tlpAtsConfigHighVoltageTransferOld

OBJECT-TYPE
1.3.6.1.4.1.850.1.1.3.4.5.2.1.1
Access
read-write
Status
obsolete
Sub-identifiers
0
The maximum line voltage allowed before the unit disconnects the AC input connection. The maximum value allowed is dictated by tlpAtsInputHighTransferVoltageUpperBound (inclusively). The minimum value allowed is dictated by tlpAtsConfigHighVoltageResetOld. This value may not be configurable on all models. If not supported, this value will return ERROR_NO_SUCH_NAME.
Unsigned32