MIB Version 2.0 History Apr 26, 2007 Added SysAlarm Config Table Version 2.0 Feb 08, 2003 Changed vpwrTrapDestinationTable to vpwrTrapTable Corrected entry for vpwrTrapTable to be VpwrTrapTableEntry This fixes errors generated by MG-SOFT mib compiler.Ver1.0 Oct 30, 2002 initial release - version 0.4
Imported Objects
RFC1213-MIBsysUpTime
SNMPv2-CONFMODULE-COMPLIANCE OBJECT-GROUP
SNMPv2-SMICounter32 enterprises Gauge32 Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-IDENTITY OBJECT-TYPE
SNMPv2-TCAutonomousType DisplayString TestAndIncr TEXTUAL-CONVENTION TimeInterval TimeStamp
OIDNameAccessStatusDescription
1.3.6.1.4.1.13858IdentityvalereDcPowerMgtMIB Version 2.0 History Apr 26, 2007 Added SysAlarm Config Table Version 2.0 Feb 08, 2003 Changed vpwrTrapDestinationTable to vpwrTrapTable Corrected entry for…
1.3.6.1.4.1.13858.1NodevpwrDcPowerProducts
1.3.6.1.4.1.13858.2NodevpwrDcPowerSystem
1.3.6.1.4.1.13858.2.1NodevpwrSystemIdentGroup
1.3.6.1.4.1.13858.2.1.1ScalarvpwrIdentManufacturerread-onlycurrentThe name of the DC Power manufacturer.
1.3.6.1.4.1.13858.2.1.2ScalarvpwrIdentModelread-onlycurrentThe DC Power Model designation.
1.3.6.1.4.1.13858.2.1.3ScalarvpwrIdentControllerVersionread-onlycurrentThe hardware/firmware version(s). This variable may or may not have the same value as vpwrIdentAgentSoftwareVersion.
1.3.6.1.4.1.13858.2.1.4ScalarvpwrIdentAgentSoftwareVersionread-onlycurrentThe SNMP agent software version. This variable may or may not have the same value as vpwrIdentControllerFirmwareVersion.
1.3.6.1.4.1.13858.2.1.5ScalarvpwrIdentNameread-writecurrentA string identifying the system. This object should be set by the administrator.
1.3.6.1.4.1.13858.2.1.6TablevpwrSystemIdentTablenot-accessiblecurrentThis table describes shelves and modules that make up the sysetm.
1.3.6.1.4.1.13858.2.1.6.1RowvpwrSystemIdentEntrynot-accessiblecurrentAn entry containing information applicable to a particular module making up the system.
1.3.6.1.4.1.13858.2.1.6.1.1ColumnvpwrShelfIndexread-onlycurrentIdentifies shelf number that this module belongs to. The possible values are 1 through 16 limited by vpwrSystemShelfCapacity. The shelf that contains the contr…
1.3.6.1.4.1.13858.2.1.6.1.2ColumnvpwrModuleIndexread-onlycurrentThis object identifies the module by its position in the shelf. Module numbering starts from the controller/expansion controller end of the shelf. So, the modu…
1.3.6.1.4.1.13858.2.1.6.1.3ColumnvpwrModuleOIDread-onlycurrentIt indicates the type of the module by specifiying its OID
1.3.6.1.4.1.13858.2.1.6.1.4ColumnvpwrModuleParameterread-onlycurrentThe meaning of this object depends upon the module type which is indicated by vpwrModuleOID as follows - Current for Rectifier module. - Not Applicable for LVD…
1.3.6.1.4.1.13858.2.1.6.1.5ColumnvpwrModuleOperStatusread-onlycurrentThis object indicates current over all status of the module.
1.3.6.1.4.1.13858.2.1.6.1.6ColumnvpwrModuleCapacityread-onlycurrentThe meaning of this object depends upon the module type which is indicated by vpwrModuleOID as follows - Capacity for Rectifier module. - Not Applicable for LV…
1.3.6.1.4.1.13858.2.2NodevpwrSystemConfigGroup
1.3.6.1.4.1.13858.2.2.1ScalarvpwrSystemTempCompensationread-writecurrentThis parameter enables/disables temperature compensation.
1.3.6.1.4.1.13858.2.2.2ScalarvpwrSystemTempCompStartTemperatureread-writecurrentThe temperature at which temperature compensation becomes active.
1.3.6.1.4.1.13858.2.2.3ScalarvpwrSystemTempCompStopVoltageread-writecurrentWhen temperature compensation is active, vpwrSystemTempCompStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage to…
1.3.6.1.4.1.13858.2.2.4ScalarvpwrSystemTempCompensationSloperead-writecurrentThe rate at which float voltage is changed, within the specified limits, when temperature compensation is active.
1.3.6.1.4.1.13858.2.2.5ScalarvpwrSystemThermalSenseTyperead-writecurrentThis parameter selects the temperature sensing point for temperature compensation (in)activation.
1.3.6.1.4.1.13858.2.2.6ScalarvpwrSystemHVAlarmSetpointread-writecurrentSystem High voltage alarm voltage setting.
1.3.6.1.4.1.13858.2.2.7ScalarvpwrSystemBDAlarmSetpointread-writecurrentSystem Battery Discharge voltage setting.
1.3.6.1.4.1.13858.2.2.8ScalarvpwrSystemInternalTempLThresholdread-writecurrentTemperature value at which temperature compensation inactive (clear) trap would be sent if temperature compensation was active when this value is reached.
1.3.6.1.4.1.13858.2.2.9ScalarvpwrSystemInternalTempUThresholdread-writecurrentTemperature value at which temperature compensation active (set) trap would be sent.
1.3.6.1.4.1.13858.2.3NodevpwrSystemParameterGroup
1.3.6.1.4.1.13858.2.3.1ScalarvpwrSystemShelfCapacityread-onlycurrentIt describes the maximum number of shelves that can/are controlled by the controller. Each shelf is uniquely numbered in the range from 1 to vpwrShelfCapacity.
1.3.6.1.4.1.13858.2.3.2ScalarvpwrSystemVoltageread-onlycurrentThe current system voltage.
1.3.6.1.4.1.13858.2.3.3ScalarvpwrSystemCurrentread-onlycurrentThe current system current.
1.3.6.1.4.1.13858.2.3.4ScalarvpwrSystemControllerStateread-onlycurrentCurrent System state as shown on the enhanced display.
1.3.6.1.4.1.13858.2.3.5ScalarvpwrSystemInternalTemperatureread-onlycurrentThe current controller internal temperature.
1.3.6.1.4.1.13858.2.3.6ScalarvpwrSystemTempCompensationStateread-onlycurrentActive or Inactive. Applicable only if temperature compensation is enabled. This means that the controller is temperature compensating the float voltage.
1.3.6.1.4.1.13858.2.3.7ScalarvpwrSystemTyperead-onlycurrentThis parameter describes the type of the system being managed. This object is set by Valere Power Inc.
1.3.6.1.4.1.13858.3NodevpwrDcPowerRectifier
1.3.6.1.4.1.13858.3.1NodevpwrRectifierConfigGroup
1.3.6.1.4.1.13858.3.1.1ScalarvpwrRectifierFVSetpointread-writecurrentSystem Float Voltage setting
1.3.6.1.4.1.13858.3.1.2ScalarvpwrRectifierHVSDSetpointread-writecurrentSystem High Voltage Shutdown voltage setting
1.3.6.1.4.1.13858.3.2NodevpwrRectifierAlarmGroup
1.3.6.1.4.1.13858.3.2.1IdentityvpwrRectAlarmDCFailcurrent
1.3.6.1.4.1.13858.3.2.2IdentityvpwrRectAlarmBoostFailcurrent
1.3.6.1.4.1.13858.3.2.3IdentityvpwrRectAlarmACFailcurrent
1.3.6.1.4.1.13858.3.2.4IdentityvpwrRectAlarmHVSDcurrent
1.3.6.1.4.1.13858.3.2.5IdentityvpwrRectAlarmFanFailcurrent
1.3.6.1.4.1.13858.3.2.6IdentityvpwrRectAlarmAmbTempcurrent
1.3.6.1.4.1.13858.3.2.7IdentityvpwrRectAlarmIntTempcurrent
1.3.6.1.4.1.13858.3.2.8IdentityvpwrRectAlarmISharecurrent
1.3.6.1.4.1.13858.3.2.9IdentityvpwrRectAlarmUVcurrent
1.3.6.1.4.1.13858.3.2.10IdentityvpwrRectAlarmLowVoltagecurrent
1.3.6.1.4.1.13858.3.2.11IdentityvpwrRectAlarmReservedcurrent
1.3.6.1.4.1.13858.3.2.12IdentityvpwrRectAlarmDCEnablecurrent
1.3.6.1.4.1.13858.3.2.13IdentityvpwrRectAlarmRemoteShutdowncurrent
1.3.6.1.4.1.13858.3.2.14IdentityvpwrRectAlarmModDisableShutdowncurrent
1.3.6.1.4.1.13858.3.2.15IdentityvpwrRectAlarmShortPinShutdowncurrent
1.3.6.1.4.1.13858.3.2.16IdentityvpwrRectAlarmBoostCommcurrent
1.3.6.1.4.1.13858.3.3NodevpwrRectifierTestGroup
1.3.6.1.4.1.13858.4NodevpwrDcPowerLvd
1.3.6.1.4.1.13858.4.1NodevpwrLvdConfigGroup
1.3.6.1.4.1.13858.4.1.1ScalarvpwrLvdWarningSetpointread-writecurrentLVD Warning voltage setpoint.
1.3.6.1.4.1.13858.4.1.2ScalarvpwrLvdDisconnectSetpointread-writecurrentLVD disconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.3ScalarvpwrLvdReconnectSetpointread-writecurrentLVD Reconnect voltage setpoint.
1.3.6.1.4.1.13858.4.1.4ScalarvpwrLvdReconnectDelayTimerread-writecurrentThe delay time, in seconds, before LVD is reconnected
1.3.6.1.4.1.13858.4.2NodevpwrLvdAlarmGroup
1.3.6.1.4.1.13858.4.2.1IdentityvpwrLvdAlarmContactorOpencurrentContactor open
1.3.6.1.4.1.13858.4.2.2IdentityvpwrLvdAlarmCBOpencurrentCircuit Breaker open
1.3.6.1.4.1.13858.4.2.3IdentityvpwrTrapLvdFuseOpencurrentFuse open
1.3.6.1.4.1.13858.4.2.4IdentityvpwrLvdAlarmWarningcurrentPlant Voltage below warning threshold
1.3.6.1.4.1.13858.4.3NodevpwrLvdTestGroup
1.3.6.1.4.1.13858.5NodevpwrDcPowerTest
1.3.6.1.4.1.13858.6NodevpwrDcPowerModuleIdent
1.3.6.1.4.1.13858.7NodevpwrDcPowerBatteryGroup
1.3.6.1.4.1.13858.7.1NodevpwrBatteryTempGroup
1.3.6.1.4.1.13858.7.1.1TablevpwrBatteryTempTablenot-accessiblecurrentThis table describes battery temperature probes.
1.3.6.1.4.1.13858.7.1.1.1RowvpwrBatteryTempTableEntrynot-accessiblecurrentAn entry containing information applicable to a particular temperature probe.
1.3.6.1.4.1.13858.7.1.1.1.1ColumnvpwrBatteryTempIndexread-onlycurrentIndex into temperature table
1.3.6.1.4.1.13858.7.1.1.1.2ColumnvpwrBatteryTempNameread-writecurrentA string identifying probe location.
1.3.6.1.4.1.13858.7.1.1.1.3ColumnvpwrBatteryTempread-onlycurrentCurrent temperature as recorded by the probe.
1.3.6.1.4.1.13858.7.1.2ScalarvpwrBatteryTempLThresholdread-writecurrentTemperature value at which a clear trap would be sent. All three battery temperature must be at or below this value to trigger this trap.
1.3.6.1.4.1.13858.7.1.3ScalarvpwrBatteryTempUThresholdread-writecurrentTemperature value at which a set trap would be sent. Any one of the three battery temperatures at or exceeding this limit would trigger the trap.
1.3.6.1.4.1.13858.8NodevpwrDcPowerAlarmGroup
1.3.6.1.4.1.13858.8.1ScalarvpwrAlarmsPresentread-onlycurrentThe present number of active alarm conditions.
1.3.6.1.4.1.13858.8.2TablevpwrAlarmTablenot-accessiblecurrentA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.13858.8.2.1RowvpwrAlarmEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.
1.3.6.1.4.1.13858.8.2.1.1ColumnvpwrAlarmIndexread-onlycurrentIdentifies the alarm associated with the module. It is unique on per module type basis. For example, multiple rectifiers can have the same alarm and therefore …
1.3.6.1.4.1.13858.8.2.1.2ColumnvpwrAlarmDescrread-onlycurrentA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.13858.8.2.1.3ColumnvpwrAlarmTimeread-onlycurrentThe value of sysUpTime when the alarm condition was detected.
1.3.6.1.4.1.13858.8.4TablesysAlarmConfigTablenot-accessiblecurrentThis table describes battery temperature probes.
1.3.6.1.4.1.13858.8.4.1RowsysAlarmConfigEntrynot-accessiblecurrentAn entry containing information applicable to a particular temperature probe.
1.3.6.1.4.1.13858.8.4.1.1ColumnsysAlarmIndexread-onlycurrentIndex into temperature table
1.3.6.1.4.1.13858.8.4.1.2ColumnsysAlarmDefaultNameread-onlycurrentA string identifying probe location.
1.3.6.1.4.1.13858.8.4.1.3ColumnsysAlarmCustomNameread-writecurrentA string identifying probe location.
1.3.6.1.4.1.13858.8.4.1.4ColumnsysAlarmSeverityread-writecurrentAlarm Severity as denoted by Major and Minor Alarm Mask
1.3.6.1.4.1.13858.8.4.1.5ColumnsysAlarmToRelayMappingread-writecurrentNo additional mapping = 0 Map to Relay A = 1 Map to Relay B = 2 Map to Relay C = 4 Map to Relay D = 8 Map to Relay E = 16 Map to Relay F = 32 Map to Relay A an…
1.3.6.1.4.1.13858.8.4.1.6ColumnsysAlarmOperStatusread-onlycurrentIndicates current alarm status
1.3.6.1.4.1.13858.9NodevpwrDcPowerSnmpConfig
1.3.6.1.4.1.13858.9.1TablevpwrTrapTablenot-accessiblecurrentA list of possible trap destinations depending upon the criticality of the trap.
1.3.6.1.4.1.13858.9.1.1RowvpwrTrapTableEntrynot-accessiblecurrentAn entry containing information applicable to a particular trap destination.
1.3.6.1.4.1.13858.9.1.1.1ColumnvpwrTrapIpIndexread-onlycurrentTrap Entry Index
1.3.6.1.4.1.13858.9.1.1.2ColumnvpwrTrapIpAddressread-writecurrentTrap destination IP Address
1.3.6.1.4.1.13858.9.1.1.3ColumnvpwrTrapCriticalityread-writecurrentCriticality of traps sent to this IP Address
1.3.6.1.4.1.13858.9.2ScalarvpwrReadCommunityStringread-writecurrentThis allows setting password to be able to do Get operations
1.3.6.1.4.1.13858.9.3ScalarvpwrWriteCommunityStringread-writecurrentThis allows setting password to be able to do Get and Set operations. The read-access is not allowed in the actual implementation.
1.3.6.1.4.1.13858.9.4ScalarvpwrTrapCommunityStringread-writecurrentThis allows setting community string required for the trap to be accepted at the destination.
1.3.6.1.4.1.13858.10NodevpwrDcPowerTraps
1.3.6.1.4.1.13858.10.1NodevpwrTrapPowerMajorAlarmMajor Alarm
1.3.6.1.4.1.13858.10.2NodevpwrTrapPowerMinorAlarmMinor Alarm
1.3.6.1.4.1.13858.10.3NodevpwrTrapACFAlarmAC Fail Alarm
1.3.6.1.4.1.13858.10.4NodevpwrTrapHVAlarmHigh Voltage Warning Alarm
1.3.6.1.4.1.13858.10.5NodevpwrTrapHVSDAlarmHigh Voltage Shutdown Alarm
1.3.6.1.4.1.13858.10.6NodevpwrTrapBDAlarmBattery on Discharge Alarm
1.3.6.1.4.1.13858.10.7NodevpwrTrapLVDWarningAlarmLVD Warning Alarm
1.3.6.1.4.1.13858.10.8NodevpwrTrapLVDOpenAlarmLVD Open Alarm
1.3.6.1.4.1.13858.10.9NodevpwrTrapDistAlarmDistribution Open Alarm
1.3.6.1.4.1.13858.10.10NodevpwrTrapAuxAlarmAuxiliary System Alarm
1.3.6.1.4.1.13858.10.11NodevpwrTrapSystemRedundancyAlarmSystem Redundant Capacity Alarm
1.3.6.1.4.1.13858.10.12NodevpwrTrapIShareAlarmRectifier Current Share Alarm
1.3.6.1.4.1.13858.10.13NodevpwrTrapModuleFailAlarmSingle Rectifier Fail Alarm
1.3.6.1.4.1.13858.10.14NodevpwrTrapMultipleModuleFailAlarmMultiple Rectifier Fail Alarm
1.3.6.1.4.1.13858.10.15NodevpwrTrapModuleCommAlarmModule Communication Alarm
1.3.6.1.4.1.13858.10.16NodevpwrTrapSystemOverTemperatureAlarmSystem Over Temperature Alarm
1.3.6.1.4.1.13858.10.17NodevpwrTrapSystemOKSYSTEM OK - No Active Alarms
1.3.6.1.4.1.13858.10.18NodevpwrTrapModuleInsertedA new module has been inserted into the system.
1.3.6.1.4.1.13858.10.19NodevpwrTrapModuleRemovedA module has been removed from the system.
1.3.6.1.4.1.13858.10.20NodevpwrTrapThermalCompActiveThermal compensation has become active.
1.3.6.1.4.1.13858.10.21NodevpwrTrapThermalCompInactiveThermal compensation has been de-activated.
1.3.6.1.4.1.13858.10.22NodevpwrTrapInternalTempAlarmSetInternal Temperature upper threshold exceeded.
1.3.6.1.4.1.13858.10.23NodevpwrTrapInternalTempAlarmClearedInternal Temperature within limits
1.3.6.1.4.1.13858.10.24NodevpwrTrapBatteryTempAlarmSetAt least one Battery Temperature exceeded upper threshold.
1.3.6.1.4.1.13858.10.25NodevpwrTrapBatteryTempAlarmClearedAll Battery Temperatures within limits
1.3.6.1.4.1.13858.11NodevpwrDcPowerTrapsMsgString
1.3.6.1.4.1.13858.11.1ScalarvpwrTrapsMsgStringnot-accessiblecurrentPlace holder for trap notification message string
Type Definitions
NameSyntaxStatusDescription
NonNegativeIntegerINTEGER (0..2147483647)currentThis data type is a non-negative value.
PositiveIntegerINTEGER (1..2147483647)currentThis data type is a non-zero and non-negative value.