MIB Viewer

tlpAtsConfigLowVoltageTransfer

OBJECT-TYPE
1.3.6.1.4.1.850.1.1.3.4.5.5.1.7
Access
read-write
Status
current
Sub-identifiers
0
The minimum line voltage allowed before the unit disconnects the AC input connection. tlpAtsConfigLowVoltageTransfer is the same value for both input sources. As such, changing this value on one source will change the value on the other source. The maximum value allowed is dictated by tlpAtsConfigLowVoltageReset. The minimum value allowed is dictated by tlpAtsInputBadTransferVoltageLowerBound (inclusively). If not supported, this value will return ERROR_NO_SUCH_NAME.
Unsigned32