MIB Viewer

upsAdvStateLifeCycleManagement

OBJECT-TYPE
1.3.6.1.4.1.318.1.1.1.11.2.14
Access
read-only
Status
mandatory
Sub-identifiers
0
An ASCII string containing the 16 flags representing the life cycle management alerts for the device. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 16, and read from left to right. The bits are defined as follows: Flag 1: End of Warranty Soon Flag 2: Battery Check Recommended Flag 3: Service Period On Wearing Parts Expired Flag 4: Secure Start-up Recommended Flag 5: Fan Life Expired Flag 6: DC Capacitor Life Expired Flag 7: AC Capacitor Life Expired Flag 8: Supply Service Life Expired Flag 9: Ups Out Of Limits Warning Flag 10: Air Filter Life Expired Flag 11: <Not Used> Flag 12: <Not Used> Flag 13: <Not Used> Flag 14: <Not Used> Flag 15: <Not Used> Flag 16: <Not Used>
DisplayString