VERTIV-IMD-MIB
287 objects
The MIB for Vertiv Products
Imported Objects
| SNMP-FRAMEWORK-MIB | SnmpAdminString |
| SNMPv2-MIB | sysName |
| SNMPv2-SMI | enterprises Gauge32 Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-IDENTITY OBJECT-TYPE |
| SNMPv2-TC | DisplayString |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.21239 | Identityvertiv | The MIB for Vertiv Products | ||
| 1.3.6.1.4.1.21239.5 | Nodeblackbird | |||
| 1.3.6.1.4.1.21239.5.2 | Nodeimd | |||
| 1.3.6.1.4.1.21239.5.2.1 | NodedeviceInfo | |||
| 1.3.6.1.4.1.21239.5.2.1.1 | ScalarproductTitle | read-only | current | Product name |
| 1.3.6.1.4.1.21239.5.2.1.2 | ScalarproductVersion | read-only | current | Product version |
| 1.3.6.1.4.1.21239.5.2.1.3 | ScalarproductFriendlyName | read-only | current | User-assigned name |
| 1.3.6.1.4.1.21239.5.2.1.4 | ScalarproductMacAddress | read-only | current | Product's unique MAC address |
| 1.3.6.1.4.1.21239.5.2.1.6 | ScalardeviceCount | read-only | current | Total number of devices on unit |
| 1.3.6.1.4.1.21239.5.2.1.7 | ScalartemperatureUnits | read-write | current | Current units for temperature/dewpoint values: 0 = Degrees Fahrenheit 1 = Degrees Celsius |
| 1.3.6.1.4.1.21239.5.2.1.8 | ScalarproductModelNumber | read-only | current | Product model number (factory-assigned) |
| 1.3.6.1.4.1.21239.5.2.1.9 | ScalarproductPartNumber | read-only | current | Product part number (factory-assigned) |
| 1.3.6.1.4.1.21239.5.2.1.10 | ScalarproductSerialNumber | read-only | current | Product serial number (factory-assigned) |
| 1.3.6.1.4.1.21239.5.2.1.11 | ScalarproductPlatform | read-only | current | Product platform |
| 1.3.6.1.4.1.21239.5.2.3 | Nodepdu | |||
| 1.3.6.1.4.1.21239.5.2.3.1 | TablepduMainTable | not-accessible | current | PDU general information |
| 1.3.6.1.4.1.21239.5.2.3.1.1 | RowpduMainEntry | not-accessible | current | Entry in the pduMainTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.3.1.1.1 | ColumnpduMainIndex | not-accessible | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.3.1.1.2 | ColumnpduMainSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.3.1.1.3 | ColumnpduMainName | read-only | current | PDU name (factory assigned) |
| 1.3.6.1.4.1.21239.5.2.3.1.1.4 | ColumnpduMainLabel | read-write | current | PDU label (user-defined) |
| 1.3.6.1.4.1.21239.5.2.3.1.1.5 | ColumnpduMainAvail | read-only | current | Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.3.1.1.6 | ColumnpduMeterType | read-only | current | Current meter type: 0 = Wye 1 = Delta |
| 1.3.6.1.4.1.21239.5.2.3.1.1.7 | ColumnpduTotalName | read-only | current | Total Name (factory-assigned) |
| 1.3.6.1.4.1.21239.5.2.3.1.1.8 | ColumnpduTotalLabel | read-write | current | Total Label (user-defined) |
| 1.3.6.1.4.1.21239.5.2.3.1.1.9 | ColumnpduTotalRealPower | read-only | current | PDU total real power |
| 1.3.6.1.4.1.21239.5.2.3.1.1.10 | ColumnpduTotalApparentPower | read-only | current | PDU total apparent power |
| 1.3.6.1.4.1.21239.5.2.3.1.1.11 | ColumnpduTotalPowerFactor | read-only | current | PDU total power factor |
| 1.3.6.1.4.1.21239.5.2.3.1.1.12 | ColumnpduTotalEnergy | read-only | current | PDU total accumulated energy in watt-hours |
| 1.3.6.1.4.1.21239.5.2.3.2 | TablepduPhaseTable | not-accessible | current | PDU phases information |
| 1.3.6.1.4.1.21239.5.2.3.2.1 | RowpduPhaseEntry | not-accessible | current | Entry in the pduPhaseTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.3.2.1.1 | ColumnpduPhaseIndex | not-accessible | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.3.2.1.2 | ColumnpduPhaseName | read-only | current | PDU phase name (factory-assigned) |
| 1.3.6.1.4.1.21239.5.2.3.2.1.3 | ColumnpduPhaseLabel | read-write | current | PDU phase label (user-defined) |
| 1.3.6.1.4.1.21239.5.2.3.2.1.4 | ColumnpduPhaseVoltage | read-only | current | PDU phase voltage in tenths of a volt |
| 1.3.6.1.4.1.21239.5.2.3.2.1.5 | ColumnpduPhaseVoltageMax | read-only | current | Highest RMS voltage measured on this phase, since power-up or last reset. The value is given in tenths of a volt |
| 1.3.6.1.4.1.21239.5.2.3.2.1.6 | ColumnpduPhaseVoltageMin | read-only | current | Lowest RMS voltage measured on this phase, since power-up or last reset. The value is given in tenths of a volt |
| 1.3.6.1.4.1.21239.5.2.3.2.1.7 | ColumnpduPhaseVoltagePeak | read-only | current | Highest instantaneous voltage measured on this phase, since power-up or last reset. The value is given in tenths of a volt. This object may not exist on all pl… |
| 1.3.6.1.4.1.21239.5.2.3.2.1.8 | ColumnpduPhaseCurrent | read-only | current | PDU phase current reading in hundreths of an amp. |
| 1.3.6.1.4.1.21239.5.2.3.2.1.9 | ColumnpduPhaseCurrentMax | read-only | current | Highest RMS current measured on this phase, since power-up or last reset. The value is given in hundreths of an amp. |
| 1.3.6.1.4.1.21239.5.2.3.2.1.10 | ColumnpduPhaseCurrentMin | read-only | current | Lowest RMS current measured on this phase, since power-up or last reset. The value is given in hundreths of an amp. |
| 1.3.6.1.4.1.21239.5.2.3.2.1.11 | ColumnpduPhaseCurrentPeak | read-only | current | Highest instantaneous current measured on ths phase, since power-up or last reset. The value is given in hundreths of an amp. This object may not exist on all … |
| 1.3.6.1.4.1.21239.5.2.3.2.1.12 | ColumnpduPhaseRealPower | read-only | current | Real power for phase in watts |
| 1.3.6.1.4.1.21239.5.2.3.2.1.13 | ColumnpduPhaseApparentPower | read-only | current | Apparent power for phase in volt-amps |
| 1.3.6.1.4.1.21239.5.2.3.2.1.14 | ColumnpduPhasePowerFactor | read-only | current | Power factor for phase |
| 1.3.6.1.4.1.21239.5.2.3.2.1.15 | ColumnpduPhaseEnergy | read-only | current | Accumulated energy for phase in watt-hours |
| 1.3.6.1.4.1.21239.5.2.3.3 | TablepduBreakerTable | not-accessible | current | PDU breaker information |
| 1.3.6.1.4.1.21239.5.2.3.3.1 | RowpduBreakerEntry | not-accessible | current | Entry in the pduBreakerTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.3.3.1.1 | ColumnpduBreakerIndex | not-accessible | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.3.3.1.2 | ColumnpduBreakerName | read-only | current | PDU breaker name (factory-assigned) |
| 1.3.6.1.4.1.21239.5.2.3.3.1.3 | ColumnpduBreakerLabel | read-write | current | PDU breaker label (user-defined) |
| 1.3.6.1.4.1.21239.5.2.3.3.1.4 | ColumnpduBreakerCurrent | read-only | current | PDU breaker current reading in hundreths of an amp |
| 1.3.6.1.4.1.21239.5.2.3.3.1.5 | ColumnpduBreakerCurrentMax | read-only | current | Highest RMS current measured on this breaker, since power-up or last reset. The value is given in hundreths of an amp. |
| 1.3.6.1.4.1.21239.5.2.3.3.1.6 | ColumnpduBreakerCurrentMin | read-only | current | Lowest RMS current measured on this breaker, since power-up or last reset. The value is given in hundreths of an amp. |
| 1.3.6.1.4.1.21239.5.2.3.3.1.7 | ColumnpduBreakerCurrentPeak | read-only | current | Highest instantaneous current measured on this breaker, since power-up or last reset. The value is given in hundreths of an amp. This object may not exist on a… |
| 1.3.6.1.4.1.21239.5.2.3.4 | TablepduLineTable | not-accessible | current | PDU line current information |
| 1.3.6.1.4.1.21239.5.2.3.4.1 | RowpduLineEntry | not-accessible | current | Entry in the pduLineTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.3.4.1.1 | ColumnpduLineIndex | not-accessible | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.3.4.1.2 | ColumnpduLineName | read-only | current | PDU line name (factory-assigned) |
| 1.3.6.1.4.1.21239.5.2.3.4.1.3 | ColumnpduLineLabel | read-write | current | PDU line label (user-defined) |
| 1.3.6.1.4.1.21239.5.2.3.4.1.4 | ColumnpduLineCurrent | read-only | current | PDU line current reading in hundreths of an amp |
| 1.3.6.1.4.1.21239.5.2.3.4.1.5 | ColumnpduLineCurrentMax | read-only | current | Highest RMS current measured on this line, since power-up or last reset. The value is given in hundreths of an amp. |
| 1.3.6.1.4.1.21239.5.2.3.4.1.6 | ColumnpduLineCurrentMin | read-only | current | Lowest RMS current measured on this line, since power-up or last reset. The value is given in hundreths of an amp. |
| 1.3.6.1.4.1.21239.5.2.3.4.1.7 | ColumnpduLineCurrentPeak | read-only | current | Highest instantaneous current measured on this line, since power-up or last reset. The value is given in hundreths of an amp. This object may not exist on all … |
| 1.3.6.1.4.1.21239.5.2.4 | TabletempSensorTable | not-accessible | current | Remote Temperature (RT) sensor |
| 1.3.6.1.4.1.21239.5.2.4.1 | RowtempSensorEntry | not-accessible | current | Entry in the tempSensorTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.4.1.1 | ColumntempSensorIndex | not-accessible | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.4.1.2 | ColumntempSensorSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.4.1.3 | ColumntempSensorLabel | read-write | current | User-defined label |
| 1.3.6.1.4.1.21239.5.2.4.1.4 | ColumntempSensorAvail | read-only | current | Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.4.1.5 | ColumntempSensorTemp | read-only | current | Temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. |
| 1.3.6.1.4.1.21239.5.2.5 | TableairFlowSensorTable | not-accessible | current | Remote Airflow, Humidity, Temperature and Dewpoint (AFHT3) Sensor |
| 1.3.6.1.4.1.21239.5.2.5.1 | RowairFlowSensorEntry | not-accessible | current | Entry in the airFlowSensorTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.5.1.1 | ColumnairFlowSensorIndex | not-accessible | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.5.1.2 | ColumnairFlowSensorSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.5.1.3 | ColumnairFlowSensorLabel | read-write | current | User-defined label |
| 1.3.6.1.4.1.21239.5.2.5.1.4 | ColumnairFlowSensorAvail | read-only | current | Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.5.1.5 | ColumnairFlowSensorTemp | read-only | current | Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo |
| 1.3.6.1.4.1.21239.5.2.5.1.6 | ColumnairFlowSensorFlow | read-only | current | Airflow reading. Still air will be less than 20, while rushing air will be around 100. |
| 1.3.6.1.4.1.21239.5.2.5.1.7 | ColumnairFlowSensorHumidity | read-only | current | Humidity reading |
| 1.3.6.1.4.1.21239.5.2.5.1.8 | ColumnairFlowSensorDewPoint | read-only | current | Dewpoint reading in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. |
| 1.3.6.1.4.1.21239.5.2.6 | TabledewPointSensorTable | not-accessible | current | Remote Dew Point sensor |
| 1.3.6.1.4.1.21239.5.2.6.1 | RowdewPointSensorEntry | not-accessible | current | Entry in the dewPointSensorTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.6.1.1 | ColumndewPointSensorIndex | not-accessible | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.6.1.2 | ColumndewPointSensorSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.6.1.3 | ColumndewPointSensorName | read-only | current | User-defined label |
| 1.3.6.1.4.1.21239.5.2.6.1.4 | ColumndewPointSensorAvail | read-only | current | Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.6.1.5 | ColumndewPointSensorTemp | read-only | current | Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo |
| 1.3.6.1.4.1.21239.5.2.6.1.6 | ColumndewPointSensorHumidity | read-only | current | Humidity reading |
| 1.3.6.1.4.1.21239.5.2.6.1.7 | ColumndewPointSensorDewPoint | read-only | current | Current reading for Dew-point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo |
| 1.3.6.1.4.1.21239.5.2.7 | TableccatSensorTable | not-accessible | current | Remote CCAT sensor |
| 1.3.6.1.4.1.21239.5.2.7.1 | RowccatSensorEntry | not-accessible | current | Entry in the ccatSensorTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.7.1.1 | ColumnccatSensorIndex | not-accessible | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.7.1.2 | ColumnccatSensorSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.7.1.3 | ColumnccatSensorName | read-only | current | User-defined label |
| 1.3.6.1.4.1.21239.5.2.7.1.4 | ColumnccatSensorAvail | read-only | current | Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.7.1.5 | ColumnccatSensorValue | read-only | current | CCAT sensor reading |
| 1.3.6.1.4.1.21239.5.2.7.1.6 | ColumnccatSensorType | read-only | current | CCAT sensor type |
| 1.3.6.1.4.1.21239.5.2.7.1.7 | ColumnccatSensorDescription | read-only | current | CCAT sensor value description |
| 1.3.6.1.4.1.21239.5.2.8 | Tablet3hdSensorTable | not-accessible | current | Remote Temperature x 3, Humidity and Dewpoint Sensor |
| 1.3.6.1.4.1.21239.5.2.8.1 | Rowt3hdSensorEntry | not-accessible | current | Entry in the t3hdSensorTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.8.1.1 | Columnt3hdSensorIndex | not-accessible | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.8.1.2 | Columnt3hdSensorSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.8.1.3 | Columnt3hdSensorLabel | read-write | current | User-defined label |
| 1.3.6.1.4.1.21239.5.2.8.1.4 | Columnt3hdSensorAvail | read-only | current | Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.8.1.5 | Columnt3hdSensorIntLabel | read-write | current | Internal label (user-defined) |
| 1.3.6.1.4.1.21239.5.2.8.1.6 | Columnt3hdSensorIntTemp | read-only | current | Internal temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. |
| 1.3.6.1.4.1.21239.5.2.8.1.7 | Columnt3hdSensorIntHumidity | read-only | current | Internal Humidity |
| 1.3.6.1.4.1.21239.5.2.8.1.8 | Columnt3hdSensorIntDewPoint | read-only | current | Internal dewpoint in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. |
| 1.3.6.1.4.1.21239.5.2.8.1.9 | Columnt3hdSensorExtAAvail | read-only | current | External A status: 0 =Unavailable 1 =Available |
| 1.3.6.1.4.1.21239.5.2.8.1.10 | Columnt3hdSensorExtALabel | read-write | current | External A label (user-defined) |
| 1.3.6.1.4.1.21239.5.2.8.1.11 | Columnt3hdSensorExtATemp | read-only | current | External A temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. |
| 1.3.6.1.4.1.21239.5.2.8.1.12 | Columnt3hdSensorExtBAvail | read-only | current | External B status: 0 = Unavailable 1 = Available |
| 1.3.6.1.4.1.21239.5.2.8.1.13 | Columnt3hdSensorExtBLabel | read-write | current | External B label (user-defined) |
| 1.3.6.1.4.1.21239.5.2.8.1.14 | Columnt3hdSensorExtBTemp | read-only | current | External B temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. |
| 1.3.6.1.4.1.21239.5.2.9 | TablethdSensorTable | not-accessible | current | Remote Temperature, Humidity and Dewpoint (THD) Sensor |
| 1.3.6.1.4.1.21239.5.2.9.1 | RowthdSensorEntry | not-accessible | current | Entry in the thdSensorTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.9.1.1 | ColumnthdSensorIndex | not-accessible | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.9.1.2 | ColumnthdSensorSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.9.1.3 | ColumnthdSensorLabel | read-write | current | User-defined label |
| 1.3.6.1.4.1.21239.5.2.9.1.4 | ColumnthdSensorAvail | read-only | current | Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.9.1.5 | ColumnthdSensorTemp | read-only | current | Temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. |
| 1.3.6.1.4.1.21239.5.2.9.1.6 | ColumnthdSensorHumidity | read-only | current | Humidity value |
| 1.3.6.1.4.1.21239.5.2.9.1.7 | ColumnthdSensorDewPoint | read-only | current | Dewpoint value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. |
| 1.3.6.1.4.1.21239.5.2.10 | TablerpmSensorTable | not-accessible | current | Remote Power Manager Sensor |
| 1.3.6.1.4.1.21239.5.2.10.1 | RowrpmSensorEntry | not-accessible | current | Entry in the rpmSensorTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.10.1.1 | ColumnrpmSensorIndex | not-accessible | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.10.1.2 | ColumnrpmSensorSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.10.1.3 | ColumnrpmSensorName | read-only | current | Friendly Name |
| 1.3.6.1.4.1.21239.5.2.10.1.4 | ColumnrpmSensorAvail | read-only | current | Device availability 0 = Unavailable 1 = Available 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.10.1.5 | ColumnrpmSensorEnergy | read-only | current | RPM Sensor Accumulated Energy |
| 1.3.6.1.4.1.21239.5.2.10.1.6 | ColumnrpmSensorVoltage | read-only | current | RPM Sensor Voltage |
| 1.3.6.1.4.1.21239.5.2.10.1.7 | ColumnrpmSensorVoltageMax | read-only | current | RPM Sensor Voltage (Max) |
| 1.3.6.1.4.1.21239.5.2.10.1.8 | ColumnrpmSensorVoltageMin | read-only | current | RPM Sensor Voltage (Min) |
| 1.3.6.1.4.1.21239.5.2.10.1.9 | ColumnrpmSensorVoltagePeak | read-only | current | RPM Sensor Voltage (Peak) |
| 1.3.6.1.4.1.21239.5.2.10.1.10 | ColumnrpmSensorCurrent | read-only | current | RPM Sensor Current reading in deciAmps |
| 1.3.6.1.4.1.21239.5.2.10.1.11 | ColumnrpmSensorRealPower | read-only | current | RPM Sensor Real Power |
| 1.3.6.1.4.1.21239.5.2.10.1.12 | ColumnrpmSensorApparentPower | read-only | current | RPM Sensor Apparent Power |
| 1.3.6.1.4.1.21239.5.2.10.1.13 | ColumnrpmSensorPowerFactor | read-only | current | RPM Sensor Power Factor |
| 1.3.6.1.4.1.21239.5.2.10.1.14 | ColumnrpmSensorOutlet1 | read-only | current | RPM Sensor Outlet 1 State: 0 = off, 1 = on |
| 1.3.6.1.4.1.21239.5.2.10.1.15 | ColumnrpmSensorOutlet2 | read-only | current | RPM Sensor Outlet 2 State: 0 = off 1 = on |
| 1.3.6.1.4.1.21239.5.2.11 | Tablea2dSensorTable | not-accessible | current | Analog measurement (A2D) sensor (voltage, current, or dry-contact) |
| 1.3.6.1.4.1.21239.5.2.11.1 | Rowa2dSensorEntry | not-accessible | current | Entry in the a2dSensorTable table: each entry contains an index and other sensor details |
| 1.3.6.1.4.1.21239.5.2.11.1.1 | Columna2dSensorIndex | not-accessible | current | Table entry index value |
| 1.3.6.1.4.1.21239.5.2.11.1.2 | Columna2dSensorSerial | read-only | current | Serial Number |
| 1.3.6.1.4.1.21239.5.2.11.1.3 | Columna2dSensorLabel | read-write | current | User-defined label |
| 1.3.6.1.4.1.21239.5.2.11.1.4 | Columna2dSensorAvail | read-only | current | Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable |
| 1.3.6.1.4.1.21239.5.2.11.1.5 | Columna2dSensorValue | read-only | current | Analog measurement value, within either a user-defined or preset range, depending on a2dSensorMode. |
| 1.3.6.1.4.1.21239.5.2.11.1.6 | Columna2dSensorDisplayValue | read-only | current | For current/voltage modes, the analog value is given as a string. In binary modes, the value is either a2dSensorLowLabel or a2dSensorHighLabel, based on a2dSen… |
| 1.3.6.1.4.1.21239.5.2.11.1.7 | Columna2dSensorMode | read-write | current | Binary modes have two states represented by the values 0 (low) or 1 (high). These correspond to a2dSensorLowLabel and a2dSensorHighLabel. Current and voltage m… |
| 1.3.6.1.4.1.21239.5.2.11.1.8 | Columna2dSensorUnits | read-write | current | The units for the analog value. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value. Otherwise, the value is fi… |
| 1.3.6.1.4.1.21239.5.2.11.1.9 | Columna2dSensorMin | read-write | current | Minimum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or … |
| 1.3.6.1.4.1.21239.5.2.11.1.10 | Columna2dSensorMax | read-write | current | Maximum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or … |
| 1.3.6.1.4.1.21239.5.2.11.1.11 | Columna2dSensorLowLabel | read-write | current | Label for 0 (low) binary value. This field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this fiel… |
| 1.3.6.1.4.1.21239.5.2.11.1.12 | Columna2dSensorHighLabel | read-write | current | Label for 1 (high) binary value. The field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this fiel… |
| 1.3.6.1.4.1.21239.5.2.11.1.13 | Columna2dSensorAnalogLabel | read-write | current | Label for the analog measurement |
| 1.3.6.1.4.1.21239.5.2.32767 | Nodetrap | |||
| 1.3.6.1.4.1.21239.5.2.32767.0 | NodetrapPrefix | |||
| 1.3.6.1.4.1.21239.5.2.32767.0.10101 | NotificationinternalTestNOTIFY | current | Test SNMP Trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10305 | NotificationpduMainAvailNOTIFY | current | PDU availability trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10309 | NotificationpduTotalRealPowerNOTIFY | current | PDU total real power trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10310 | NotificationpduTotalApparentPowerNOTIFY | current | PDU total apparent power trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10311 | NotificationpduTotalPowerFactorNOTIFY | current | PDU total power factor trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10312 | NotificationpduTotalEnergyNOTIFY | current | PDU total energy trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10324 | NotificationpduPhaseVoltageNOTIFY | current | PDU phase voltage trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10325 | NotificationpduPhaseVoltageMaxNOTIFY | current | PDU phase voltage (max) trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10326 | NotificationpduPhaseVoltageMinNOTIFY | current | PDU phase voltage (min) trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10327 | NotificationpduPhaseVoltagePeakNOTIFY | current | PDU phase voltage (peak) trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10328 | NotificationpduPhaseCurrentNOTIFY | current | PDU phase current trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10329 | NotificationpduPhaseCurrentMaxNOTIFY | current | PDU phase current (max) trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10330 | NotificationpduPhaseCurrentMinNOTIFY | current | PDU phase current (min) trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10331 | NotificationpduPhaseCurrentPeakNOTIFY | current | PDU phase current (peak) trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10332 | NotificationpduPhaseRealPowerNOTIFY | current | PDU phase real power trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10333 | NotificationpduPhaseApparentPowerNOTIFY | current | PDU phase apparent power trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10334 | NotificationpduPhasePowerFactorNOTIFY | current | PDU phase power factor trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10335 | NotificationpduPhaseEnergyNOTIFY | current | PDU phase energy trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10354 | NotificationpduBreakerCurrentNOTIFY | current | PDU breaker current trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10355 | NotificationpduBreakerCurrentMaxNOTIFY | current | PDU breaker current (max) trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10356 | NotificationpduBreakerCurrentMinNOTIFY | current | PDU breaker current (min) trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10357 | NotificationpduBreakerCurrentPeakNOTIFY | current | PDU breaker current (peak) trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10374 | NotificationpduLineCurrentNOTIFY | current | PDU line current trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10375 | NotificationpduLineCurrentMaxNOTIFY | current | PDU line current (max) trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10376 | NotificationpduLineCurrentMinNOTIFY | current | PDU line current (min) trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10377 | NotificationpduLineCurrentPeakNOTIFY | current | PDU line current (peak) trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10404 | NotificationtempSensorAvailNOTIFY | current | RT availability trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10405 | NotificationtempSensorTempNOTIFY | current | RT temperature trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10504 | NotificationairFlowSensorAvailNOTIFY | current | AFHT3 availability trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10505 | NotificationairFlowSensorTempNOTIFY | current | AFHT3 temperature trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10506 | NotificationairFlowSensorFlowNOTIFY | current | AFHT3 airflow trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10507 | NotificationairFlowSensorHumidityNOTIFY | current | AFHT3 humidity trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10508 | NotificationairFlowSensorDewPointNOTIFY | current | AFHT3 dewpoint trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10604 | NotificationdewPointSensorAvailNOTIFY | current | Dewpoint available trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10605 | NotificationdewPointSensorTempNOTIFY | current | Dewpoint temperature trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10606 | NotificationdewPointSensorHumidityNOTIFY | current | Dewpoint humidity trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10607 | NotificationdewPointSensorDewPointNOTIFY | current | Dewpoint dewpoint trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10704 | NotificationccatSensorAvailNOTIFY | current | CCAT available trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10705 | NotificationccatSensorValueNOTIFY | current | CCAT measurement trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10804 | Notificationt3hdSensorAvailNOTIFY | current | T3HD availability trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10806 | Notificationt3hdSensorIntTempNOTIFY | current | T3HD Internal temperature trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10807 | Notificationt3hdSensorIntHumidityNOTIFY | current | T3HD Internal humidity trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10808 | Notificationt3hdSensorIntDewPointNOTIFY | current | T3HD dewpoint trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10811 | Notificationt3hdSensorExtATempNOTIFY | current | T3HD External A temperature trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10814 | Notificationt3hdSensorExtBTempNOTIFY | current | T3HD External B temperature trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10904 | NotificationthdSensorAvailNOTIFY | current | THD availability trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10905 | NotificationthdSensorTempNOTIFY | current | THD temperature trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10906 | NotificationthdSensorHumidityNOTIFY | current | THD humidity trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.10907 | NotificationthdSensorDewPointNOTIFY | current | THD dewpoint trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11004 | NotificationrpmSensorAvailNOTIFY | current | RPM available trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11005 | NotificationrpmSensorEnergyNOTIFY | current | RPM energy trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11006 | NotificationrpmSensorVoltageNOTIFY | current | RPM voltage trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11007 | NotificationrpmSensorVoltageMaxNOTIFY | current | RPM voltage (max) trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11008 | NotificationrpmSensorVoltageMinNOTIFY | current | RPM voltage (min) trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11009 | NotificationrpmSensorVoltagePeakNOTIFY | current | RPM voltage (peak) trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11010 | NotificationrpmSensorCurrentNOTIFY | current | RPM current trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11011 | NotificationrpmSensorRealPowerNOTIFY | current | RPM real power trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11012 | NotificationrpmSensorApparentPowerNOTIFY | current | RPM apparent power trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11013 | NotificationrpmSensorPowerFactorNOTIFY | current | RPM power factor trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11104 | Notificationa2dSensorAvailNOTIFY | current | A2D availability trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.11105 | Notificationa2dSensorValueNOTIFY | current | A2D measurement trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20305 | NotificationpduMainAvailCLEAR | current | PDU availability clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20309 | NotificationpduTotalRealPowerCLEAR | current | PDU total real power clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20310 | NotificationpduTotalApparentPowerCLEAR | current | PDU total apparent power clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20311 | NotificationpduTotalPowerFactorCLEAR | current | PDU total power factor clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20312 | NotificationpduTotalEnergyCLEAR | current | PDU total energy clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20324 | NotificationpduPhaseVoltageCLEAR | current | PDU phase voltage clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20325 | NotificationpduPhaseVoltageMaxCLEAR | current | PDU phase voltage (max) clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20326 | NotificationpduPhaseVoltageMinCLEAR | current | PDU phase voltage (min) clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20327 | NotificationpduPhaseVoltagePeakCLEAR | current | PDU phase voltage (peak) clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20328 | NotificationpduPhaseCurrentCLEAR | current | PDU phase current clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20329 | NotificationpduPhaseCurrentMaxCLEAR | current | PDU phase current (max) clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20330 | NotificationpduPhaseCurrentMinCLEAR | current | PDU phase current (min) clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20331 | NotificationpduPhaseCurrentPeakCLEAR | current | PDU phase current (peak) clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20332 | NotificationpduPhaseRealPowerCLEAR | current | PDU phase real power clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20333 | NotificationpduPhaseApparentPowerCLEAR | current | PDU phase apparent power clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20334 | NotificationpduPhasePowerFactorCLEAR | current | PDU phase power factor clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20335 | NotificationpduPhaseEnergyCLEAR | current | PDU phase energy clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20354 | NotificationpduBreakerCurrentCLEAR | current | PDU breaker current clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20355 | NotificationpduBreakerCurrentMaxCLEAR | current | PDU breaker current (max) clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20356 | NotificationpduBreakerCurrentMinCLEAR | current | PDU breaker current (min) clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20357 | NotificationpduBreakerCurrentPeakCLEAR | current | PDU breaker current (peak) clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20374 | NotificationpduLineCurrentCLEAR | current | PDU line current clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20375 | NotificationpduLineCurrentMaxCLEAR | current | PDU line current (max) clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20376 | NotificationpduLineCurrentMinCLEAR | current | PDU line current (min) clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20377 | NotificationpduLineCurrentPeakCLEAR | current | PDU line current (peak) clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20404 | NotificationtempSensorAvailCLEAR | current | RT availability clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20405 | NotificationtempSensorTempCLEAR | current | RT temperature clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20504 | NotificationairFlowSensorAvailCLEAR | current | AFHT3 availability clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20505 | NotificationairFlowSensorTempCLEAR | current | AFHT3 temperature clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20506 | NotificationairFlowSensorFlowCLEAR | current | AFHT3 airflow clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20507 | NotificationairFlowSensorHumidityCLEAR | current | AFHT3 humidity clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20508 | NotificationairFlowSensorDewPointCLEAR | current | AFHT3 dewpoint clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20604 | NotificationdewPointSensorAvailCLEAR | current | Dewpoint available clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20605 | NotificationdewPointSensorTempCLEAR | current | Dewpoint temperature clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20606 | NotificationdewPointSensorHumidityCLEAR | current | Dewpoint humidity clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20607 | NotificationdewPointSensorDewPointCLEAR | current | Dewpoint dewpoint clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20704 | NotificationccatSensorAvailCLEAR | current | CCAT available clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20705 | NotificationccatSensorValueCLEAR | current | CCAT measurement clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20804 | Notificationt3hdSensorAvailCLEAR | current | T3HD availability clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20806 | Notificationt3hdSensorIntTempCLEAR | current | T3HD Internal temperature clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20807 | Notificationt3hdSensorIntHumidityCLEAR | current | T3HD Internal humidity clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20808 | Notificationt3hdSensorIntDewPointCLEAR | current | T3HD dewpoint clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20811 | Notificationt3hdSensorExtATempCLEAR | current | T3HD External A temperature clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20814 | Notificationt3hdSensorExtBTempCLEAR | current | T3HD External B temperature clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20904 | NotificationthdSensorAvailCLEAR | current | THD availability clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20905 | NotificationthdSensorTempCLEAR | current | THD temperature clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20906 | NotificationthdSensorHumidityCLEAR | current | THD humidity clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.20907 | NotificationthdSensorDewPointCLEAR | current | THD dewpoint clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21004 | NotificationrpmSensorAvailCLEAR | current | RPM available clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21005 | NotificationrpmSensorEnergyCLEAR | current | RPM energy clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21006 | NotificationrpmSensorVoltageCLEAR | current | RPM voltage clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21007 | NotificationrpmSensorVoltageMaxCLEAR | current | RPM voltage (max) clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21008 | NotificationrpmSensorVoltageMinCLEAR | current | RPM voltage (min) clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21009 | NotificationrpmSensorVoltagePeakCLEAR | current | RPM voltage (peak) clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21010 | NotificationrpmSensorCurrentCLEAR | current | RPM current clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21011 | NotificationrpmSensorRealPowerCLEAR | current | RPM real power clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21012 | NotificationrpmSensorApparentPowerCLEAR | current | RPM apparent power clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21013 | NotificationrpmSensorPowerFactorCLEAR | current | RPM power factor clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21104 | Notificationa2dSensorAvailCLEAR | current | A2D availability clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.0.21105 | Notificationa2dSensorValueCLEAR | current | A2D measurement clear trap | |
| 1.3.6.1.4.1.21239.5.2.32767.1 | NodetrapObj | |||
| 1.3.6.1.4.1.21239.5.2.32767.1.1 | ScalartrapSeverity | accessible-for-notify | current | Indicates the severity of the trap: 0 = None, 1 = Warning, 2 = Alarm |
| 1.3.6.1.4.1.21239.5.2.32767.1.2 | ScalartrapThreshType | accessible-for-notify | current | Only sent for threshold alarms. Identifies the threshold type: 1 = Low, 2 = High |
| 1.3.6.1.4.1.21239.42 | Nodecommon | |||
| 1.3.6.1.4.1.21239.42.1 | Nodeidentity | |||
| 1.3.6.1.4.1.21239.42.1.31 | Identitywd15 | current | Value (OID) used to identify a WD-15 unit | |
| 1.3.6.1.4.1.21239.42.1.32 | Identitywd100 | current | Value (OID) used to identify a WD-100 unit | |
| 1.3.6.1.4.1.21239.42.1.52 | Identityi02 | current | Value (OID) used to identify a GU1 (I-02) unit |