iso/org/dod/internet/private/enterprises/asentria/s450/.1/.1/esPointTable/esPointEntry/esPointInEventState
esPointInEventState
OBJECT-TYPE
1.3.6.1.4.1.3052.17.1.1.1.1.5
Description
A number referring to the event state of a point on an EventSensor. This number can have different meanings depending on the point class. If the point class is temperature, humidity, or analog input, then the values of this object are: 1=very low 2=low 3=normal 4=high 5=very high For contact closures the values of this object are: 1=point in event state 2=point in normal state For relays the values of this object are: 1=relay energized (active) 2=relay de-energized (inactive) For any point class and any point, if the event state is undefined, then the value of this object is 0. For any point class except relay, this object is read-only. For relays, setting this object to 1 puts the relay into its active (energized) state. Setting it to 2 puts the relay into its inactive (de-energized) state. Setting it to any value greater than 2 puts the relay into its active state for that many seconds (up to 3600), after which time it puts the relay into its inactive state.
Syntax
Integer32