MIB Viewer

lgpPduEntrySWOverTemperatureProtectionDelay

OBJECT-TYPE
1.3.6.1.4.1.476.1.42.3.8.5.10
Access
read-write
Status
current
Sub-identifiers
0
This sets the delay for the PDU Software Over Temperature Protection feature. This value determines the amount of time to delay, after the high temperature alarm becomes active, before taking action on the enabled receptacles. If the high temperature alarm becomes inactive before the expiration of the delay time, no action will be taken on the enabled receptacles. See lgpPduRcpEntrySwOverTemperatureProtection to enable this feature and get further information about what actions will be performed.
Unsigned32