tlpAtsConfigHighVoltageReset

OBJECT-TYPE
1.3.6.1.4.1.850.1.1.3.4.5.5.1.2
Access
read-write
Status
current
Sub-identifiers
0
If an input connection is disconnected due to over-voltage, the line voltage on the input source has to fall below this value before the unit re-connects the AC input connection for the input source. tlpAtsConfigHighVoltageReset is the same value for both input sources on some units. On such units, changing this value on one source will change the value on the other source. The maximum value allowed is dictated by tlpAtsConfigHighVoltageTransfer. On units where this is the same value for both sources, the minimum value allowed is dictated by the greater of tlpAtsConfigTransferReset.1 and tlpAtsConfigTransferReset.2. On units where the value is distinct for each source, the minimum value allowed is dictated solely by this source's tlpAtsConfigTransferReset. If not supported, this value will return ERROR_NO_SUCH_NAME.
Unsigned32