MIB Viewer

eqptPowerBatFailure

OBJECT-TYPE
1.3.6.1.4.1.637.61.1.23.18.1.8
Access
read-only
Status
mandatory
Sub-identifiers
0
The battery failure state will provide an view on the failure state of the battery. This failure state has meaning for devices that have a configured eqptPowerBatType and eqptPowerBatState different from default or no-data. Other devices get a not-applicable (0) value returned. Specific ranges for the failure cases strongly depend on the battery type used. The ranges will be detailed in the customer documentation. Enumeration is as follows: 0 = not applicable 1 = voltage good 2 = voltage out of range 3 = over-voltage 4 = over-temperature alarm on local temperature sensor 5 = battery depleted ALCATEL NOTE: SUPPORT: YES INSRVMOD: NA RANGE: See above PERSIST: NO DEFVALUE: 0 UNITS: -
INTEGER { not-applicable (0), voltage-good (1), voltage-out-of-range (2), over-voltage (3), over-temperature (4), battery-depleted (5) }