lgpEnvConfigDeltaGlycolType

OBJECT-TYPE
1.3.6.1.4.1.476.1.42.3.4.4.26
Access
read-write
Status
current
Sub-identifiers
0
The system configuration parameter that specifies how the system will determine if there is enough capacity to initiate free cooling. If 'disabled', the system will use the valve temperature to initiate free cooling. If 'contact', a input to the system will initiate free cooling. If 'valve', the system compares the room and glycol temperature differential with the valve temperature to initiate free cooling. If the temperature differential is greater than or equal to the valve temperature, free cooling will be initiated.
INTEGER { disabled(1), contact(2), value(3) }