| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.935 | Nodeppc | |||
| 1.3.6.1.4.1.935.1 | NodecommunicationLost | SEVERE: Communication to the UPS has been lost. Steps to reestablish communication are in progress. | ||
| 1.3.6.1.4.1.935.1 | Nodeproducts | |||
| 1.3.6.1.4.1.935.1.1 | Nodehardware | |||
| 1.3.6.1.4.1.935.1.1.1 | Nodeups | |||
| 1.3.6.1.4.1.935.1.1.1.1 | NodeupsIdentp | |||
| 1.3.6.1.4.1.935.1.1.1.1.1 | NodeupsBaseIdent | |||
| 1.3.6.1.4.1.935.1.1.1.1.1.1 | ScalarupsBaseIdentModel | read-only | mandatory | The UPS model name (e.g. 'Intelligent 8000E 900VA'). |
| 1.3.6.1.4.1.935.1.1.1.1.1.2 | ScalarupsBaseIdentUpsName | read-write | mandatory | An 8 byte ID string identifying the UPS. This object can be set by the administrator. |
| 1.3.6.1.4.1.935.1.1.1.1.2 | NodeupsSmartIdent | |||
| 1.3.6.1.4.1.935.1.1.1.1.2.1 | ScalarupsSmartIdentFirmwareRevision | read-only | mandatory | The firmware revision of the UPS system. |
| 1.3.6.1.4.1.935.1.1.1.1.2.2 | ScalarupsSmartIdentDateOfManufacture | read-only | mandatory | The date when the UPS was manufactured in mm/dd/yy format. |
| 1.3.6.1.4.1.935.1.1.1.1.2.3 | ScalarupsSmartIdentUpsSerialNumber | read-only | mandatory | An 8-character string identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspon… |
| 1.3.6.1.4.1.935.1.1.1.1.2.4 | ScalarupsSmartIdentAgentFirmwareRevision | read-only | mandatory | The firmware revision of the UPS SNMP Proxy agent. |
| 1.3.6.1.4.1.935.1.1.1.2 | NodeupsBatteryp | |||
| 1.3.6.1.4.1.935.1.1.1.2.1 | NodeupsBaseBattery | |||
| 1.3.6.1.4.1.935.1.1.1.2.1.1 | ScalarupsBaseBatteryStatus | read-only | mandatory | The status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is … |
| 1.3.6.1.4.1.935.1.1.1.2.1.2 | ScalarupsBaseBatteryTimeOnBattery | read-only | mandatory | The elapsed time in seconds since the UPS has switched to battery power. |
| 1.3.6.1.4.1.935.1.1.1.2.1.3 | ScalarupsBaseBatteryLastReplaceDate | read-write | mandatory | The date when the UPS system's batteries were last replaced in mm/dd/yy format. For UPS models, this value is originally set in the factory. When the UPS batte… |
| 1.3.6.1.4.1.935.1.1.1.2.2 | NodeupsSmartBattery | |||
| 1.3.6.1.4.1.935.1.1.1.2.2.1 | ScalarupsSmartBatteryCapacity | read-only | mandatory | The remaining battery capacity expressed in percent of full capacity. |
| 1.3.6.1.4.1.935.1.1.1.2.2.2 | ScalarupsSmartBatteryVoltage | read-only | mandatory | The current battery voltage expressed in 1/10 VDC. |
| 1.3.6.1.4.1.935.1.1.1.2.2.3 | ScalarupsSmartBatteryTemperature | read-only | mandatory | The current internal UPS temperature expressed in tenths of a Celsius degree. |
| 1.3.6.1.4.1.935.1.1.1.2.2.4 | ScalarupsSmartBatteryRunTimeRemaining | read-only | mandatory | The UPS battery run time remaining before battery exhaustion, in seconds. |
| 1.3.6.1.4.1.935.1.1.1.2.2.5 | ScalarupsSmartBatteryReplaceIndicator | read-only | mandatory | Indicates whether the UPS batteries need replacing. |
| 1.3.6.1.4.1.935.1.1.1.2.2.6 | ScalarupsSmartBatteryFullChargeVoltage | read-only | mandatory | The fully charged battery voltage of the battery system used in the UPS, expressed in tenths of a volt. |
| 1.3.6.1.4.1.935.1.1.1.2.2.7 | ScalarupsSmartBatteryCurrent | read-only | mandatory | The current battery current expressed in percent of maximum current. |
| 1.3.6.1.4.1.935.1.1.1.3 | NodeupsInputp | |||
| 1.3.6.1.4.1.935.1.1.1.3.1 | NodeupsBaseInput | |||
| 1.3.6.1.4.1.935.1.1.1.3.1.1 | ScalarupsBaseInputPhase | read-only | mandatory | The current AC input phase. |
| 1.3.6.1.4.1.935.1.1.1.3.2 | NodeupsSmartInput | |||
| 1.3.6.1.4.1.935.1.1.1.3.2.1 | ScalarupsSmartInputLineVoltage | read-only | mandatory | The current utility line voltage in 1/10 VAC. |
| 1.3.6.1.4.1.935.1.1.1.3.2.2 | ScalarupsSmartInputMaxLineVoltage | read-only | mandatory | The maximum utility line voltage in 1/10 VAC over the previous 1 minute period. |
| 1.3.6.1.4.1.935.1.1.1.3.2.3 | ScalarupsSmartInputMinLineVoltage | read-only | mandatory | The minimum utility line voltage in 1/10 VAC over the previous 1 minute period. |
| 1.3.6.1.4.1.935.1.1.1.3.2.4 | ScalarupsSmartInputFrequency | read-only | mandatory | The current input frequency to the UPS system in 1/10 Hz. |
| 1.3.6.1.4.1.935.1.1.1.3.2.5 | ScalarupsSmartInputLineFailCause | read-only | mandatory | The reason for the occurrence of the last transfer to UPS battery power. The variable is set to noTransfer(1) if there is no transfer yet. The variable is set … |
| 1.3.6.1.4.1.935.1.1.1.4 | NodeupsOutputp | |||
| 1.3.6.1.4.1.935.1.1.1.4.1 | NodeupsBaseOutput | |||
| 1.3.6.1.4.1.935.1.1.1.4.1.1 | ScalarupsBaseOutputStatus | read-only | mandatory | The current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1). |
| 1.3.6.1.4.1.935.1.1.1.4.1.2 | ScalarupsBaseOutputPhase | read-only | mandatory | The current output phase. |
| 1.3.6.1.4.1.935.1.1.1.4.2 | NodeupsSmartOutput | |||
| 1.3.6.1.4.1.935.1.1.1.4.2.1 | ScalarupsSmartOutputVoltage | read-only | mandatory | The output voltage of the UPS system in 1/10 VAC. |
| 1.3.6.1.4.1.935.1.1.1.4.2.2 | ScalarupsSmartOutputFrequency | read-only | mandatory | The current output frequency of the UPS system in 1/10 Hz. |
| 1.3.6.1.4.1.935.1.1.1.4.2.3 | ScalarupsSmartOutputLoad | read-only | mandatory | The current UPS load expressed in percent of rated capacity. |
| 1.3.6.1.4.1.935.1.1.1.5 | NodeupsConfigp | |||
| 1.3.6.1.4.1.935.1.1.1.5.1 | NodeupsBaseConfig | |||
| 1.3.6.1.4.1.935.1.1.1.5.1.1 | ScalarupsBaseConfigNumDevices | read-only | mandatory | The number of devices that are plugged into the UPS. |
| 1.3.6.1.4.1.935.1.1.1.5.1.2 | TableupsBaseConfigDeviceTable | not-accessible | mandatory | A list of devices that are plugged into the UPS. The number of entries is given by the value of upsBaseConfigNumDevices. |
| 1.3.6.1.4.1.935.1.1.1.5.1.2.1 | RowupsBaseConfigDeviceEntry | not-accessible | mandatory | The devices plugged in to the UPS. |
| 1.3.6.1.4.1.935.1.1.1.5.1.2.1.1 | ColumnindexOfDevice | read-only | mandatory | The index of the device that is plugged into the UPS. |
| 1.3.6.1.4.1.935.1.1.1.5.1.2.1.2 | ColumnnameOfDevice | read-write | mandatory | The name/description of the device plugged into the UPS. |
| 1.3.6.1.4.1.935.1.1.1.5.1.2.1.3 | ColumnvaRatingOfDevice | read-write | mandatory | The volt-amp rating of the device plugged into the UPS. |
| 1.3.6.1.4.1.935.1.1.1.5.1.2.1.4 | ColumndeviceAccept | read-write | mandatory | An entry is added if yes, the entry is deleted if no. |
| 1.3.6.1.4.1.935.1.1.1.5.2 | NodeupsSmartConfig | |||
| 1.3.6.1.4.1.935.1.1.1.5.2.1 | ScalarupsSmartConfigRatedOutputVoltage | read-write | mandatory | The nominal output voltage from the UPS in 1/10 VAC. Possible values are 1000, 1200, 2080, 2200, 2250, 2300 and 2400. NOTE: Only units that are 2200, 2250, 230… |
| 1.3.6.1.4.1.935.1.1.1.5.2.2 | ScalarupsSmartConfigHighTransferVolt | read-write | mandatory | The maximum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup. Allowed value depend on the UPS used: 120 Volt units allow sett… |
| 1.3.6.1.4.1.935.1.1.1.5.2.3 | ScalarupsSmartConfigLowTransferVolt | read-write | mandatory | The minimum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup. Allowable values depend on the UPS used: 120 Volt units allow s… |
| 1.3.6.1.4.1.935.1.1.1.5.2.4 | ScalarupsSmartConfigAlarm | read-write | mandatory | A flag indicating how the UPS should handle audible line fail alarms. |
| 1.3.6.1.4.1.935.1.1.1.5.2.5 | ScalarupsSmartConfigAlarmTimer | read-write | mandatory | The time in seconds after initial line failure at which the UPS begins emitting audible alarms (beeping). This timer is observerd only if the value of extContr… |
| 1.3.6.1.4.1.935.1.1.1.5.2.6 | ScalarupsSmartConfigMinReturnCapacity | read-write | mandatory | The minimum battery capacity as a percent of full capacity required before the UPS will return from a low battery shutdown condition. In other words, the UPS w… |
| 1.3.6.1.4.1.935.1.1.1.5.2.7 | ScalarupsSmartConfigSensitivity | read-write | mandatory | The sensitivity of the UPS to utility line abnormalities or noises. |
| 1.3.6.1.4.1.935.1.1.1.5.2.8 | ScalarupsSmartConfigLowBatteryRunTime | read-write | mandatory | The desired run time in seconds once the low battery condition is reached. Allowed values are 120, 300, 420, or 600 seconds. During this time the UPS will prod… |
| 1.3.6.1.4.1.935.1.1.1.5.2.9 | ScalarupsSmartConfigReturnDelay | read-write | mandatory | The delay in seconds after utility line power returns before the UPS will turn on. This value is also used when the UPS comes out of a reboot and before the UP… |
| 1.3.6.1.4.1.935.1.1.1.5.2.10 | ScalarupsSmartConfigShutoffDelay | read-write | mandatory | The delay in seconds the UPS remains on after being told to turn off. Allowed values are 12, 18, 24, 30, 36, 42, 48, 54, 60, 120, 180, 240, 300, 360, 420, 480,… |
| 1.3.6.1.4.1.935.1.1.1.5.2.11 | ScalarupsSmartConfigUpsSleepTime | read-write | mandatory | The time in minutes for the UPS to go to 'sleep' when instructed. When in sleep mode, the UPS will not provide output power regardless of the input line state.… |
| 1.3.6.1.4.1.935.1.1.1.5.2.12 | ScalarupsSmartConfigSetEEPROMDefaults | read-write | mandatory | WRITE: Resets the UPS EEPROM variables to default values. READ: returns 0 |
| 1.3.6.1.4.1.935.1.1.1.6 | NodeupsControlp | |||
| 1.3.6.1.4.1.935.1.1.1.6.1 | NodeupsBaseControl | |||
| 1.3.6.1.4.1.935.1.1.1.6.1.1 | ScalarupsBaseControlConserveBattery | read-write | mandatory | Setting this variable to turnUpsOffToConserveBattery(2) causes a UPS on battery to be put into 'sleep' mode immediately. The (10) means suspending time(10 minu… |
| 1.3.6.1.4.1.935.1.1.1.6.2 | NodeupsSmartControl | |||
| 1.3.6.1.4.1.935.1.1.1.6.2.1 | ScalarupsSmartControlUpsOff | read-write | mandatory | Setting this variable to turnUpsOff(2) causes the UPS to shut off. When in this state, the UPS will not provide output power regardless of the input line state… |
| 1.3.6.1.4.1.935.1.1.1.6.2.2 | ScalarupsSmartControlRebootUps | read-write | mandatory | Setting this variable to rebootUps(2) causes the UPS to shut off and turn back on. Setting this value to noRebootUps(1) has no effect. The value noRebootUps(1)… |
| 1.3.6.1.4.1.935.1.1.1.6.2.3 | ScalarupsSmartControlUpsSleep | read-write | mandatory | Setting this variable to putUpsToSleep(2) causes the UPS to go to sleep for the time specified by upsSmartConfigUpsSleepTime. When in sleep mode, the UPS will … |
| 1.3.6.1.4.1.935.1.1.1.6.2.4 | ScalarupsSmartControlSimulatePowerFail | read-write | mandatory | Setting this variable to simulatePowerFailure(2) causes the UPS switch to battery power. Setting this value to noSimulatePowerFailure(1) has no effect. The val… |
| 1.3.6.1.4.1.935.1.1.1.6.2.5 | ScalarupsSmartControlFlashAndBeep | read-write | mandatory | UPS to identify itself by lighting all indicators and beeping. Setting this variable to FlashAndBeep(2) causes the UPS lights all panel indicators and beeps. S… |
| 1.3.6.1.4.1.935.1.1.1.6.2.6 | ScalarupsSmartControlTurnOnUpsLoad | read-write | mandatory | Setting this variable to upsSmartControlTurnOnUpsLoad(2) causes the UPS switch back to utility power if utility power is present. Setting this value to noUpsSm… |
| 1.3.6.1.4.1.935.1.1.1.7 | NodeupsTestp | |||
| 1.3.6.1.4.1.935.1.1.1.7.1 | NodeupsBaseTest | |||
| 1.3.6.1.4.1.935.1.1.1.7.2 | NodeupsSmartTest | |||
| 1.3.6.1.4.1.935.1.1.1.7.2.1 | ScalarupsSmartTestDiagnosticSchedule | read-write | mandatory | The UPS system's automatic battery test schedule. |
| 1.3.6.1.4.1.935.1.1.1.7.2.2 | ScalarupsSmartTestDiagnostics | read-write | mandatory | Setting this variable to testDiagnostics(2) causes the UPS to perform a diagnostic self test. Setting this value to noTestDiagnostics(1) has no effect. The val… |
| 1.3.6.1.4.1.935.1.1.1.7.2.3 | ScalarupsSmartTestDiagnosticsResults | read-only | mandatory | The results of the last UPS diagnostics test performed. |
| 1.3.6.1.4.1.935.1.1.1.7.2.4 | ScalarupsSmartTestLastDiagnosticsDate | read-only | mandatory | The date the last UPS diagnostics test was performed in mm/dd/yy format. |
| 1.3.6.1.4.1.935.1.1.1.7.2.5 | ScalarupsSmartTestIndicators | read-write | mandatory | Setting this variable to testIndicators(2) causes the UPS to perform a front panel indicator (lights) test. Setting this value to noTestIndicators(1) has no ef… |
| 1.3.6.1.4.1.935.1.1.1.7.2.6 | ScalarupsSmartTestRuntimeCalibration | read-write | mandatory | Setting this variable to performCalibration(2) causes the UPS to discharge to calibrate the UPS. The test will only start if the battery capacity is 100 percen… |
| 1.3.6.1.4.1.935.1.1.1.7.2.7 | ScalarupsSmartTestCalibrationResults | read-only | mandatory | The results of the last runtime calibration. Value ok(1) means a successful runtime calibration. Value invalidTest(2) indicates last calibration did not take p… |
| 1.3.6.1.4.1.935.1.1.1.7.2.8 | ScalarupsSmartTestCalibrationDate | read-only | mandatory | The date the last UPS runtime calibration was performed in mm/dd/yy format. |
| 1.3.6.1.4.1.935.1.1.1.8 | NodeupsThreePhase | |||
| 1.3.6.1.4.1.935.1.1.1.8.1 | NodeupsThreePhaseBatteryGrp | |||
| 1.3.6.1.4.1.935.1.1.1.8.1.1 | ScalarupsThreePhaseBatteryVoltage | read-only | mandatory | Battery Voltage |
| 1.3.6.1.4.1.935.1.1.1.8.1.2 | ScalarupsThreePhaseBatteryCapacityPercentage | read-only | mandatory | Battery Capacity Percentage |
| 1.3.6.1.4.1.935.1.1.1.8.1.3 | ScalarupsThreePhaseBatteryTimeRemain | read-only | mandatory | Battery Time Remain (unit is Minute) |
| 1.3.6.1.4.1.935.1.1.1.8.1.4 | ScalarupsThreePhaseBatteryCurrent | read-only | mandatory | Battery Electric Current |
| 1.3.6.1.4.1.935.1.1.1.8.1.5 | ScalarupsThreePhaseBatteryTemperature | read-only | mandatory | Battery Temperature |
| 1.3.6.1.4.1.935.1.1.1.8.2 | NodeupsThreePhaseInputGrp | |||
| 1.3.6.1.4.1.935.1.1.1.8.2.1 | ScalarupsThreePhaseInputFrequency | read-only | mandatory | Input Frequency |
| 1.3.6.1.4.1.935.1.1.1.8.2.2 | ScalarupsThreePhaseInputVoltageR | read-only | mandatory | Input VoltageR |
| 1.3.6.1.4.1.935.1.1.1.8.2.3 | ScalarupsThreePhaseInputVoltageS | read-only | mandatory | Input VoltageS |
| 1.3.6.1.4.1.935.1.1.1.8.2.4 | ScalarupsThreePhaseInputVoltageT | read-only | mandatory | Input VoltageT |
| 1.3.6.1.4.1.935.1.1.1.8.3 | NodeupsThreePhaseOutputGrp | |||
| 1.3.6.1.4.1.935.1.1.1.8.3.1 | ScalarupsThreePhaseOutputFrequency | read-only | mandatory | Output Frequency |
| 1.3.6.1.4.1.935.1.1.1.8.3.2 | ScalarupsThreePhaseOutputVoltageR | read-only | mandatory | Output VoltageR |
| 1.3.6.1.4.1.935.1.1.1.8.3.3 | ScalarupsThreePhaseOutputVoltageS | read-only | mandatory | Output VoltageS |
| 1.3.6.1.4.1.935.1.1.1.8.3.4 | ScalarupsThreePhaseOutputVoltageT | read-only | mandatory | Output VoltageT |
| 1.3.6.1.4.1.935.1.1.1.8.3.5 | ScalarupsThreePhaseOutputLoadPercentageR | read-only | mandatory | Load PercentageR |
| 1.3.6.1.4.1.935.1.1.1.8.3.6 | ScalarupsThreePhaseOutputLoadPercentageS | read-only | mandatory | Load PercentageS |
| 1.3.6.1.4.1.935.1.1.1.8.3.7 | ScalarupsThreePhaseOutputLoadPercentageT | read-only | mandatory | Load PercentageT |
| 1.3.6.1.4.1.935.1.1.1.8.4 | NodeupsThreePhaseBypassGrp | |||
| 1.3.6.1.4.1.935.1.1.1.8.4.1 | ScalarupsThreePhaseBypassSourceFrequency | read-only | mandatory | Bypass Frequency |
| 1.3.6.1.4.1.935.1.1.1.8.4.2 | ScalarupsThreePhaseBypassSourceVoltageR | read-only | mandatory | Bypass VoltageR |
| 1.3.6.1.4.1.935.1.1.1.8.4.3 | ScalarupsThreePhaseBypassSourceVoltageS | read-only | mandatory | Bypass VoltageS |
| 1.3.6.1.4.1.935.1.1.1.8.4.4 | ScalarupsThreePhaseBypassSourceVoltageT | read-only | mandatory | Bypass VoltageT |
| 1.3.6.1.4.1.935.1.1.1.8.5 | NodeupsThreePhaseDCandRectifierStatusGrp | |||
| 1.3.6.1.4.1.935.1.1.1.8.5.1 | ScalarupsThreePhaseDCandRectifierStatusRecRotError | read-only | mandatory | Rectifier Rotation Error |
| 1.3.6.1.4.1.935.1.1.1.8.5.2 | ScalarupsThreePhaseDCandRectifierStatusLowBatteryShutdown | read-only | mandatory | Low Battery Shutdown |
| 1.3.6.1.4.1.935.1.1.1.8.5.3 | ScalarupsThreePhaseDCandRectifierStatusLowBattery | read-only | mandatory | Low Battery |
| 1.3.6.1.4.1.935.1.1.1.8.5.4 | ScalarupsThreePhaseDCandRectifierStatusInAndOut | read-only | mandatory | In And Put |
| 1.3.6.1.4.1.935.1.1.1.8.5.5 | ScalarupsThreePhaseDCandRectifierStatusBatteryStatus | read-only | mandatory | Back Status |
| 1.3.6.1.4.1.935.1.1.1.8.5.6 | ScalarupsThreePhaseDCandRectifierStatusChargeStatus | read-only | mandatory | Charge Status |
| 1.3.6.1.4.1.935.1.1.1.8.5.7 | ScalarupsThreePhaseDCandRectifierStatusRecOperating | read-only | mandatory | Rectifier Operating |
| 1.3.6.1.4.1.935.1.1.1.8.6 | NodeupsThreePhaseUPSStatusGrp | |||
| 1.3.6.1.4.1.935.1.1.1.8.6.1 | ScalarupsThreePhaseUPSStatusBypassFreqFail | read-only | mandatory | Bypass Status |
| 1.3.6.1.4.1.935.1.1.1.8.6.2 | ScalarupsThreePhaseUPSStatusManualBypassBreaker | read-only | mandatory | Breaker Status |
| 1.3.6.1.4.1.935.1.1.1.8.6.3 | ScalarupsThreePhaseUPSStatusACStatus | read-only | mandatory | AC Status |
| 1.3.6.1.4.1.935.1.1.1.8.6.4 | ScalarupsThreePhaseUPSStaticSwitchMode | read-only | mandatory | Switch Mode |
| 1.3.6.1.4.1.935.1.1.1.8.6.5 | ScalarupsThreePhaseUPSStatusInverterOperating | read-only | mandatory | Operating |
| 1.3.6.1.4.1.935.1.1.1.8.7 | NodeupsThreePhaseFaultStatusGrp | |||
| 1.3.6.1.4.1.935.1.1.1.8.7.1 | ScalarupsThreePhaseFaultStatusEmergencyStop | read-only | mandatory | Emergency Stop |
| 1.3.6.1.4.1.935.1.1.1.8.7.2 | ScalarupsThreePhaseFaultStatusHighDCShutdown | read-only | mandatory | High DC Shutdown |
| 1.3.6.1.4.1.935.1.1.1.8.7.3 | ScalarupsThreePhaseFaultStatusBypassBreaker | read-only | mandatory | Bypass Breaker |
| 1.3.6.1.4.1.935.1.1.1.8.7.4 | ScalarupsThreePhaseFaultStatusOverLoad | read-only | mandatory | Over Load |
| 1.3.6.1.4.1.935.1.1.1.8.7.5 | ScalarupsThreePhaseFaultStatusInverterOutputFail | read-only | mandatory | Output Fail |
| 1.3.6.1.4.1.935.1.1.1.8.7.6 | ScalarupsThreePhaseFaultStatusOverTemperature | read-only | mandatory | Over Temperature |
| 1.3.6.1.4.1.935.1.1.1.8.7.7 | ScalarupsThreePhaseFaultStatusShortCircuit | read-only | mandatory | Short Circuit |
| 1.3.6.1.4.1.935.1.1.1.8.8 | NodeupsThreePhaseRatingGrp | |||
| 1.3.6.1.4.1.935.1.1.1.8.8.1 | ScalarupsThreePhaseRatingRectifierVoltage | read-only | mandatory | Rectifier Voltage |
| 1.3.6.1.4.1.935.1.1.1.8.8.2 | ScalarupsThreePhaseRatingRectifierFrequency | read-only | mandatory | Rectifier Frequency |
| 1.3.6.1.4.1.935.1.1.1.8.8.3 | ScalarupsThreePhaseRatingBypassVoltage | read-only | mandatory | Bypass Voltage |
| 1.3.6.1.4.1.935.1.1.1.8.8.4 | ScalarupsThreePhaseRatingBypassFrequency | read-only | mandatory | Bypass Frequency |
| 1.3.6.1.4.1.935.1.1.1.8.8.5 | ScalarupsThreePhaseRatingOutputVoltage | read-only | mandatory | Output Voltage |
| 1.3.6.1.4.1.935.1.1.1.8.8.6 | ScalarupsThreePhaseRatingOutputFrequency | read-only | mandatory | Output Frequency |
| 1.3.6.1.4.1.935.1.1.1.8.8.7 | ScalarupsThreePhaseRatingBatteryVoltage | read-only | mandatory | Battery Voltage |
| 1.3.6.1.4.1.935.1.1.1.8.8.8 | ScalarupsThreePhaseRatingPower | read-only | mandatory | Power Rating |
| 1.3.6.1.4.1.935.1.1.1.9 | NodeupsEnvironment | |||
| 1.3.6.1.4.1.935.1.1.1.9.1 | NodeupsEnvStatus | |||
| 1.3.6.1.4.1.935.1.1.1.9.1.1 | ScalarupsEnvTemperature | read-only | mandatory | The ambient environment temperature. |
| 1.3.6.1.4.1.935.1.1.1.9.1.2 | ScalarupsEnvHumidity | read-only | mandatory | The environment humidity. |
| 1.3.6.1.4.1.935.1.1.1.9.1.3 | ScalarupsEnvWater | read-only | mandatory | Water status |
| 1.3.6.1.4.1.935.1.1.1.9.1.4 | ScalarupsEnvSmoke | read-only | mandatory | Smoke status |
| 1.3.6.1.4.1.935.1.1.1.9.1.5 | ScalarupsEnvSecurity1 | read-only | mandatory | Security status |
| 1.3.6.1.4.1.935.1.1.1.9.1.6 | ScalarupsEnvSecurity2 | read-only | mandatory | Security status |
| 1.3.6.1.4.1.935.1.1.1.9.1.7 | ScalarupsEnvSecurity3 | read-only | mandatory | Security status |
| 1.3.6.1.4.1.935.1.1.1.9.1.8 | ScalarupsEnvSecurity4 | read-only | mandatory | Security status |
| 1.3.6.1.4.1.935.1.1.1.9.1.9 | ScalarupsEnvSecurity5 | read-only | mandatory | Security status |
| 1.3.6.1.4.1.935.1.1.1.9.1.10 | ScalarupsEnvSecurity6 | read-only | mandatory | Security status |
| 1.3.6.1.4.1.935.1.1.1.9.1.11 | ScalarupsEnvSecurity7 | read-only | mandatory | Security status |
| 1.3.6.1.4.1.935.1.1.1.9.2 | NodeupsEnvSetting | |||
| 1.3.6.1.4.1.935.1.1.1.9.2.1 | ScalarupsEnvOverTemperature | read-write | mandatory | Alarm dupsAlarmOverTemperature on when the environment temperature over the value. |
| 1.3.6.1.4.1.935.1.1.1.9.2.2 | ScalarupsEnvUnderTemperature | read-write | mandatory | Alarm dupsAlarmUnderTemperature on when the environment temperature below the value. |
| 1.3.6.1.4.1.935.1.1.1.9.2.3 | ScalarupsEnvOverHumidity | read-write | mandatory | Alarm dupsAlarmOverHumidity on when the environment humidity over the value. |
| 1.3.6.1.4.1.935.1.1.1.9.2.4 | ScalarupsEnvUnderHumidity | read-write | mandatory | Alarm dupsAlarmUnderHumidity on when the environment humidity below the value. |
| 1.3.6.1.4.1.935.2 | Nodeppcmgmt | |||
| 1.3.6.1.4.1.935.2 | NodeupsOverLoad | SEVERE: The UPS has sensed a load greater than 100 percent of its rated capacity. | ||
| 1.3.6.1.4.1.935.2.1 | Nodemconfig | |||
| 1.3.6.1.4.1.935.2.1.1 | ScalarmconfigTrapsReceiversNum | read-only | mandatory | The number of managers to send traps to. |
| 1.3.6.1.4.1.935.2.1.2 | TablemconfigTrapsReceiversTable | not-accessible | mandatory | A list of managers to send traps to. The number of entries is given by the value of mconfigNumTrapReceivers |
| 1.3.6.1.4.1.935.2.1.2.1 | RowmconfigTrapsReceiversEntry | not-accessible | mandatory | The managers to send traps to. |
| 1.3.6.1.4.1.935.2.1.2.1.1 | ColumntrapsIndex | read-only | mandatory | The index to a trap receiver entry. |
| 1.3.6.1.4.1.935.2.1.2.1.2 | ColumntrapsReceiverAddr | read-write | mandatory | The IP address of the manager to send a trap to. |
| 1.3.6.1.4.1.935.2.1.2.1.3 | ColumnreceiverCommunityString | read-write | mandatory | The community name to use in the trap when sent to the manager. |
| 1.3.6.1.4.1.935.2.1.2.1.4 | ColumnseverityLevel | read-write | mandatory | The severity threshold of traps to send to the manager. traps are labeled in severity as informational(1), warning(2), severe(3). Only traps of equal or greate… |
| 1.3.6.1.4.1.935.2.1.2.1.5 | ColumnreceiverAccept | read-write | mandatory | An entry will become active if yes, and will be deleted if no. |
| 1.3.6.1.4.1.935.3 | NodeupsDiagnosticsFailed | SEVERE: The UPS failed its internal diagnostic self-test. | ||
| 1.3.6.1.4.1.935.4 | NodeupsDischarged | SEVERE: The UPS just started a runtime calibration discharge. The UPS batteries are being discharged. | ||
| 1.3.6.1.4.1.935.5 | NodeupsOnBattery | WARNING: The UPS has switched to battery backup power. | ||
| 1.3.6.1.4.1.935.6 | NodeboostOn | WARNING: The UPS has enabled Boost. | ||
| 1.3.6.1.4.1.935.7 | NodelowBattery | SEVERE: The UPS batteries are low and will soon be exhausted. If utility power is not restored the UPS will put itself to 'sleep' and immediately cut power to … | ||
| 1.3.6.1.4.1.935.8 | NodecommunicationEstablished | INFORMATION: Communication with the UPS has been established. | ||
| 1.3.6.1.4.1.935.9 | NodepowerRestored | INFORMATION: Utility power has been restored. | ||
| 1.3.6.1.4.1.935.10 | NodeupsDiagnosticsPassed | INFORMATION: The UPS passed its internal self-test. | ||
| 1.3.6.1.4.1.935.11 | NodereturnFromLowBattery | INFORMATION: The UPS has returned from a low battery condition. | ||
| 1.3.6.1.4.1.935.12 | NodeupsTurnedOff | WARNING: The UPS has been turned 'off' by the management station. | ||
| 1.3.6.1.4.1.935.13 | NodeupsSleeping | WARNING: The UPS is entering 'sleep' mode. Power to the load will be cut off. | ||
| 1.3.6.1.4.1.935.14 | NodeupsWokeUp | INFORMATION: The UPS woke up from 'sleep' mode. Power to the load has been restored. | ||
| 1.3.6.1.4.1.935.15 | NodeupsRebootStarted | WARNING: The UPS has started its reboot sequence. After the specified delay the UPS will perform a reboot. | ||
| 1.3.6.1.4.1.935.16 | NodeenvOverTemperature | WARNING: The environment temperature exceed the normal value. | ||
| 1.3.6.1.4.1.935.17 | NodeenvTemperatureNormal | INFORMATION: The environment temperature is normal. | ||
| 1.3.6.1.4.1.935.18 | NodeenvOverHumidity | WARNING: The environment humidity exceed the normal value. | ||
| 1.3.6.1.4.1.935.19 | NodeenvHumidityNormal | INFORMATION: The environment humidity is normal. | ||
| 1.3.6.1.4.1.935.20 | NodeenvSmokeAbnormal | WARNING: Smoke is abnormal. | ||
| 1.3.6.1.4.1.935.21 | NodeenvWaterAbnormal | WARNING: Water is abnormal. | ||
| 1.3.6.1.4.1.935.22 | NodeenvSecurityAbnormal | WARNING: Security is abnormal. | ||
| 1.3.6.1.4.1.935.24 | NodeenvWaterNormal | INFORMATION: Water is normal. | ||
| 1.3.6.1.4.1.935.26 | NodeenvGasAbnormal | WARNING: Gas Alarm | ||
| 1.3.6.1.4.1.935.27 | NodeupsTemp | WARNING: UPS Temperature Overrun | ||
| 1.3.6.1.4.1.935.28 | NodeupsLoadNormal | WARNING: UPS Load Normal | ||
| 1.3.6.1.4.1.935.29 | NodeupsTempNormal | WARNING: UPS temperature Normal | ||
| 1.3.6.1.4.1.935.30 | NodeenvUnderTemperature | WARNING: The environment temperature below the normal value. | ||
| 1.3.6.1.4.1.935.31 | NodeenvUnderHumidity | WARNING: The environment humidity below the normal value. | ||
| 1.3.6.1.4.1.935.32 | NodeupsBypass | WARNING: The UPS is entering 'bypass' mode. | ||
| 1.3.6.1.4.1.935.33 | NodeenvSecurity1 | WARNING: Security1 Alarm. | ||
| 1.3.6.1.4.1.935.34 | NodeenvSecurity2 | WARNING: Security2 Alarm. | ||
| 1.3.6.1.4.1.935.35 | NodeenvSecurity3 | WARNING: Security3 Alarm. | ||
| 1.3.6.1.4.1.935.36 | NodeenvSecurity4 | WARNING: Security4 Alarm. | ||
| 1.3.6.1.4.1.935.37 | NodeenvSecurity5 | WARNING: Security5 Alarm. | ||
| 1.3.6.1.4.1.935.38 | NodeenvSecurity6 | WARNING: Security6 Alarm. | ||
| 1.3.6.1.4.1.935.39 | NodeenvSecurity7 | WARNING: Security7 Alarm. | ||
| 1.3.6.1.4.1.935.47 | NodeupsRecroterror | WARNING: Rectifier Rotation Error | ||
| 1.3.6.1.4.1.935.48 | NodeupsBypassFreFail | WARNING: Bypass Frequency Fail | ||
| 1.3.6.1.4.1.935.49 | NodeupsBypassacnormal | WARNING: Bypass AC Normal | ||
| 1.3.6.1.4.1.935.50 | NodeupsBypassacabnormal | WARNING: Bypass AC Abnormal | ||
| 1.3.6.1.4.1.935.51 | NodeupsTest | WARNING: UPS Test | ||
| 1.3.6.1.4.1.935.52 | NodeupsScheduleShutdown | WARNING: UPS Schedule Shutdown | ||
| 1.3.6.1.4.1.935.53 | NodeupsBypassReturn | The UPS return from Bypass Mode | ||
| 1.3.6.1.4.1.935.54 | NodeupsShortCircuitShutdown | The UPS Short Circuit Shutdown | ||
| 1.3.6.1.4.1.935.55 | NodeupsInverterOutputFailShutdown | The UPS Inverter Output Fail Shutdown | ||
| 1.3.6.1.4.1.935.56 | NodeupsBypassBreadkerOnShutdown | The UPS Manual Bypass Breaker on Shutdown | ||
| 1.3.6.1.4.1.935.57 | NodeupsHighDCShutdown | The UPS High DC Shutdown | ||
| 1.3.6.1.4.1.935.58 | NodeupsEmergencyStop | The UPS Emergency Stop | ||
| 1.3.6.1.4.1.935.59 | NodeupsInverterMode | The UPS Static Switch in Inverter Mode | ||
| 1.3.6.1.4.1.935.60 | NodeupsBypassMode | The UPS Static Switch in Bypass Mode | ||
| 1.3.6.1.4.1.935.61 | NodeupsOverTemperatureShutdown | The UPS Over Temperature Shutdown | ||
| 1.3.6.1.4.1.935.62 | NodeupsOverLoadShutdown | The UPS Overload Shutdown | ||
| 1.3.6.1.4.1.935.63 | NodeupsCapacityUnderrun | The UPS Capacity Underrun | ||
| 1.3.6.1.4.1.935.64 | NodeupsCapacityNormal | The UPS Capacity Normal | ||
| 1.3.6.1.4.1.935.67 | NodeupsLowBatteryShutdown | The UPS Low Battery Shutdown | ||
| 1.3.6.1.4.1.935.68 | NodebuckOn | WARNING: The UPS has enabled Buck. | ||
| 1.3.6.1.4.1.935.69 | NodereturnFromBuck | WARNING: The UPS has return from Buck. | ||
| 1.3.6.1.4.1.935.70 | NodereturnFromBoost | WARNING: The UPS has return from Boost. |