MIB Viewer

acpmsTRPValueStr

OBJECT-TYPE
1.3.6.1.4.1.3052.14.1.8.1.1.24
Access
read-only
Status
current
Sub-identifiers
0
Total real power, in watts. On the YD2010, this is calculated using the formula (register * PT ratio * CT ratio * Urg * 0.4), where Urg is the voltage range taken from register 0x30A. On the WattsOn models, this is calculated using the formula (register * PT * CT).
DisplayString