podInputPhaseConfigOverloadRestriction

OBJECT-TYPE
1.3.6.1.4.1.38446.3.3.2.1.3
Access
read-write
Status
current
Sub-identifiers
0
This OID controls the behavior of a Switched PDU Input Phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding Input Phase to turn on. Setting this OID to restrictOnUpperWarning (2) will not allow outlets on the corresponding Input Phase to turn on if the podInputPhaseConfigUpperWarningThreshold OID is exceeded. Setting this OID to restrictOnUpperCritical (3) will not allow outlets on the corresponding Input Phase to turn on if the podInputPhaseConfigUpperCriticalThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.
INTEGER { alwaysAllowTurnOn (1), restrictOnUpperWarning (2), restrictOnUpperCritical (3), notSupported (4) }