1.3.6.1.4.1.13858.10.25NodevpwrTrapBatteryTempAlarmClearedAll Battery Temperatures within limits.
1.3.6.1.4.1.13858.10.26NodevpwrTrapLoginFailAdmin login failed due to wrong username/password.
1.3.6.1.4.1.13858.10.27NodevpwrTrapLoginSuccessAdmin login successful.
1.3.6.1.4.1.13858.10.28NodevpwrTrapLogoutAdmin logout.
1.3.6.1.4.1.13858.10.29NodevpwrTrapAdminPwdChangeConfig change submitted with invalid access.
1.3.6.1.4.1.13858.10.30NodevpwrTrapIllegalConfigSubmitConfig change submitted with invalid access.
1.3.6.1.4.1.13858.10.31NodevpwrTrapCfgChangeConfig change submitted.
1.3.6.1.4.1.13858.10.32NodevpwrTrapClearEventHistoryClear Event history buffer clear request.
1.3.6.1.4.1.13858.10.33NodevpwrTrapSwDownloadNoRebootSystem software upgrade without reboot.
1.3.6.1.4.1.13858.10.34NodevpwrTrapSwDownloadAndRebootSystem reboot due to software upgrade.
1.3.6.1.4.1.13858.10.35NodevpwrTrapSystemClockChangeSystem clock updated.
1.3.6.1.4.1.13858.10.36NodevpwrTrapModuleAlarmModule Alarm.
1.3.6.1.4.1.13858.10.37NodevpwrTrapOIDChangeChange in OID.
1.3.6.1.4.1.13858.10.38NodevpwrTrapThermalRunawayThermal Runaway Alarm.
1.3.6.1.4.1.13858.10.39NodevpwrTrapBatteryDischargeTestAlarmSystem Voltage dropped to BDT Alarm Setpoint.
1.3.6.1.4.1.13858.10.40NodevpwrTrapRingerAAlarmRinger A Fail Alarm.
1.3.6.1.4.1.13858.10.41NodevpwrTrapRingerBAlarmRinger B Fail Alarm.
1.3.6.1.4.1.13858.10.42NodevpwrTrapSingleRingerAlarmSingle Ringer Fail Alarm.
1.3.6.1.4.1.13858.10.43NodevpwrTrapMultipleRingerAlarmMultiple Ringer Fail Alarm.
1.3.6.1.4.1.13858.10.44NodevpwrTrapThermalProbeAlarmThermal Probe Missing Alarm.
1.3.6.1.4.1.13858.10.45NodevpwrTrapRingerCommAlarmRinger Communication Alarm.
1.3.6.1.4.1.13858.10.46NodevpwrTrapDistributionCommAlarmDistribution Communication Alarm.
1.3.6.1.4.1.13858.10.47NodevpwrTrapConverterAlarmSingle Converter Fail Alarm.
1.3.6.1.4.1.13858.10.48NodevpwrTrapMultipleConvFailAlarmMultiple Converter Fail Alarm.
1.3.6.1.4.1.13858.10.49NodevpwrTrapUnmappedAddressAlarmUnmapped I2C Address.
1.3.6.1.4.1.13858.10.50NodevpwrTrapConfigErrorAlarmConfiguration Error.
1.3.6.1.4.1.13858.10.51NodevpwrTrapDisplayFirmwareMismatchAlarmDisplay Firmware Mismatch.
1.3.6.1.4.1.13858.10.52NodevpwrTrapConverterInputFailAlarmConverter Input Fail Alarm.
1.3.6.1.4.1.13858.10.53NodevpwrTrapBatteryRechgIlimitFailAlarmBattery Recharge Current Limit Fail.
1.3.6.1.4.1.13858.10.54NodevpwrTrapSystemAlivePeriodic Keepalive trap.
1.3.6.1.4.1.13858.11NodevpwrDcPowerTrapsMsgString
1.3.6.1.4.1.13858.11.1ScalarvpwrTrapsMsgStringnot-accessiblecurrentPlace holder for trap notification message string
1.3.6.1.4.1.13858.11.2ScalarvpwrTrapUserIpAddressnot-accessiblecurrentPlace holder for IP address of the user accessing the system
1.3.6.1.4.1.13858.11.3ScalarvpwrTrapEventTimeStampnot-accessiblecurrentPlace holder for time-stamp.
1.3.6.1.4.1.13858.12NodevpwrDcPowerRinger
1.3.6.1.4.1.13858.12.1NodevpwrRingerConfigGroup
1.3.6.1.4.1.13858.12.1.1TablevpwrRingerParameterTablenot-accessiblecurrentA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.13858.12.1.1.1RowvpwrRingerParameterEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.
1.3.6.1.4.1.13858.12.1.1.1.1ColumnvpwrRingerIndexread-onlycurrentThis parameter allows selecting ringer A or Ringer B as the active ringer.
1.3.6.1.4.1.13858.12.1.1.1.2ColumnvpwrRingerParameterAdminStateread-writecurrentThis parameter allows selecting ringer A or Ringer B as the active ringer.
1.3.6.1.4.1.13858.12.1.1.1.3ColumnvpwrRingerParameterAcVoltageread-writecurrent
1.3.6.1.4.1.13858.12.1.1.1.4ColumnvpwrRingerParameterDcVoltageread-writecurrent
1.3.6.1.4.1.13858.12.1.1.1.5ColumnvpwrRingerParameterFrequencyread-writecurrent
1.3.6.1.4.1.13858.12.1.2ScalarvpwrRingerNumberPresentread-onlycurrentThe present number of active alarm conditions.
1.3.6.1.4.1.13858.12.2NodevpwrRingerAlarmGroup
1.3.6.1.4.1.13858.12.2.1IdentityvpwrRingerAlarmaAFailedcurrentRinger A Failed
1.3.6.1.4.1.13858.12.2.2IdentityvpwrRingerAlarmAOTempcurrentRinger A Heatsink Over-Temperature
1.3.6.1.4.1.13858.12.2.3IdentityvpwrRingerAlarmAOCurrentcurrentRinger A Over-Current protection
1.3.6.1.4.1.13858.12.2.4IdentityvpwrRingerAlarmaBFailedcurrentRinger A Failed
1.3.6.1.4.1.13858.12.2.5IdentityvpwrRingerAlarmBOverTempcurrentRinger A Heatsink Over-Temperature
1.3.6.1.4.1.13858.12.2.6IdentityvpwrRingerAlarmBOverCurrentcurrentRinger A Over-Current protection
1.3.6.1.4.1.13858.12.3NodevpwrRingerTestGroup
1.3.6.1.4.1.13858.13NodevpwrDcPowerDcDcConverter
1.3.6.1.4.1.13858.13.1NodevpwrDcDcConverterConfigGroup
1.3.6.1.4.1.13858.13.2NodevpwrDcDcConverterAlarmGroup
1.3.6.1.4.1.13858.13.3NodevpwrDcDcConverterTestGroup
1.3.6.1.4.1.13858.14NodevpwrDcPowerDcAcInverter
1.3.6.1.4.1.13858.14.1NodevpwrDcAcInverterConfigGroup
1.3.6.1.4.1.13858.14.2NodevpwrDcAcInverterAlarmGroup
1.3.6.1.4.1.13858.14.3NodevpwrDcAcInverterTestGroup
1.3.6.1.4.1.13858.15NodevpwrDcPowerBayController
1.3.6.1.4.1.13858.16NodevpwrDcPowerIoModule
1.3.6.1.4.1.13858.16.1NodevpwrIoModuleConfigGroup
1.3.6.1.4.1.13858.16.2NodevpwrIoModuleAlarmGroup
1.3.6.1.4.1.13858.16.3NodevpwrIoModuleTestGroup
1.3.6.1.4.1.13858.17NodevpwrDcPowerDist
1.3.6.1.4.1.13858.18NodevpwrDcPowerTrio
Type Definitions
NameSyntaxStatusDescription
NonNegativeIntegerINTEGER (0..2147483647)currentThis data type is a non-negative value.
PositiveIntegerINTEGER (1..2147483647)currentThis data type is a non-zero and non-negative value.