EPPC-MIB

293 objects
No module-level DESCRIPTION found.
OIDNameAccessStatusDescription
1.3.6.1.4.1.935Nodeppc
1.3.6.1.4.1.935.10Nodedevice
1.3.6.1.4.1.935.10.1NodeupsAgent
1.3.6.1.4.1.935.10.1.1NodeupsE
1.3.6.1.4.1.935.10.1.1.1NodeupsEIdentity
1.3.6.1.4.1.935.10.1.1.1.1ScalarupsEIdentityManufacturerread-onlymandatoryThe name of the UPS manufacturer.
1.3.6.1.4.1.935.10.1.1.1.2ScalarupsEIdentityModelread-onlymandatoryThe UPS Model designation.
1.3.6.1.4.1.935.10.1.1.1.3ScalarupsEIdentityUPSFirmwareVerisonread-onlymandatoryThe UPS firmware/software version(s).
1.3.6.1.4.1.935.10.1.1.1.4ScalarupsEIndentityUPSSerialNumberread-onlymandatoryoptional. Most UPS don't supply the value of UPS serial No.
1.3.6.1.4.1.935.10.1.1.1.5ScalarupsEIdentityDescriptionread-writemandatoryA string to identify the UPS. This object should be set by the administrator.
1.3.6.1.4.1.935.10.1.1.1.6ScalarupsEIdentityAgentSoftwareVerisonread-onlymandatoryThe Network Management Card software/firmware version. This variable may or may not have the same value as upsEIdentGroupUPSSoftwareVersion in some implementat…
1.3.6.1.4.1.935.10.1.1.1.7ScalarupsEIdentityAttachedDevicesread-writemandatoryA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator
1.3.6.1.4.1.935.10.1.1.2NodeupsESystemSummary
1.3.6.1.4.1.935.10.1.1.2.1ScalarupsESystemStatusread-onlymandatoryThe indication of UPS system status.
1.3.6.1.4.1.935.10.1.1.2.2ScalarupsESystemTemperatureread-onlymandatoryThe temperature of UPS presented in 0.1 degree.
1.3.6.1.4.1.935.10.1.1.2.3ScalarupsESystemWarningCoderead-onlymandatoryThe warning code of UPS. Please refer the warning table of 'Q6' for details.
1.3.6.1.4.1.935.10.1.1.2.4ScalarupsESystemFaultCoderead-onlymandatoryThe fault code of UPS.Please refer the fault code of 'Q6' for details.
1.3.6.1.4.1.935.10.1.1.2.5ScalarupsESystemConfigInputVoltageread-onlymandatoryThe magnitude of the nominal input voltage presented in 0.1 V. On those systems which support read-write access to this object, if there is an attempt to set t…
1.3.6.1.4.1.935.10.1.1.2.6ScalarupsESystemConfigInputFrequenceread-onlymandatoryThe nominal input frequency presented in 0.1 Hz. On those systems which support read-write access to this object, if there is an attempt to set this variable t…
1.3.6.1.4.1.935.10.1.1.2.7ScalarupsESystemConfigOutputVoltageread-onlymandatoryThe magnitude of the nominal output voltage presented in 0.1V. On those systems which support read-write access to this object, if there is an attempt to set t…
1.3.6.1.4.1.935.10.1.1.2.8ScalarupsESystemConfigOutputFrequencyread-onlymandatoryThe nominal output frequency presented in 0.1Hz. On those systems which support read-write access to this object, if there is an attempt to set this variable t…
1.3.6.1.4.1.935.10.1.1.2.9ScalarupsESystemConfigOutputVAread-onlymandatoryThe magnitude of the nominal Volt-Amp rating presented in VA.
1.3.6.1.4.1.935.10.1.1.2.10ScalarupsESystemConfigOutputPowerread-onlymandatoryThe magnitude of the nominal true power rating presented in W .
1.3.6.1.4.1.935.10.1.1.2.11ScalarupsESystemConfigOutputLoadHighSetPointread-writemandatoryThe maximum output load allowed before the load is too high for UPS operation
1.3.6.1.4.1.935.10.1.1.2.12ScalarupsESystemConfigOverTemperatureSetPointread-writemandatoryThe maximum temperature allowed before the UPS operation temperature is too high, presented in 0.1 degree.
1.3.6.1.4.1.935.10.1.1.2.13ScalarupsESystemInputSourceNumread-onlymandatoryThe present external source of input power.
1.3.6.1.4.1.935.10.1.1.2.14ScalarupsESystemInputLineBadsread-onlymandatoryThe number of times the Input was out of tolerance in voltage or frequency. Its value should be initialized 0 after agent restarting.
1.3.6.1.4.1.935.10.1.1.2.15ScalarupsESystemInputNumPhasesread-onlymandatoryThe number of input phase utilized is this device, serves as the table index. This value indicate the device initialized feature.
1.3.6.1.4.1.935.10.1.1.2.16TableupsESystemInputTablenot-accessiblemandatoryA list of input table entries. The number of entries is given by the value of upsESystemInputNumPhase.
1.3.6.1.4.1.935.10.1.1.2.16.1RowupsESystemInputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.935.10.1.1.2.16.1.1ColumnupsESystemInputPhasenot-accessiblemandatoryThe number of the phase. Serves as index for input table
1.3.6.1.4.1.935.10.1.1.2.16.1.2ColumnupsESystemInputFrequencyread-onlymandatoryThe measured input frquency from the UPS meters in 0.1Hz.
1.3.6.1.4.1.935.10.1.1.2.16.1.3ColumnupsESystemInputVoltageread-onlymandatoryThe measured input voltage from the UPS meters in 0.1 volts
1.3.6.1.4.1.935.10.1.1.2.16.1.4ColumnupsESystemInputCurrentread-onlymandatoryThe measured input mandatory from the UPS meters in 0.1 amps.
1.3.6.1.4.1.935.10.1.1.2.16.1.5ColumnupsESystemInputWattsread-onlymandatoryThe measured input real power in watts.
1.3.6.1.4.1.935.10.1.1.2.17ScalarupsESystemOutputNumPhaseread-onlymandatoryThe number of metered output phases, serves as the table index. This value indicate the device initialized feature.
1.3.6.1.4.1.935.10.1.1.2.18TableupsESystemOutputTablenot-accessiblemandatoryA list of output table entries. The number of entries is given by the value of upsESystemOutputNumPhase.
1.3.6.1.4.1.935.10.1.1.2.18.1RowupsESystemOutputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular line.
1.3.6.1.4.1.935.10.1.1.2.18.1.1ColumnupsESystemOutputPhasenot-accessiblemandatoryThe number of the phase. Serves as index for output table
1.3.6.1.4.1.935.10.1.1.2.18.1.2ColumnupsESystemOutputFrequencyread-onlymandatoryThe measured output frequency from the UPS meters in 0.1Hz.
1.3.6.1.4.1.935.10.1.1.2.18.1.3ColumnupsESystemOutputVoltageread-onlymandatoryThe measured output voltage from the UPS meters in 0.1 volts
1.3.6.1.4.1.935.10.1.1.2.18.1.4ColumnupsESystemOutputCurrentread-onlymandatoryThe measured output mandatory from the UPS meters in 0.1 amps.
1.3.6.1.4.1.935.10.1.1.2.18.1.5ColumnupsESystemOutputWattsread-onlymandatoryThe measured output real power in watts.
1.3.6.1.4.1.935.10.1.1.2.18.1.6ColumnupsESystemOutputVAread-onlymandatoryThe measured output real complex power in VA.
1.3.6.1.4.1.935.10.1.1.2.18.1.7ColumnupsESystemOutputLoadread-onlymandatoryThe UPS output load in percent of rated capacity.
1.3.6.1.4.1.935.10.1.1.2.19ScalarupsESystemBypassNumPhaseread-onlymandatoryThe number of bypass phases, serves as the table index. This value indicate the device initialized feature
1.3.6.1.4.1.935.10.1.1.2.20TableupsESystemBypassTablenot-accessiblemandatoryA list of bypass table entries. The number of entries is given by the value of upsESystemBypassNumPhase.
1.3.6.1.4.1.935.10.1.1.2.20.1RowupsESystemBypassEntrynot-accessiblemandatoryAn entry containing information applicable to a particular line.
1.3.6.1.4.1.935.10.1.1.2.20.1.1ColumnupsESystemBypassPhasenot-accessiblemandatoryThe number of the phase. Serves as index for bypass table
1.3.6.1.4.1.935.10.1.1.2.20.1.2ColumnupsESystemBypassFrequencyread-onlymandatoryThe measured bypass frequency from the UPS meters in 0.1 Hz.
1.3.6.1.4.1.935.10.1.1.2.20.1.3ColumnupsESystemBypassVoltageread-onlymandatoryThe measured bypass voltage from the UPS meters in 0.1 volts
1.3.6.1.4.1.935.10.1.1.2.20.1.4ColumnupsESystemBypassCurrentread-onlymandatoryThe measured bypass mandatory from the UPS meters in 0.1 amps
1.3.6.1.4.1.935.10.1.1.2.20.1.5ColumnupsESystemBypassWattsread-onlymandatoryThe measured bypass input real power in watts.
1.3.6.1.4.1.935.10.1.1.2.21ScalarupsESystemConfigBelowCapacityLimitread-writemandatoryThe UPS batteries capacity(%) limit for shutdown
1.3.6.1.4.1.935.10.1.1.2.22ScalarupsESystemConfigBelowRemainTimeLimitread-writemandatoryThe UPS batteries backup time(minute) limit for shutdown
1.3.6.1.4.1.935.10.1.1.3NodeupsEBatterySystem
1.3.6.1.4.1.935.10.1.1.3.1ScalarupsEBatteryStatusread-onlymandatoryThe status of UPS battery, a value of batteryLow indicates that the battery-low status bit has been set from device. A value of batteryDepleted indicates that …
1.3.6.1.4.1.935.10.1.1.3.2ScalarupsESecondsOnBatteryread-onlymandatoryIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.935.10.1.1.3.3ScalarupsEBatteryEstimatedMinutesRemainingread-onlymandatoryAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.935.10.1.1.3.4ScalarupsEBatteryEstimatedChargeRemainingread-onlymandatoryAn estimate of the battery charge remaining expressed as a percent of full charge
1.3.6.1.4.1.935.10.1.1.3.5ScalarupsEPositiveBatteryVoltageread-onlymandatoryThe magnitude of the present positive battery voltage in 0.1 Volt DC
1.3.6.1.4.1.935.10.1.1.3.6ScalarupsENegativeBatteryVoltageread-onlymandatoryThe magnitude of the present negative battery voltage in 0.1 Volt DC
1.3.6.1.4.1.935.10.1.1.3.7ScalarupsEBatteryCellNumberread-onlymandatoryThis object indicate the cell number of each set.
1.3.6.1.4.1.935.10.1.1.3.8ScalarupsEBatteryTemperatureread-onlymandatoryThe ambient temperature at or near the UPS Battery casing in 0.1 degree.
1.3.6.1.4.1.935.10.1.1.3.9ScalarupsEBatteryLastReplacedDateread-onlymandatoryThe date when the Batteries in this UPS were last replaced. The format should be DD/MM/YYYY.
1.3.6.1.4.1.935.10.1.1.3.10ScalarupsEBatteryABMStatusread-onlymandatoryThe status of ABM.
1.3.6.1.4.1.935.10.1.1.3.11ScalarupsEChargerModulesNumread-onlymandatoryThe number of charger modules inserted to UPS systems. served as the index of the upsEChargerModulesTable. The default value 0 indicate that the UPS system don…
1.3.6.1.4.1.935.10.1.1.3.12TableupsEChargerModulesTablenot-accessiblemandatoryA list of charger modules entries. The number of entries is given by the value of upsEchargerModulesNum.
1.3.6.1.4.1.935.10.1.1.3.12.1RowupsEChargerModulesEntrynot-accessiblemandatoryAn entry containing information applicable to a particular charger module.
1.3.6.1.4.1.935.10.1.1.3.12.1.1ColumnchargerModulesNumnot-accessiblemandatoryThe number of charger modules. Serves as index for charger module table
1.3.6.1.4.1.935.10.1.1.3.12.1.2ColumnchargerModulesAddressread-onlymandatoryCharger Modules' address.
1.3.6.1.4.1.935.10.1.1.3.12.1.3ColumnpositiveChargeVotlageread-onlymandatoryThe measured positive charger voltage from the UPS meters in 0.1 volts
1.3.6.1.4.1.935.10.1.1.3.12.1.4ColumnnegativeChargeVoltageread-onlymandatoryThe measured nepositive charger voltage from the UPS meters in 0.1 volts
1.3.6.1.4.1.935.10.1.1.3.12.1.5ColumnpositiveChargeCurrentread-onlymandatoryThe measured positive charger mandatory from the UPS meters in in 0.1 amps.
1.3.6.1.4.1.935.10.1.1.3.12.1.6ColumnnegativeChargeCurrentread-onlymandatoryThe measured nepositive charger mandatory from the UPS meters in 0.1 amps.
1.3.6.1.4.1.935.10.1.1.3.12.1.7ColumnchargerModulesTemperatureread-onlymandatoryThe measured charger temperature from the UPS meters in 0.1 degree.
1.3.6.1.4.1.935.10.1.1.3.12.1.8ColumnchargerModulesModeread-onlymandatoryThe working mode of charger modules.
1.3.6.1.4.1.935.10.1.1.4NodeupsEPowerConverterSystem
1.3.6.1.4.1.935.10.1.1.4.1ScalarupsEUPSModulesNumread-onlymandatoryThe number of UPS modules inserted to UPS systems. served as the index of the upsEModulesTable. the default value 0 indicate that the UPS system do not have se…
1.3.6.1.4.1.935.10.1.1.4.2TableupsEModulesTablenot-accessiblemandatoryA list of UPS modules entries. The number of entries is given by the value of upsEModulesNum.
1.3.6.1.4.1.935.10.1.1.4.2.1RowupsEModulesEntrynot-accessiblemandatoryAn entry containing information applicable to a particular upsE module.
1.3.6.1.4.1.935.10.1.1.4.2.1.1ColumnupsEModulesNumnot-accessiblemandatoryThe number of UPS modules. Serves as index for UPS module table
1.3.6.1.4.1.935.10.1.1.4.2.1.2ColumnupsEModuleAddressread-onlymandatorythe address of UPS modules.
1.3.6.1.4.1.935.10.1.1.4.2.1.3ColumnupsEModulePositiveBusVoltread-onlymandatoryThe measured positive upsE module voltage from the UPS meters in 0.1 volts
1.3.6.1.4.1.935.10.1.1.4.2.1.4ColumnupsEModuleNegativeBusVoltread-onlymandatoryThe measured nepositive upsE module voltage from the UPS meters in 0.1 volts
1.3.6.1.4.1.935.10.1.1.4.2.1.5ColumnupsEModuleTemperatureread-onlymandatoryThe measured upsE module temperature from the UPS meters in 0.1 degree.
1.3.6.1.4.1.935.10.1.1.4.2.1.6ColumnupsEModuleWorkingModeread-onlymandatoryThe working mode of UPS modules.
1.3.6.1.4.1.935.10.1.1.4.2.1.7ColumnupsEModuleOutputCurrentRread-onlymandatoryThe measured upsE module output mandatory from the UPS meters in 0.1 A.
1.3.6.1.4.1.935.10.1.1.4.2.1.8ColumnupsEModuleOutputWattRread-onlymandatoryThe measured upsE module output watts from the UPS meters in watts.
1.3.6.1.4.1.935.10.1.1.4.2.1.9ColumnupsEModuleOutputLoadRread-onlymandatoryThe output load of UPS modules in %.
1.3.6.1.4.1.935.10.1.1.4.2.1.10ColumnupsEModuleWarningCoderead-onlymandatoryThe warning code of ups modules.Please refer the warning table of 'QU,XX' for details.
1.3.6.1.4.1.935.10.1.1.4.2.1.11ColumnupsEModuleFaultCoderead-onlymandatoryThe fault code of ups modules.Please refer command 'QU,XX' for details.
1.3.6.1.4.1.935.10.1.1.4.2.1.12ColumnupsEModuleTrapStateread-onlymandatorythe values indicate the unrestored traps. For example, after AC fail, so the value of upsETrapState should be '1'. And then the AC restore, the value of upsEMo…
1.3.6.1.4.1.935.10.1.1.4.2.1.13ColumnupsEModuleConfigOutputVAread-onlymandatoryThe magnitude of the nominal Volt-Amp rating presented in VA.
1.3.6.1.4.1.935.10.1.1.4.2.1.14ColumnupsEModuleOutputCurrentSread-onlymandatoryThe measured upsE module output mandatory from the UPS meters in 0.1 A.
1.3.6.1.4.1.935.10.1.1.4.2.1.15ColumnupsEModuleOutputCurrentTread-onlymandatoryThe measured upsE module output mandatory from the UPS meters in 0.1 A.
1.3.6.1.4.1.935.10.1.1.4.2.1.16ColumnupsEModuleOutputWattSread-onlymandatoryThe measured upsE module output watts from the UPS meters in watts.
1.3.6.1.4.1.935.10.1.1.4.2.1.17ColumnupsEModuleOutputWattTread-onlymandatoryThe measured upsE module output watts from the UPS meters in watts.
1.3.6.1.4.1.935.10.1.1.4.2.1.18ColumnupsEModuleOutputLoadSread-onlymandatoryThe output load of UPS modules in %.
1.3.6.1.4.1.935.10.1.1.4.2.1.19ColumnupsEModuleOutputLoadTread-onlymandatoryThe output load of UPS modules in %.
1.3.6.1.4.1.935.10.1.1.4.2.1.20ColumnupsEModuleOutputVARread-onlymandatoryThe magnitude of the nominal Volt-Amp rating presented in VA.
1.3.6.1.4.1.935.10.1.1.4.2.1.21ColumnupsEModuleOutputVASread-onlymandatoryThe magnitude of the nominal Volt-Amp rating presented in VA.
1.3.6.1.4.1.935.10.1.1.4.2.1.22ColumnupsEModuleOutputVATread-onlymandatoryThe magnitude of the nominal Volt-Amp rating presented in VA.
1.3.6.1.4.1.935.10.1.1.5NodeupsELoadSegment
1.3.6.1.4.1.935.10.1.1.5.1ScalarupsELoadSegment1OffDelayread-writemandatorySetting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less. Setting this object to 0 will cause the shutdown …
1.3.6.1.4.1.935.10.1.1.5.2ScalarupsELoadSegment1OnDelayread-writemandatorySetting this object will start the Load segment output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to …
1.3.6.1.4.1.935.10.1.1.5.3ScalarupsELoadSegment1AutoOffTimerread-writemandatoryThe load segment turns automatically off after the delay while the unit operates on battery, but the shutdown is cancelled if the utility return before the del…
1.3.6.1.4.1.935.10.1.1.5.4ScalarupsELoadSegment1AutoOnTimerread-writemandatoryThe load segment is automatically turned on after a selected delay if it has been shutdown due to on battery.
1.3.6.1.4.1.935.10.1.1.5.5ScalarupsELoadSegment1Stateread-onlymandatoryLoad segment output state.
1.3.6.1.4.1.935.10.1.1.5.6ScalarupsELoadSegment2OffDelayread-writemandatorySetting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less. Setting this object to 0 will cause the shutdown …
1.3.6.1.4.1.935.10.1.1.5.7ScalarupsELoadSegment2OnDelayread-writemandatorySetting this object will start the Load segment output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to …
1.3.6.1.4.1.935.10.1.1.5.8ScalarupsELoadSegment2AutoOffTimerread-writemandatoryThe load segment turns automatically off after the delay while the unit operates on battery, but the shutdown is cancelled if the utility return before the del…
1.3.6.1.4.1.935.10.1.1.5.9ScalarupsELoadSegment2AutoOnTimerread-writemandatoryThe load segment is automatically turned on after a selected delay if it has been shutdown due to on battery.
1.3.6.1.4.1.935.10.1.1.5.10ScalarupsELoadSegment2Stateread-onlymandatoryLoad segment output state.
1.3.6.1.4.1.935.10.1.1.6NodeupsEEnvironment
1.3.6.1.4.1.935.10.1.1.6.1NodeupsEEnvironmentTemperature
1.3.6.1.4.1.935.10.1.1.6.1.1ScalarupsEEnvironmentCurrentTemperatureread-onlymandatoryThe measurement of temperature sensor, in 0.1 degree
1.3.6.1.4.1.935.10.1.1.6.1.2ScalarupsEEnvironmentTemperatureHighSetPointread-writemandatoryThe set point for high temperature warning, in 0.1 degrees. This value must be greater than upsEEnvironmentTemperatureLowSetPoint, and the least significant di…
1.3.6.1.4.1.935.10.1.1.6.1.3ScalarupsEEnvironmentTemperatureHighStatusread-writemandatoryTo enable/disable high set point check with sensor temperature.
1.3.6.1.4.1.935.10.1.1.6.1.4ScalarupsEEnvironmentTemperatureLowSetPointread-writemandatoryThe set point for low temperature warning, in 0.1 degrees. This value must be less than upsEEnvironmentTemperatureHighSetPoint, and the least significant digit…
1.3.6.1.4.1.935.10.1.1.6.1.5ScalarupsEEnvironmentTemperatureLowStatusread-writemandatoryTo enable/disable low set point check with sensor temperature.
1.3.6.1.4.1.935.10.1.1.6.1.6ScalarupsEEnvironmentTemperatureOffsetread-writemandatoryThe offset to calibrate temperature of EMD, in 0.1 degrees
1.3.6.1.4.1.935.10.1.1.6.2NodeupsEEnvironmentHumidity
1.3.6.1.4.1.935.10.1.1.6.2.1ScalarupsEEnvironmentCurrentHumidityread-onlymandatoryThe measurement of sensor humidity present in %.
1.3.6.1.4.1.935.10.1.1.6.2.2ScalarupsEEnvironmentHumidityHighSetPointread-writemandatoryThe set point for high humidity warning, in %. This value must be greater than upsEEnvironmentHumidityLowSetPoint.
1.3.6.1.4.1.935.10.1.1.6.2.3ScalarupsEEnvironmentHumidityHighStatusread-writemandatoryTo enable/disable high set point check with emd humidity.
1.3.6.1.4.1.935.10.1.1.6.2.4ScalarupsEEnvironmentHumidityLowSetPointread-writemandatoryThe set point for low humidity warning, in %. This value must be less than upsEEnvironmentHumidityHighSetPoint.
1.3.6.1.4.1.935.10.1.1.6.2.5ScalarupsEEnvironmentHumidityLowStatusread-writemandatoryTo enable/disable high set point check with emd humidity.
1.3.6.1.4.1.935.10.1.1.6.2.6ScalarupsEEnvironmentHumidityOffsetread-writemandatoryThe offset to calibrate humidity of EMD, in %.
1.3.6.1.4.1.935.10.1.1.6.3ScalarupsEEnvironmentContactsNumread-onlymandatoryThe number of environment contacts, serves as the table index.
1.3.6.1.4.1.935.10.1.1.6.4TableupsEEnvironmentContactTablenot-accessiblemandatoryA list of contacts table entries. The number of entries is given by the value of upsEEnvironmentContactsNum
1.3.6.1.4.1.935.10.1.1.6.4.1RowupsEEnvironmentContactEntrynot-accessiblemandatoryAn entry containing information applicable to a particular contact
1.3.6.1.4.1.935.10.1.1.6.4.1.1ColumnupsEEnvironmentContactIndexnot-accessiblemandatoryThe number of environment contacts. Serves as index for environment contact table
1.3.6.1.4.1.935.10.1.1.6.4.1.2ColumnupsEEnvironmentContactTyperead-writemandatoryoperation type
1.3.6.1.4.1.935.10.1.1.6.4.1.3ColumnupsEEnvironmentContactStateread-onlymandatoryThe mandatory status.
1.3.6.1.4.1.935.10.1.1.6.4.1.4ColumnupsEEnvironmentContactDescriptionread-writemandatoryDescription of environment contact.
1.3.6.1.4.1.935.10.1.1.7NodeupsEBatteryTest
1.3.6.1.4.1.935.10.1.1.7.1ScalarupsEBatteryTestStartread-writemandatoryThis object specify the battery test type and initiate battery test. If battTestWithTime selected, the test time is refer to upsEBatteryTestSettingTime.
1.3.6.1.4.1.935.10.1.1.7.2ScalarupsEBatteryTestSettingTimeread-writemandatoryThe object specify the test time for battery test in seconds.
1.3.6.1.4.1.935.10.1.1.7.3ScalarupsEBatteryTestResultread-onlymandatoryThis object indicate the test result of battery.
1.3.6.1.4.1.935.10.1.1.7.4ScalarupsEBatteryTestStartTimeread-onlymandatoryThe value of the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsETestBatt…
1.3.6.1.4.1.935.10.1.1.7.5ScalarupsEBatteryTestElapsedTimeread-onlymandatoryThe amount of time in format hh:mm:ss, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the valu…
1.3.6.1.4.1.935.10.1.1.7.6TableupsEBatteryTestScheduleTablenot-accessiblemandatoryThis table describes the schedule for automatically battery test.
1.3.6.1.4.1.935.10.1.1.7.6.1RowupsEBatteryTestScheduleEntrynot-accessiblemandatoryAn entry containing information applicable to schedule test.
1.3.6.1.4.1.935.10.1.1.7.6.1.1ColumnupsEBatteryTestScheduleIndexnot-accessiblemandatoryThe index of battery test scheduled.
1.3.6.1.4.1.935.10.1.1.7.6.1.2ColumnupsEBatteryTestScheduleDayread-writemandatoryThe weekday or specaial day on which the UPS should start battery test.
1.3.6.1.4.1.935.10.1.1.7.6.1.3ColumnupsEBatteryTestScheduleTimeread-writemandatoryThe time that the battery test will be initiated in hh:mm format.
1.3.6.1.4.1.935.10.1.1.7.6.1.5ColumnupsEBatteryTestScheduleTyperead-writemandatoryThe type of battery test.
1.3.6.1.4.1.935.10.1.1.7.6.1.6ColumnupsEBatteryTestScheduleTestWithTimeread-writemandatoryThe battery time of setting time test in seconds.
1.3.6.1.4.1.935.10.1.1.7.6.1.7ColumnupsEBatteryTestScheduleSpecialDayread-writemandatoryThe special day that the battery test will be initiated in dd/mm/yyyy format.
1.3.6.1.4.1.935.10.1.1.8NodeupsEControl
1.3.6.1.4.1.935.10.1.1.8.1ScalarupsEControlOutputOffDelayread-writemandatorySetting this value to other than zero will cause the UPS output to turn off after the number of seconds.
1.3.6.1.4.1.935.10.1.1.8.2ScalarupsEControlOutputOnDelayread-writemandatorySetting this value to other than zero will cause the UPS output to turn on after the number of seconds.
1.3.6.1.4.1.935.10.1.1.8.3ScalarupsEControlOutputOnOffControlread-writemandatoryupsEOutputOff ( 1 ) indicates the shutdown sequence, upsEOutputOffCancel ( 2 ) indicates cancel the shutdown sequence, upsESleep( 3 ) indicates shutdown UPS fi…
1.3.6.1.4.1.935.10.1.1.8.4TableupsEShutdownEventsTablenot-accessiblemandatoryThis table describes the parametes for shutdown process when shutdown event occurs
1.3.6.1.4.1.935.10.1.1.8.4.1RowupsEShutdownEventsEntrynot-accessiblemandatoryAn entry containing information applicable to a particular shutdown event line
1.3.6.1.4.1.935.10.1.1.8.4.1.1ColumnupsEShutdownEventnot-accessiblemandatoryThe shutdown event identification
1.3.6.1.4.1.935.10.1.1.8.4.1.2ColumnupsEShutdownEventActionread-writemandatoryStatus of the corresponding shutdown Event. When set to disable(), shutdown process will not start when corresponding event occured.
1.3.6.1.4.1.935.10.1.1.8.4.1.3ColumnupsEShutdownwarningPeriodTimeread-writemandatoryThe Delay in seconds after the occurance of the curresponding shutdown event, and warning message should be popped in this period.
1.3.6.1.4.1.935.10.1.1.8.4.1.4ColumnupsEShutdownWarningPeriodIntervalread-writemandatoryThe frequency of sending warning messages to the connected clients when the curresponding shutdown event occurs. The value is in units of seconds.
1.3.6.1.4.1.935.10.1.1.8.5TableupsEControlWeeklyScheduleTablenot-accessiblemandatoryThe table to schedule shutting down the ups by weekly
1.3.6.1.4.1.935.10.1.1.8.5.1RowupsEControlWeeklyScheduleEntrynot-accessiblemandatoryAn entry containing information applicable to a particular line
1.3.6.1.4.1.935.10.1.1.8.5.1.1ColumnupsEControlWeeklyScheduleIndexnot-accessiblemandatorythe index of schedule events.
1.3.6.1.4.1.935.10.1.1.8.5.1.2ColumnupsEWeeklyScheduleShutdownDayread-writemandatorythe weekday on which upsE shoud shutdown
1.3.6.1.4.1.935.10.1.1.8.5.1.3ColumnupsEWeeklyScheduleShutdownTimeread-writemandatoryThe time that the process of shutting down the UPS will be initiated in hh:mm format.
1.3.6.1.4.1.935.10.1.1.8.5.1.4ColumnupsEWeeklyScheduleRestartDayread-writemandatorythe weekday on which the UPS should restart.
1.3.6.1.4.1.935.10.1.1.8.5.1.5ColumnupsEWeeklyScheduleRestartTimeread-writemandatoryThe time the UPS will restart in hh:mm format.
1.3.6.1.4.1.935.10.1.1.8.6TableupsEControlSpecialDayScheduleTablenot-accessiblemandatoryThe table to schedule shutting down the ups.
1.3.6.1.4.1.935.10.1.1.8.6.1RowupsEControlSpecialDayScheduleEntrynot-accessiblemandatoryAn entry containing information applicable to a particular line.
1.3.6.1.4.1.935.10.1.1.8.6.1.1ColumnupsEControlSpecialDayScheduleIndexnot-accessiblemandatoryThe index of special day schedule.
1.3.6.1.4.1.935.10.1.1.8.6.1.2ColumnupsESpecialDayScheduleShutdownDayread-writemandatoryThe special day on which UPS should shutdown with the format of DD/MM/YYYY.
1.3.6.1.4.1.935.10.1.1.8.6.1.3ColumnupsESpecialDayScheduleShutdownTimeread-writemandatoryThe time that the process of shutting down the UPS will be initiated in hh:mm format.
1.3.6.1.4.1.935.10.1.1.8.6.1.4ColumnupsESpecialDayScheduleRestartDayread-writemandatoryThe special day on which the UPS should restart with the format of DD/MM/YYYY.
1.3.6.1.4.1.935.10.1.1.8.6.1.5ColumnupsESpecialDayScheduleRestartTimeread-writemandatoryThe time the UPS will restart in hh:mm format.
1.3.6.1.4.1.935.10.1.1.8.7ScalarupsESystemMasterOffDelayread-onlymandatoryThe UPS output will shutdown after the indicated number of seconds, -1 indicate no action.
1.3.6.1.4.1.935.10.1.1.8.8ScalarupsESystemMasterOnDelayread-onlymandatoryThe UPS output will start on after the indicated number of seconds, -1 indicate no action.
1.3.6.1.4.1.935.10.1.1.9NodeupsETrapControl
1.3.6.1.4.1.935.10.1.1.9.1TableupsETrapsReceiversTablenot-accessiblemandatoryThis table list the managers'IP to send traps to.
1.3.6.1.4.1.935.10.1.1.9.1.1RowupsETrapsReceiversEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.935.10.1.1.9.1.1.1ColumnupsETrapsReceiversIndexnot-accessiblemandatoryThe index to a trap receiver entry
1.3.6.1.4.1.935.10.1.1.9.1.1.2ColumnupsETrapsReceiverAddressread-writemandatoryThe IP address of the manager to send a trap to.
1.3.6.1.4.1.935.10.1.1.9.1.1.3ColumnupsETrapReceiverCommunityStringread-writemandatoryThe community name to use in the trap when sent to the manager.
1.3.6.1.4.1.935.10.1.1.9.1.1.4ColumnupsETrapTyperead-writemandatoryThe type of trap to be received by the manager.
1.3.6.1.4.1.935.10.1.1.9.1.1.5ColumnupsETrapsSeverityLevelread-writemandatoryThe severity level of traps to be received by this manager.
1.3.6.1.4.1.935.10.1.1.9.1.1.6ColumnupsETrapReceiverDescriptionread-writemandatoryDescription of trap receivers
1.3.6.1.4.1.935.10.1.1.9.2ScalarupsETrapStateread-onlymandatorythe values indicate the unrestored traps. For example, after AC fail, the agent send the trap 1(AC Fail) and trap 7(battery on) to NMS. so the value of upsETra…
1.3.6.1.4.1.935.10.1.2NodeupsETraps
1.3.6.1.4.1.935.10.1.2.1NodeupsEPowerFailWARNING: Utility power not available.
1.3.6.1.4.1.935.10.1.2.2NodeupsEPowerRestoredINFORMATION: Utility power has restored.
1.3.6.1.4.1.935.10.1.2.3NodeupsELowBatterySEVERE: The UPS batteries are low and will soon be exhausted.
1.3.6.1.4.1.935.10.1.2.4NodeupsEReturnFromLowBatteryINFORMATION: The UPS has return from a low battery condition.
1.3.6.1.4.1.935.10.1.2.5NodeupsEFailedSEVERE: The UPS is not working fine.
1.3.6.1.4.1.935.10.1.2.6NodeupsEOkINFORMATION: The UPS is working fine.
1.3.6.1.4.1.935.10.1.2.7NodeupsEOnBatteryWARNING: The UPS has switched to battery backup power.
1.3.6.1.4.1.935.10.1.2.8NodeupsENotOnBatteryINFORMATION: The UPS is not on battery power.
1.3.6.1.4.1.935.10.1.2.9NodeupsETestInProgressINFORMATION: The testing is going on ups.
1.3.6.1.4.1.935.10.1.2.10NodeupsETestOverINFORMATION: The testing of UPS is completed.
1.3.6.1.4.1.935.10.1.2.11NodeupsEBypassOnINFORMATION: The UPS has enabled bypass.
1.3.6.1.4.1.935.10.1.2.12NodeupsEOnlineINFORMATION: The UPS is not on Bypass and return to normal status.
1.3.6.1.4.1.935.10.1.2.13NodeupsECommunicationLostSEVERE: Communication to the UPS has been lost.
1.3.6.1.4.1.935.10.1.2.14NodeupsECommunicationEstablishedINFORMATION: Communication with the UPS has been established.
1.3.6.1.4.1.935.10.1.2.15NodeupsEGoingShutdownWARNING: The UPS is going to shutdown output.
1.3.6.1.4.1.935.10.1.2.16NodeupsEShutdownCancelledINFORMATION: The UPS is not going to shutdown output.
1.3.6.1.4.1.935.10.1.2.17NodeupsEOutlet1GoingShutdownWARNING: The UPS is going to shutdown outlet1.
1.3.6.1.4.1.935.10.1.2.18NodeupsEOutlet1ShutdownCancelledINFORMATION: The UPS is not going to shutdown outlet1.
1.3.6.1.4.1.935.10.1.2.19NodeupsEOutlet2GoingShutdownWARNING: The UPS is going to shutdown outlet2.
1.3.6.1.4.1.935.10.1.2.20NodeupsEOutlet2ShutdownCancelledINFORMATION: The UPS is not going to shutdown outlet2.
1.3.6.1.4.1.935.10.1.2.21NodeupsESleepingINFORMATION: UPS has entered sleep mode and power to load has been cut off.
1.3.6.1.4.1.935.10.1.2.22NodeupsEWokeUpINFORMATION: The UPS woke up from sleep mode and power to load has been restored.
1.3.6.1.4.1.935.10.1.2.23NodeupsEOverTemperatureWARNING: The UPS temperature is over the setting limit.
1.3.6.1.4.1.935.10.1.2.24NodeupsENotOverTemperatureINFORMATION: The UPS temperature is not over the setting limit.
1.3.6.1.4.1.935.10.1.2.25NodeupsEOverLoadWARNING: The UPS load is over the setting limit.
1.3.6.1.4.1.935.10.1.2.26NodeupsENotOverLoadINFORMATION: The UPS load is not over the setting limit.
1.3.6.1.4.1.935.10.1.2.27NodeupsEModuleInsertedWARNING: UPS module or charger module plug-in.
1.3.6.1.4.1.935.10.1.2.28NodeupsEModuleRemovedWARNING: UPS module or charger module unplugs.
1.3.6.1.4.1.935.10.1.2.29NodesensorTemperatureTooHighWARNING: Sensor Temperature over high Set point.
1.3.6.1.4.1.935.10.1.2.30NodesensorTemperatureNotHighINFORMATION: Sensor Temperature not over high Set point.
1.3.6.1.4.1.935.10.1.2.31NodesensorTemperatureTooLowWARNING: Sensor Temperature under low Set point.
1.3.6.1.4.1.935.10.1.2.32NodesensorTemperatureNotLowINFORMATION: Sensor Temperature not under low Set point.
1.3.6.1.4.1.935.10.1.2.33NodesensorHumidityTooHighWARNING: Sensor Humidity over high Set point.
1.3.6.1.4.1.935.10.1.2.34NodesensorHumidityNotHighINFORMATION: Sensor Humidity not over high Set point.
1.3.6.1.4.1.935.10.1.2.35NodesensorHumidityTooLowWARNING: Sensor Humidity under low Set point.
1.3.6.1.4.1.935.10.1.2.36NodesensorHumidityNotLowINFORMATION: Sensor Humidity not under low Set point.
1.3.6.1.4.1.935.10.1.2.37NodecontactAlarm1ActiveWARNING: Contact Alarm-1 activated.
1.3.6.1.4.1.935.10.1.2.38NodeconcactAlarm1NormalINFORMATION: Contact Alarm-1 not active.
1.3.6.1.4.1.935.10.1.2.39NodecontactAlarm2ActiveWARNING: Contact Alarm-2 activated.
1.3.6.1.4.1.935.10.1.2.40NodecontactAlarm2NormalINFORMATION: Contact Alarm-2 not active.
1.3.6.1.4.1.935.10.1.2.41NodeupsEInternalwarningWARNING: Internal warning.
1.3.6.1.4.1.935.10.1.2.42NodeupsEReturnFromInternalwarningINFORMATION: Return from Internal warning.
1.3.6.1.4.1.935.10.1.2.43NodeupsEEPOActiveWARNING: EPO Active.
1.3.6.1.4.1.935.10.1.2.44NodeupsEReturnFromEPOActiveINFORMATION: Return from EPO Active.
1.3.6.1.4.1.935.10.1.2.45NodeupsEModuleUnlockWARNING: Module Unlock.
1.3.6.1.4.1.935.10.1.2.46NodeupsEReturnFromModuleUnlockINFORMATION: Return from Module Unlock.
1.3.6.1.4.1.935.10.1.2.47NodeupsEMain1NeutrallossWARNING: Main 1 Neutral loss.
1.3.6.1.4.1.935.10.1.2.48NodeupsEReturnFromMain1NeutrallossINFORMATION: Return from Main 1 Neutral loss.
1.3.6.1.4.1.935.10.1.2.49NodeupsEMain1phaseerrorWARNING: Main 1 phase error.
1.3.6.1.4.1.935.10.1.2.50NodeupsEReturnFromMain1phaseerrorINFORMATION: Return from Main 1 phase error.
1.3.6.1.4.1.935.10.1.2.51NodeupsESitefaultWARNING: Site fault.
1.3.6.1.4.1.935.10.1.2.52NodeupsEReturnFromSitefaultINFORMATION: Return from Site fault.
1.3.6.1.4.1.935.10.1.2.53NodeupsEBypassAbnormalWARNING: Bypass Abnormal.
1.3.6.1.4.1.935.10.1.2.54NodeupsEReturnFromBypassAbnormalINFORMATION: Return from Bypass Abnormal.
1.3.6.1.4.1.935.10.1.2.55NodeupsEBypassPhaseErrorWARNING: Bypass Phase Error.
1.3.6.1.4.1.935.10.1.2.56NodeupsEReturnFromBypassPhaseErrorINFORMATION: Return from Bypass Phase Error.
1.3.6.1.4.1.935.10.1.2.57NodeupsEBatteryOpenWARNING: Battery Open.
1.3.6.1.4.1.935.10.1.2.58NodeupsEReturnFromBatteryOpenINFORMATION: Return from Battery Open.
1.3.6.1.4.1.935.10.1.2.59NodeupsEBatteryOverChargeWARNING: Battery Over Charge.
1.3.6.1.4.1.935.10.1.2.60NodeupsEReturnFromBatteryOverChargeINFORMATION: Return from Battery Over Charge.
1.3.6.1.4.1.935.10.1.2.61NodeupsEBatteryReverseWARNING: Battery Reverse.
1.3.6.1.4.1.935.10.1.2.62NodeupsEReturnFromBatteryReverseINFORMATION: Return from Battery Reverse.
1.3.6.1.4.1.935.10.1.2.63NodeupsEOverloadforewarningWARNING: Overload forewarning.
1.3.6.1.4.1.935.10.1.2.64NodeupsEReturnFromOverloadforewarningINFORMATION: Return from Overload forewarning.
1.3.6.1.4.1.935.10.1.2.65NodeupsEOverloadWarningWARNING: Overload Warning.
1.3.6.1.4.1.935.10.1.2.66NodeupsEReturnFromOverloadWarningINFORMATION: Return from Overload Warning.
1.3.6.1.4.1.935.10.1.2.67NodeupsEFanLockWARNING: Fan Lock.
1.3.6.1.4.1.935.10.1.2.68NodeupsEReturnFromFanLockINFORMATION: Return from Fan Lock.
1.3.6.1.4.1.935.10.1.2.69NodeupsEMaintaincoverisopenWARNING: Maintain cover is open.
1.3.6.1.4.1.935.10.1.2.70NodeupsEReturnFromMaintaincoverisopenINFORMATION: Return from Maintain cover is open.
1.3.6.1.4.1.935.10.1.2.71NodeupsEChargerfaultWARNING: Charger fault.
1.3.6.1.4.1.935.10.1.2.72NodeupsEReturnFromChargerfaultINFORMATION: Return from Charger fault.
1.3.6.1.4.1.935.10.1.2.73NodeupsEModulelocationerrorWARNING: Module location error.
1.3.6.1.4.1.935.10.1.2.74NodeupsEReturnFromModulelocationerrorINFORMATION: Return from Module location error.
1.3.6.1.4.1.935.10.1.2.75NodeupsETurnonabnormalWARNING: Turn on abnormal.
1.3.6.1.4.1.935.10.1.2.76NodeupsEReturnFromTurnonabnormalINFORMATION: Return from Turn on abnormal.
1.3.6.1.4.1.935.10.1.2.77NodeupsERedundancylossWARNING: Redundancy loss.
1.3.6.1.4.1.935.10.1.2.78NodeupsEReturnFromRedundancylossINFORMATION: Return from Redundancy loss.
1.3.6.1.4.1.935.10.1.2.79NodeupsEHotSwapActivedWARNING: Hot Swap Active.
1.3.6.1.4.1.935.10.1.2.80NodeupsEReturnFromHotSwapActivedINFORMATION: Return from Hot Swap Active.
1.3.6.1.4.1.935.10.1.2.81NodeupsEBatteryInformWARNING: Battery Inform.
1.3.6.1.4.1.935.10.1.2.82NodeupsEReturnFromBatteryInformINFORMATION: Return from Battery Inform.
1.3.6.1.4.1.935.10.1.2.83NodeupsEInspectionInformWARNING: Inspection Inform.
1.3.6.1.4.1.935.10.1.2.84NodeupsEReturnFromInspectionInformINFORMATION: Return from Inspection Inform.
1.3.6.1.4.1.935.10.1.2.85NodeupsEGuaranteeInformWARNING: Guarantee Inform.
1.3.6.1.4.1.935.10.1.2.86NodeupsEReturnFromGuaranteeInformINFORMATION: Return from Guarantee Inform.
1.3.6.1.4.1.935.10.1.2.87NodeupsETemperatureLowWARNING: Temperature Low.
1.3.6.1.4.1.935.10.1.2.88NodeupsEReturnFromTemperatureLowINFORMATION: Return from Temperature Low.
1.3.6.1.4.1.935.10.1.2.89NodeupsETemperatureHighWARNING: Temperature High.
1.3.6.1.4.1.935.10.1.2.90NodeupsEReturnFromTemperatureHighINFORMATION: Return from Temperature High.
1.3.6.1.4.1.935.10.1.2.91NodeupsEBatteryOverTemperatureWARNING: Battery Over Temperature.
1.3.6.1.4.1.935.10.1.2.92NodeupsEReturnFromBatteryOverTemperatureINFORMATION: Return from Battery Over Temperature.
1.3.6.1.4.1.935.10.1.2.93NodeupsEFanMaintainInformWARNING: Fan Maintain Inform.
1.3.6.1.4.1.935.10.1.2.94NodeupsEReturnFromFanMaintainInformINFORMATION: Return from Fan Maintain Inform.
1.3.6.1.4.1.935.10.1.2.95NodeupsEBusCapacitanceMaintainInformWARNING: Bus Capacitance Maintain Inform.
1.3.6.1.4.1.935.10.1.2.96NodeupsEReturnFromBusCapacitanceMaintainInformINFORMATION: Return from Bus Capacitance Maintain Inform.
1.3.6.1.4.1.935.10.1.2.97NodeupsESystemOverCapacityWARNING: System Over Capacity.
1.3.6.1.4.1.935.10.1.2.98NodeupsEReturnFromSystemOverCapacityINFORMATION: Return from System Over Capacity.
1.3.6.1.4.1.935.10.1.2.123NodeupsEBelowCapacityLimitSEVERE: The UPS batteries capacity is lower than setting limit.
1.3.6.1.4.1.935.10.1.2.124NodeupsENotBelowCapacityLimitINFORMATION: The UPS batteries capacity is not lower than setting limit.
1.3.6.1.4.1.935.10.1.2.125NodeupsEBelowRemainTimeLimitSEVERE: The UPS batteries backup time is below the setting limit.
1.3.6.1.4.1.935.10.1.2.126NodeupsENotBelowRemainTimeLimitINFORMATION: The UPS batteries backup time is not below the setting limit.
1.3.6.1.4.1.935.10.1.2.127NodeupsELoadSegment1OffWARNING: Load segment 1 is off.
1.3.6.1.4.1.935.10.1.2.128NodeupsELoadSegment1OnINFORMATION: Load segment 1 is on.
1.3.6.1.4.1.935.10.1.2.129NodeupsELoadSegment2OffWARNING: Load segment 2 is off.
1.3.6.1.4.1.935.10.1.2.130NodeupsELoadSegment2OnINFORMATION: Load segment 2 is on.