MIB Viewer

XUPS-MIB

220 objects
No module-level DESCRIPTION found.
OIDNameAccessStatusDescription
1.3.6.1.4.1.534Nodepowerware
1.3.6.1.4.1.534.1Nodexups
1.3.6.1.4.1.534.1.1NodexupsIdent
1.3.6.1.4.1.534.1.1.1ScalarxupsIdentManufacturerread-onlymandatoryThe UPS Manufacturer Name (e.g. Powerware Corporation).
1.3.6.1.4.1.534.1.1.2ScalarxupsIdentModelread-onlymandatoryThe UPS Model (e.g. Powerware Plus Model 18).
1.3.6.1.4.1.534.1.1.3ScalarxupsIdentSoftwareVersionread-onlymandatoryThe firmware revision level(s) of the UPS microcontroller(s).
1.3.6.1.4.1.534.1.1.4ScalarxupsIdentOemCoderead-onlymandatoryA binary code indicating who the UPS was manufactured or labeled for. 0 or 255 indicates Powerware itself.
1.3.6.1.4.1.534.1.2NodexupsBattery
1.3.6.1.4.1.534.1.2.1ScalarxupsBatTimeRemainingread-onlymandatoryBattery run time in seconds before UPS turns off due to low battery.
1.3.6.1.4.1.534.1.2.2ScalarxupsBatVoltageread-onlymandatoryBattery voltage as reported by the UPS meters.
1.3.6.1.4.1.534.1.2.3ScalarxupsBatCurrentread-onlymandatoryBattery Current as reported by the UPS metering. Current is positive when discharging, negative when recharging the battery.
1.3.6.1.4.1.534.1.2.4ScalarxupsBatCapacityread-onlymandatoryBattery percent charge.
1.3.6.1.4.1.534.1.2.5ScalarxupsBatteryAbmStatusread-onlymandatoryGives the status of the Advanced Battery Management; batteryFloating(3) status means that the charger is temporarily charging the battery to its float voltage;…
1.3.6.1.4.1.534.1.2.6ScalarxupsBatteryLastReplacedDateread-writemandatoryThe date when the Batteries in this UPS were last replaced. Should be the same as xupsConfigInstallDate initially. Free text format, so the preferred local dat…
1.3.6.1.4.1.534.1.3NodexupsInput
1.3.6.1.4.1.534.1.3.1ScalarxupsInputFrequencyread-onlymandatoryThe utility line frequency in tenths of Hz.
1.3.6.1.4.1.534.1.3.2ScalarxupsInputLineBadsread-onlymandatoryThe number of times the Input was out of tolerance in voltage or frequency.
1.3.6.1.4.1.534.1.3.3ScalarxupsInputNumPhasesread-onlymandatory
1.3.6.1.4.1.534.1.3.4TablexupsInputTablenot-accessiblemandatoryThe Aggregate Object with number of entries equal to NumPhases and including the xupsInput group.
1.3.6.1.4.1.534.1.3.4.1RowxupsInputEntrynot-accessiblemandatoryThe input table entry containing the current, voltage, etc.
1.3.6.1.4.1.534.1.3.4.1.1ColumnxupsInputPhaseread-onlymandatoryThe number of the phase. Serves as index for input table.
1.3.6.1.4.1.534.1.3.4.1.2ColumnxupsInputVoltageread-onlymandatoryThe measured input voltage from the UPS meters in volts.
1.3.6.1.4.1.534.1.3.4.1.3ColumnxupsInputCurrentread-onlymandatoryThe measured input current from the UPS meters in amps.
1.3.6.1.4.1.534.1.3.4.1.4ColumnxupsInputWattsread-onlymandatoryThe measured input real power in watts.
1.3.6.1.4.1.534.1.3.5ScalarxupsInputSourceread-onlymandatoryThe present external source of input power. The enumeration none(2) indicates that there is no external source of power, for example, the UPS is On Battery (an…
1.3.6.1.4.1.534.1.3.6ScalarxupsDualInputStatusread-onlymandatoryThe present status of the sources of input power in a dual source UPS. The enumeration primarySourceGood(2) indicates that the primary source of power is prese…
1.3.6.1.4.1.534.1.3.7ScalarxupsSecondaryInputWatchread-writemandatoryThis object enables(2) or disables(1) the alarms and traps related to the availability and use of the secondary input of a dual-input UPS (i.e., OnAlternatePow…
1.3.6.1.4.1.534.1.4NodexupsOutput
1.3.6.1.4.1.534.1.4.1ScalarxupsOutputLoadread-onlymandatoryThe UPS output load in percent of rated capacity.
1.3.6.1.4.1.534.1.4.2ScalarxupsOutputFrequencyread-onlymandatoryThe measured UPS output frequency in tenths of Hz.
1.3.6.1.4.1.534.1.4.3ScalarxupsOutputNumPhasesread-onlymandatoryThe number of metered output phases, serves as the table index.
1.3.6.1.4.1.534.1.4.4TablexupsOutputTablenot-accessiblemandatoryThe Aggregate Object with number of entries equal to NumPhases and including the xupsOutput group.
1.3.6.1.4.1.534.1.4.4.1RowxupsOutputEntrynot-accessiblemandatoryOutput Table Entry containing voltage, current, etc.
1.3.6.1.4.1.534.1.4.4.1.1ColumnxupsOutputPhaseread-onlymandatoryThe number {1..3} of the output phase.
1.3.6.1.4.1.534.1.4.4.1.2ColumnxupsOutputVoltageread-onlymandatoryThe measured output voltage from the UPS metering in volts.
1.3.6.1.4.1.534.1.4.4.1.3ColumnxupsOutputCurrentread-onlymandatoryThe measured UPS output current in amps.
1.3.6.1.4.1.534.1.4.4.1.4ColumnxupsOutputWattsread-onlymandatoryThe measured real output power in watts.
1.3.6.1.4.1.534.1.4.5ScalarxupsOutputSourceread-onlymandatoryThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.534.1.5NodexupsBypass
1.3.6.1.4.1.534.1.5.1ScalarxupsBypassFrequencyread-onlymandatoryThe bypass frequency in tenths of Hz.
1.3.6.1.4.1.534.1.5.2ScalarxupsBypassNumPhasesread-onlymandatoryThe number of lines in the UPS bypass table.
1.3.6.1.4.1.534.1.5.3TablexupsBypassTablenot-accessiblemandatory
1.3.6.1.4.1.534.1.5.3.1RowxupsBypassEntrynot-accessiblemandatoryEntry in the XUPS bypass table.
1.3.6.1.4.1.534.1.5.3.1.1ColumnxupsBypassPhaseread-onlymandatoryThe Bypass Phase, index for the table.
1.3.6.1.4.1.534.1.5.3.1.2ColumnxupsBypassVoltageread-onlymandatoryThe measured UPS bypass voltage in volts.
1.3.6.1.4.1.534.1.6NodexupsEnvironment
1.3.6.1.4.1.534.1.6.1ScalarxupsEnvAmbientTempread-onlymandatoryThe reading of the ambient temperature in the vicinity of the UPS or SNMP agent.
1.3.6.1.4.1.534.1.6.2ScalarxupsEnvAmbientLowerLimitread-writemandatoryThe Lower Limit of the ambient temperature; if xupsEnvAmbientTemp falls below this value, the xupsAmbientTempBad alarm will occur.
1.3.6.1.4.1.534.1.6.3ScalarxupsEnvAmbientUpperLimitread-writemandatoryThe Upper Limit of the ambient temperature; if xupsEnvAmbientTemp rises above this value, the xupsAmbientTempBad alarm will occur. This value should be greater…
1.3.6.1.4.1.534.1.6.4ScalarxupsEnvAmbientHumidityread-onlymandatoryThe reading of the ambient humidity in the vicinity of the UPS or SNMP agent.
1.3.6.1.4.1.534.1.6.5ScalarxupsEnvRemoteTempread-onlymandatoryThe reading of a remote temperature sensor connected to the UPS or SNMP agent.
1.3.6.1.4.1.534.1.6.6ScalarxupsEnvRemoteHumidityread-onlymandatoryThe reading of a remote humidity sensor connected to the UPS or SNMP agent.
1.3.6.1.4.1.534.1.6.7ScalarxupsEnvNumContactsread-onlymandatoryThe number of Contacts in the xupsContactSenseTable. This object indicates the number of rows in the xupsContactSenseTable.
1.3.6.1.4.1.534.1.6.8TablexupsContactSenseTablenot-accessiblemandatoryA list of Contact Sensing table entries. The number of entries is given by the value of xupsEnvNumContacts.
1.3.6.1.4.1.534.1.6.8.1RowxupsContactsTableEntrynot-accessiblemandatoryAn entry containing information applicable to a particular Contact input.
1.3.6.1.4.1.534.1.6.8.1.1ColumnxupsContactIndexread-onlymandatoryThe Contact identifier; identical to the Contact Number. This object is not-accessible to MIB browsers, but had to be changed to read-only to satisfy SMIv2 syn…
1.3.6.1.4.1.534.1.6.8.1.2ColumnxupsContactTyperead-writemandatoryThe normal state for this contact. The 'other' state is the Active state for generating the xupstdContactActiveNotice trap. If anyChange(3) is selected, then t…
1.3.6.1.4.1.534.1.6.8.1.3ColumnxupsContactStateread-onlymandatoryThe current state of the Contact input; the value is based on the open/closed input state and the setting for xupsContactType. When entering the openWithNotice…
1.3.6.1.4.1.534.1.6.8.1.4ColumnxupsContactDescrread-writemandatoryA label identifying the Contact. This object should be set by the administrator.
1.3.6.1.4.1.534.1.6.9ScalarxupsEnvRemoteTempLowerLimitread-writemandatoryThe Lower Limit of the remote temperature; if xupsEnvRemoteTemp falls below this value, the xupsRemoteTempBad alarm will occur.
1.3.6.1.4.1.534.1.6.10ScalarxupsEnvRemoteTempUpperLimitread-writemandatoryThe Upper Limit of the remote temperature; if xupsEnvRemoteTemp rises above this value, the xupsRemoteTempBad alarm will occur. This value should be greater th…
1.3.6.1.4.1.534.1.6.11ScalarxupsEnvRemoteHumidityLowerLimitread-writemandatoryThe Lower Limit of the remote humidity reading; if xupsEnvRemoteHumidity falls below this value, the xupsRemoteHumidityBad alarm will occur.
1.3.6.1.4.1.534.1.6.12ScalarxupsEnvRemoteHumidityUpperLimitread-writemandatoryThe Upper Limit of the remote humidity reading; if xupsEnvRemoteHumidity rises above this value, the xupsRemoteHumidityBad alarm will occur. This value should …
1.3.6.1.4.1.534.1.7NodexupsAlarm
1.3.6.1.4.1.534.1.7.1ScalarxupsAlarmsread-onlymandatoryThe current number of alarm conditions.
1.3.6.1.4.1.534.1.7.2TablexupsAlarmTablenot-accessiblemandatory
1.3.6.1.4.1.534.1.7.2.1RowxupsAlarmEntrynot-accessiblemandatory
1.3.6.1.4.1.534.1.7.2.1.1ColumnxupsAlarmIDread-onlymandatoryA unique identifier for an alarm condition.
1.3.6.1.4.1.534.1.7.2.1.2ColumnxupsAlarmDescrread-onlymandatoryA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.534.1.7.2.1.3ColumnxupsAlarmTimeread-onlymandatoryThe value of the MIB-II variable sysUpTime when the alarm condition occurred.
1.3.6.1.4.1.534.1.7.3NodexupsOnBattery
1.3.6.1.4.1.534.1.7.4NodexupsLowBattery
1.3.6.1.4.1.534.1.7.5NodexupsUtilityPowerRestored
1.3.6.1.4.1.534.1.7.6NodexupsReturnFromLowBattery
1.3.6.1.4.1.534.1.7.7NodexupsOutputOverload
1.3.6.1.4.1.534.1.7.8NodexupsInternalFailure
1.3.6.1.4.1.534.1.7.9NodexupsBatteryDischarged
1.3.6.1.4.1.534.1.7.10NodexupsInverterFailure
1.3.6.1.4.1.534.1.7.11NodexupsOnBypass
1.3.6.1.4.1.534.1.7.12NodexupsBypassNotAvailable
1.3.6.1.4.1.534.1.7.13NodexupsOutputOff
1.3.6.1.4.1.534.1.7.14NodexupsInputFailure
1.3.6.1.4.1.534.1.7.15NodexupsBuildingAlarm
1.3.6.1.4.1.534.1.7.16NodexupsShutdownImminent
1.3.6.1.4.1.534.1.7.17NodexupsOnInverter
1.3.6.1.4.1.534.1.7.18ScalarxupsAlarmNumEventsread-onlymandatoryThe number of entries in the UPS event history queue.
1.3.6.1.4.1.534.1.7.19TablexupsAlarmEventTablenot-accessiblemandatoryA table of the UPS internal event history queue.
1.3.6.1.4.1.534.1.7.19.1RowxupsAlarmEventEntrynot-accessiblemandatoryOne of the entries in the UPS event history queue.
1.3.6.1.4.1.534.1.7.19.1.1ColumnxupsAlarmEventIDnot-accessiblemandatoryA unique number that reflects the order in which the event occurred. The oldest event in the queue will be number 1. Subsequent events will be numbered 2, 3, 4…
1.3.6.1.4.1.534.1.7.19.1.2ColumnxupsAlarmEventDateAndTimeread-onlydeprecatedThe time and date that an event occurred as recorded in the UPS internal event queue. This string will reflect the time and date as set in the UPS itself and w…
1.3.6.1.4.1.534.1.7.19.1.3ColumnxupsAlarmEventKindread-onlydeprecatedEnumerated value that tells whether the event is an occurrence of an alarm condition or a clearing of an alarm condition.
1.3.6.1.4.1.534.1.7.19.1.4ColumnxupsAlarmEventDescrread-onlydeprecatedA description of the event stored in the UPS event queue. This description will be a sixteen bit integer value representing one of the defined alarms in the Po…
1.3.6.1.4.1.534.1.7.19.1.5ColumnxupsAlarmEventMsgread-onlymandatoryA text string describing each entry in the Event Log. The format of this text message is free (not fixed) for the operator to read; good contents would be a ti…
1.3.6.1.4.1.534.1.7.20NodexupsBreakerOpen
1.3.6.1.4.1.534.1.7.21NodexupsAlarmEntryAdded
1.3.6.1.4.1.534.1.7.22NodexupsAlarmEntryRemoved
1.3.6.1.4.1.534.1.7.23NodexupsAlarmBatteryBad
1.3.6.1.4.1.534.1.7.24NodexupsOutputOffAsRequested
1.3.6.1.4.1.534.1.7.25NodexupsDiagnosticTestFailed
1.3.6.1.4.1.534.1.7.26NodexupsCommunicationsLost
1.3.6.1.4.1.534.1.7.27NodexupsUpsShutdownPending
1.3.6.1.4.1.534.1.7.28NodexupsAlarmTestInProgress
1.3.6.1.4.1.534.1.7.29NodexupsAmbientTempBad
1.3.6.1.4.1.534.1.7.30NodexupsLossOfRedundancy
1.3.6.1.4.1.534.1.7.31NodexupsAlarmTempBad
1.3.6.1.4.1.534.1.7.32NodexupsAlarmChargerFailed
1.3.6.1.4.1.534.1.7.33NodexupsAlarmFanFailure
1.3.6.1.4.1.534.1.7.34NodexupsAlarmFuseFailure
1.3.6.1.4.1.534.1.7.35NodexupsPowerSwitchBad
1.3.6.1.4.1.534.1.7.36NodexupsModuleFailure
1.3.6.1.4.1.534.1.7.37NodexupsOnAlternatePowerSource
1.3.6.1.4.1.534.1.7.38NodexupsAltPowerNotAvailable
1.3.6.1.4.1.534.1.7.39NodexupsNoticeCondition
1.3.6.1.4.1.534.1.7.40NodexupsRemoteTempBad
1.3.6.1.4.1.534.1.7.41NodexupsRemoteHumidityBad
1.3.6.1.4.1.534.1.7.42NodexupsAlarmOutputBad
1.3.6.1.4.1.534.1.7.43NodexupsAlarmAwaitingPower
1.3.6.1.4.1.534.1.7.44NodexupsOnMaintenanceBypass
1.3.6.1.4.1.534.1.8NodexupsTest
1.3.6.1.4.1.534.1.8.1ScalarxupsTestStartread-writemandatorySetting this object initiates the requested Test. If a UPS does not support the requested test, the set operation may succeed but the result will end up as not…
1.3.6.1.4.1.534.1.8.2ScalarxupsTestBatteryStatusread-onlymandatoryReading this enumerated value gives an indication of the (last) UPS Battery test status.
1.3.6.1.4.1.534.1.8.3ScalarxupsLastGeneralTestread-onlymandatoryIndicates the last UPS test requested via xupsTestStart or by other non-SNMP means, other than for the testBattery (1) case. The results of the test indicated …
1.3.6.1.4.1.534.1.8.4ScalarxupsLastGeneralTestResultread-onlymandatoryReading this enumerated value gives the result of the test indicated in xupsLastGeneralTest.
1.3.6.1.4.1.534.1.9NodexupsControl
1.3.6.1.4.1.534.1.9.1ScalarxupsControlOutputOffDelayread-writemandatorySetting this value to other than zero will cause the UPS output to turn off after the number of seconds. Setting it to 0 will cause an attempt to abort a pendi…
1.3.6.1.4.1.534.1.9.2ScalarxupsControlOutputOnDelayread-writemandatorySetting this value to other than zero will cause the UPS output to turn on after the number of seconds. Setting it to 0 will cause an attempt to abort a pendin…
1.3.6.1.4.1.534.1.9.3ScalarxupsControlOutputOffTrapDelayread-writemandatoryWhen xupsControlOutputOffDelay reaches this value, a trap will be sent.
1.3.6.1.4.1.534.1.9.4ScalarxupsControlOutputOnTrapDelayread-writedeprecatedWhen xupsControlOutputOnDelay reaches this value, a xupsOutputOff trap will be sent.
1.3.6.1.4.1.534.1.9.5ScalarxupsControlToBypassDelayread-writemandatorySetting this value to other than zero will cause the UPS output to go to Bypass after the number of seconds. If the Bypass is unavailable, this may cause the U…
1.3.6.1.4.1.534.1.9.6ScalarxupsLoadShedSecsWithRestartread-writemandatorySetting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is ag…
1.3.6.1.4.1.534.1.10NodexupsConfig
1.3.6.1.4.1.534.1.10.1ScalarxupsConfigOutputVoltageread-onlymandatoryThe nominal UPS Output voltage per phase in volts.
1.3.6.1.4.1.534.1.10.2ScalarxupsConfigInputVoltageread-onlymandatoryThe nominal UPS Input voltage per phase in volts.
1.3.6.1.4.1.534.1.10.3ScalarxupsConfigOutputWattsread-onlymandatoryThe nominal UPS available real power output in watts.
1.3.6.1.4.1.534.1.10.4ScalarxupsConfigOutputFreqread-onlymandatoryThe nominal output frequency in tenths of Hz.
1.3.6.1.4.1.534.1.10.5ScalarxupsConfigDateAndTimeread-writemandatoryDate and time information for the UPS. Setting this variable will initiate a set UPS date and time to this value. Reading this variable will return the UPS tim…
1.3.6.1.4.1.534.1.10.6ScalarxupsConfigLowOutputVoltageLimitread-onlymandatoryThe Lower limit for acceptable Output Voltage, per the UPS specifications.
1.3.6.1.4.1.534.1.10.7ScalarxupsConfigHighOutputVoltageLimitread-onlymandatoryThe Upper limit for acceptable Output Voltage, per the UPS specifications.
1.3.6.1.4.1.534.1.10.8ScalarxupsConfigInstallDateread-writemandatoryThe date when this UPS was installed. Free text format, so the preferred local date format may be used (MM/DD/YYYY, DD-Mon-YYYY, etc).
1.3.6.1.4.1.534.1.11NodexupsTrapControl
1.3.6.1.4.1.534.1.11.1ScalarxupsMaxTrapLevelread-writemandatoryThe level of severity of traps which will be sent to the requesting host; individual trap receivers will have individual values for this variable. Values are: …
1.3.6.1.4.1.534.1.11.2ScalarxupsSendTrapTyperead-writemandatoryThe type of traps which will be sent to the requesting host; individual trap receivers will have individual values for this variable. The additional variables …
1.3.6.1.4.1.534.1.11.3ScalarxupsTrapMessageread-onlymandatoryA descriptive text message which may be sent with traps to further explain the reason for the trap. This object is not-accessible to MIB browsers, but had to b…
1.3.6.1.4.1.534.1.11.4NodexupsTrapSource
1.3.6.1.4.1.534.1.11.4.1NodexupsTrapDefined
1.3.6.1.4.1.534.1.11.4.1.1NodexupstdControlOffThe UPS output power will turn off in a number of seconds equal to upsControlOutputOffTrapDelay.
1.3.6.1.4.1.534.1.11.4.1.2NodexupstdControlOnThe UPS output power will turn on in a number of seconds equal to upsControlOutputOnTrapDelay.
1.3.6.1.4.1.534.1.11.4.1.3NodexupstdOnBatteryThe UPS has no AC input power and is running on battery.
1.3.6.1.4.1.534.1.11.4.1.4NodexupstdLowBatteryThe UPS batteries are low. Tied to low battery alarm condition.
1.3.6.1.4.1.534.1.11.4.1.5NodexupstdUtilityPowerRestoredInput power has been restored after running on battery.
1.3.6.1.4.1.534.1.11.4.1.6NodexupstdReturnFromLowBatteryThe battery has recovered from a low battery condition.
1.3.6.1.4.1.534.1.11.4.1.7NodexupstdOutputOverloadThe ups has sensed an overload of greater than 106 percent. Tied to the 106% overload alarm.
1.3.6.1.4.1.534.1.11.4.1.8NodexupstdInternalFailureSome component of the ups - rectifier, inverter, control panel has failed. Tied to alarms indi- cating failure.
1.3.6.1.4.1.534.1.11.4.1.9NodexupstdBatteryDischargedThe Battery Totally Discharged Alarm has occurred.
1.3.6.1.4.1.534.1.11.4.1.10NodexupstdInverterFailureThe ups inverter is unavailable due to an internal failure.
1.3.6.1.4.1.534.1.11.4.1.11NodexupstdOnBypassThe ups has gone on bypass for some reason.
1.3.6.1.4.1.534.1.11.4.1.12NodexupstdBypassNotAvailableThe ups bypass is unavailable
1.3.6.1.4.1.534.1.11.4.1.13NodexupstdOutputOffThe ups output is switched off.
1.3.6.1.4.1.534.1.11.4.1.14NodexupstdInputFailureThe ups input power is incorrect in voltage, frequency, or phase rotation.
1.3.6.1.4.1.534.1.11.4.1.15NodexupstdBuildingAlarmOne of the defined building alarms has occurred.
1.3.6.1.4.1.534.1.11.4.1.16NodexupstdShutdownImminentThe ups shutdown imminent alarm has occurred.
1.3.6.1.4.1.534.1.11.4.1.17NodexupstdOnInverterThe ups is returned to utility power running the inverter after either a transfer to bypass or a run on battery.
1.3.6.1.4.1.534.1.11.4.1.20NodexupstdBreakerOpenOne of the UPS breakers or contactors has been opened.
1.3.6.1.4.1.534.1.11.4.1.21NodexupstdAlarmEntryAddedAn alarm not defined in the xups Well Known Alarms (eg, an alarm defined in RFC1628) has been added to the Alarm Table.
1.3.6.1.4.1.534.1.11.4.1.22NodexupstdAlarmEntryRemovedAn alarm not defined in the xups Well Known Alarms has been removed from the Alarm Table.
1.3.6.1.4.1.534.1.11.4.1.23NodexupstdAlarmBatteryBadOne or more batteries have been determined to require replacement.
1.3.6.1.4.1.534.1.11.4.1.24NodexupstdOutputOffAsRequestedThe UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.4.1.534.1.11.4.1.25NodexupstdDiagnosticTestFailedThe result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.534.1.11.4.1.26NodexupstdCommunicationsLostA problem has been encountered in the communications between the agent and the UPS.
1.3.6.1.4.1.534.1.11.4.1.27NodexupstdUpsShutdownPendingAn xupsControlOutputOffDelay countdown is underway.
1.3.6.1.4.1.534.1.11.4.1.28NodexupstdAlarmTestInProgressA test is in progress, as initiated and indicated by the xupsTest Group. When the test is complete, one of the following traps will be sent: - xupstdDiagnostic…
1.3.6.1.4.1.534.1.11.4.1.29NodexupstdAmbientTempBadThe ambient temperature, xupsEnvAmbientTemp, has fallen below the set lower limit, xupsEnvAmbientLowerLimit, or has risen above the set upper limit, xupsEnvAmb…
1.3.6.1.4.1.534.1.11.4.1.30NodexupstdContactActiveNoticeThe Contact indicated by xupsContactIndex is in its Active state. The following are the situations that generate this trap: For xupsContactType: and xupsContac…
1.3.6.1.4.1.534.1.11.4.1.31NodexupstdContactInactiveNoticeThe Contact indicated by xupsContactIndex has changed to its Inactive state.
1.3.6.1.4.1.534.1.11.4.1.32NodexupstdLossOfRedundancyA parallel UPS system is no longer operating in N+1 redundant mode; this may be due to module failure or removal, or due to overloading.
1.3.6.1.4.1.534.1.11.4.1.33NodexupstdAlarmTempBadAn internal temperature is out of tolerance.
1.3.6.1.4.1.534.1.11.4.1.34NodexupstdAlarmChargerFailedAn uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.4.1.534.1.11.4.1.35NodexupstdAlarmFanFailureThe failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.534.1.11.4.1.36NodexupstdAlarmFuseFailureThe failure of one or more fuses has been detected.
1.3.6.1.4.1.534.1.11.4.1.37NodexupstdPowerSwitchBadA Relay, Contactor, or Breaker has failed.
1.3.6.1.4.1.534.1.11.4.1.38NodexupstdModuleFailureOne module in a parallel or composite system has failed.
1.3.6.1.4.1.534.1.11.4.1.39NodexupstdOnAlternatePowerSourceThe system is being powered by its Alternate Power Source, such as a Secondary utility feed (on a dual AC input UPS), generator, flywheel, or fuel cell.
1.3.6.1.4.1.534.1.11.4.1.40NodexupstdAltPowerNotAvailableOn systems with a separate alternate power source (eg, dual AC inputs), that alternate power source is currently not available. This could be a problem if the …
1.3.6.1.4.1.534.1.11.4.1.41NodexupstdNoticeConditionSome Notice condition exists which is not covered by the other traps. This is like an xupstdInternalFailure, but at a lower severity level.
1.3.6.1.4.1.534.1.11.4.1.42NodexupstdRemoteTempBadThe remote temperature, xupsEnvRemoteTemp, has fallen below the set lower limit, xupsEnvRemoteTempLowerLimit, or has risen above the set upper limit, xupsEnvRe…
1.3.6.1.4.1.534.1.11.4.1.43NodexupstdRemoteHumidityBadThe remote temperature, xupsEnvRemoteHumidity, has fallen below the set lower limit, xupsEnvRemoteHumidityLowerLimit, or has risen above the set upper limit, x…
1.3.6.1.4.1.534.1.11.4.1.44NodexupstdHeartbeatA periodic status trap message. It is sent at an interval set by object xupsHeartbeatMinsInterval. The included variables provide a brief statement of the UPS …
1.3.6.1.4.1.534.1.11.4.1.45NodexupstdDiagnosticTestPassedA diagnostic test just completed, and its result is Passed. The included variables provide additional information on the test.
1.3.6.1.4.1.534.1.11.4.1.46NodexupstdOutputBadThe output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.534.1.11.4.1.47NodexupstdAwaitingPowerThe UPS output is off and the UPS is awaiting the return of input power.
1.3.6.1.4.1.534.1.11.4.1.48NodexupstdOnMaintenanceBypassThe UPS has been placed on Maintenance / Manual Bypass by an operator.
1.3.6.1.4.1.534.1.11.4.1.49NodexupstdCommEstablishedThis trap is sent when the SNMP agent first establishes a communication link with the UPS. The included variables provide identification and UPS status informa…
1.3.6.1.4.1.534.1.11.4.1.50NodexupstdAgentDownThis trap is sent when the SNMP agent is exiting or closing down gracefully. This may be triggered by a signal from the OS to stop this process. In many implem…
1.3.6.1.4.1.534.1.11.5ScalarxupsHeartbeatMinsIntervalread-writemandatoryHow often to send the xupstdHeartbeat trap, in units of minutes. A setting of 0 disables the Heartbeat function.
1.3.6.1.4.1.534.1.12NodexupsRecep
1.3.6.1.4.1.534.1.12.1ScalarxupsNumReceptaclesread-onlymandatoryThe number of independently controllable Receptacles, as described in the xupsRecepTable.
1.3.6.1.4.1.534.1.12.2TablexupsRecepTablenot-accessiblemandatoryThe Aggregate Object with number of entries equal to NumReceptacles and including the xupsRecep group.
1.3.6.1.4.1.534.1.12.2.1RowxupsRecepEntrynot-accessiblemandatoryThe Recep table entry, etc.
1.3.6.1.4.1.534.1.12.2.1.1ColumnxupsRecepIndexread-onlymandatoryThe number of the Receptacle. Serves as index for Receptacle table.
1.3.6.1.4.1.534.1.12.2.1.2ColumnxupsRecepStatusread-onlymandatoryThe Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off, 4=Off w/Pending ON, 5=Unknown, 6=Reserved for future, 7=Failed in Closed position, 8=Failed in Ope…
1.3.6.1.4.1.534.1.12.2.1.3ColumnxupsRecepOffDelaySecsread-writemandatoryThe Delay until the Receptacle is turned Off. Setting this value to other than -1 will cause the UPS output to turn off after the number of seconds (0 is immed…
1.3.6.1.4.1.534.1.12.2.1.4ColumnxupsRecepOnDelaySecsread-writemandatoryThe Delay until the Receptacle is turned On. Setting this value to other than -1 will cause the UPS output to turn on after the number of seconds (0 is immedia…
1.3.6.1.4.1.534.1.12.2.1.5ColumnxupsRecepAutoOffDelayread-writemandatoryThe delay after going On Battery until the Receptacle is automatically turned Off. A value of -1 means that this Output should never be turned Off automaticall…
1.3.6.1.4.1.534.1.12.2.1.6ColumnxupsRecepAutoOnDelayread-writemandatorySeconds delay after the Outlet is signaled to turn On before the Output is Automatically turned ON. A value of -1 means that this Output should never be turned…
1.3.6.1.4.1.534.1.12.2.1.7ColumnxupsRecepShedSecsWithRestartread-writemandatorySetting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is ag…
1.3.6.1.4.1.534.1.13NodexupsTopology
1.3.6.1.4.1.534.1.13.1ScalarxupsTopologyTyperead-onlymandatoryValue which denotes the type of UPS by its power topology. Values are the same as those described in the XCP Topology block's Overall Topology field.
1.3.6.1.4.1.534.1.13.2ScalarxupsTopoMachineCoderead-onlymandatoryID Value which denotes the Powerware model of the UPS for software. Values are the same as those described in the XCP Configuration block's Machine Code field.
1.3.6.1.4.1.534.1.13.3ScalarxupsTopoUnitNumberread-onlymandatoryIdentifies which unit and what type of data is being reported. A value of 0 means that this MIB information comes from the top-level system view (eg, manifold …
1.3.6.1.4.1.534.1.13.4ScalarxupsTopoPowerStrategyread-writemandatoryValue which denotes which Power Strategy is currently set for the UPS. The values are: highAlert(1) - The UPS shall optimize its operating state to maximize it…
1.3.6.1.4.1.534.2NodexupsObjectId
1.3.6.1.4.1.534.2.1NodepowerwareEthernetSnmpAdapter
1.3.6.1.4.1.534.2.2NodepowerwareNetworkSnmpAdapterEther
1.3.6.1.4.1.534.2.3NodepowerwareNetworkSnmpAdapterToken
1.3.6.1.4.1.534.2.4NodeonlinetDaemon
1.3.6.1.4.1.534.2.5NodeconnectUPSAdapterEthernet
1.3.6.1.4.1.534.2.6NodepowerwareNetworkDigitalIOEther
1.3.6.1.4.1.534.2.7NodeconnectUPSAdapterTokenRing
1.3.6.1.4.1.534.2.8NodesimpleSnmpAdapter
1.3.6.1.4.1.534.2.9NodepowerwareEliSnmpAdapter