EPPC-MIB
293 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | Counter enterprises IpAddress |
| SNMPv2-TC | DisplayString |
| UPS-MIB | NonNegativeInteger PositiveInteger |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.935 | Nodeppc | |||
| 1.3.6.1.4.1.935.10 | Nodedevice | |||
| 1.3.6.1.4.1.935.10.1 | NodeupsAgent | |||
| 1.3.6.1.4.1.935.10.1.1 | NodeupsE | |||
| 1.3.6.1.4.1.935.10.1.1.1 | NodeupsEIdentity | |||
| 1.3.6.1.4.1.935.10.1.1.1.1 | ScalarupsEIdentityManufacturer | read-only | mandatory | The name of the UPS manufacturer. |
| 1.3.6.1.4.1.935.10.1.1.1.2 | ScalarupsEIdentityModel | read-only | mandatory | The UPS Model designation. |
| 1.3.6.1.4.1.935.10.1.1.1.3 | ScalarupsEIdentityUPSFirmwareVerison | read-only | mandatory | The UPS firmware/software version(s). |
| 1.3.6.1.4.1.935.10.1.1.1.4 | ScalarupsEIndentityUPSSerialNumber | read-only | mandatory | optional. Most UPS don't supply the value of UPS serial No. |
| 1.3.6.1.4.1.935.10.1.1.1.5 | ScalarupsEIdentityDescription | read-write | mandatory | A string to identify the UPS. This object should be set by the administrator. |
| 1.3.6.1.4.1.935.10.1.1.1.6 | ScalarupsEIdentityAgentSoftwareVerison | read-only | mandatory | The Network Management Card software/firmware version. This variable may or may not have the same value as upsEIdentGroupUPSSoftwareVersion in some implementat… |
| 1.3.6.1.4.1.935.10.1.1.1.7 | ScalarupsEIdentityAttachedDevices | read-write | mandatory | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator |
| 1.3.6.1.4.1.935.10.1.1.2 | NodeupsESystemSummary | |||
| 1.3.6.1.4.1.935.10.1.1.2.1 | ScalarupsESystemStatus | read-only | mandatory | The indication of UPS system status. |
| 1.3.6.1.4.1.935.10.1.1.2.2 | ScalarupsESystemTemperature | read-only | mandatory | The temperature of UPS presented in 0.1 degree. |
| 1.3.6.1.4.1.935.10.1.1.2.3 | ScalarupsESystemWarningCode | read-only | mandatory | The warning code of UPS. Please refer the warning table of 'Q6' for details. |
| 1.3.6.1.4.1.935.10.1.1.2.4 | ScalarupsESystemFaultCode | read-only | mandatory | The fault code of UPS.Please refer the fault code of 'Q6' for details. |
| 1.3.6.1.4.1.935.10.1.1.2.5 | ScalarupsESystemConfigInputVoltage | read-only | mandatory | The magnitude of the nominal input voltage presented in 0.1 V. On those systems which support read-write access to this object, if there is an attempt to set t… |
| 1.3.6.1.4.1.935.10.1.1.2.6 | ScalarupsESystemConfigInputFrequence | read-only | mandatory | The nominal input frequency presented in 0.1 Hz. On those systems which support read-write access to this object, if there is an attempt to set this variable t… |
| 1.3.6.1.4.1.935.10.1.1.2.7 | ScalarupsESystemConfigOutputVoltage | read-only | mandatory | The magnitude of the nominal output voltage presented in 0.1V. On those systems which support read-write access to this object, if there is an attempt to set t… |
| 1.3.6.1.4.1.935.10.1.1.2.8 | ScalarupsESystemConfigOutputFrequency | read-only | mandatory | The nominal output frequency presented in 0.1Hz. On those systems which support read-write access to this object, if there is an attempt to set this variable t… |
| 1.3.6.1.4.1.935.10.1.1.2.9 | ScalarupsESystemConfigOutputVA | read-only | mandatory | The magnitude of the nominal Volt-Amp rating presented in VA. |
| 1.3.6.1.4.1.935.10.1.1.2.10 | ScalarupsESystemConfigOutputPower | read-only | mandatory | The magnitude of the nominal true power rating presented in W . |
| 1.3.6.1.4.1.935.10.1.1.2.11 | ScalarupsESystemConfigOutputLoadHighSetPoint | read-write | mandatory | The maximum output load allowed before the load is too high for UPS operation |
| 1.3.6.1.4.1.935.10.1.1.2.12 | ScalarupsESystemConfigOverTemperatureSetPoint | read-write | mandatory | The maximum temperature allowed before the UPS operation temperature is too high, presented in 0.1 degree. |
| 1.3.6.1.4.1.935.10.1.1.2.13 | ScalarupsESystemInputSourceNum | read-only | mandatory | The present external source of input power. |
| 1.3.6.1.4.1.935.10.1.1.2.14 | ScalarupsESystemInputLineBads | read-only | mandatory | The number of times the Input was out of tolerance in voltage or frequency. Its value should be initialized 0 after agent restarting. |
| 1.3.6.1.4.1.935.10.1.1.2.15 | ScalarupsESystemInputNumPhases | read-only | mandatory | The number of input phase utilized is this device, serves as the table index. This value indicate the device initialized feature. |
| 1.3.6.1.4.1.935.10.1.1.2.16 | TableupsESystemInputTable | not-accessible | mandatory | A list of input table entries. The number of entries is given by the value of upsESystemInputNumPhase. |
| 1.3.6.1.4.1.935.10.1.1.2.16.1 | RowupsESystemInputEntry | not-accessible | mandatory | An entry containing information applicable to a particular input line. |
| 1.3.6.1.4.1.935.10.1.1.2.16.1.1 | ColumnupsESystemInputPhase | not-accessible | mandatory | The number of the phase. Serves as index for input table |
| 1.3.6.1.4.1.935.10.1.1.2.16.1.2 | ColumnupsESystemInputFrequency | read-only | mandatory | The measured input frquency from the UPS meters in 0.1Hz. |
| 1.3.6.1.4.1.935.10.1.1.2.16.1.3 | ColumnupsESystemInputVoltage | read-only | mandatory | The measured input voltage from the UPS meters in 0.1 volts |
| 1.3.6.1.4.1.935.10.1.1.2.16.1.4 | ColumnupsESystemInputCurrent | read-only | mandatory | The measured input mandatory from the UPS meters in 0.1 amps. |
| 1.3.6.1.4.1.935.10.1.1.2.16.1.5 | ColumnupsESystemInputWatts | read-only | mandatory | The measured input real power in watts. |
| 1.3.6.1.4.1.935.10.1.1.2.17 | ScalarupsESystemOutputNumPhase | read-only | mandatory | The number of metered output phases, serves as the table index. This value indicate the device initialized feature. |
| 1.3.6.1.4.1.935.10.1.1.2.18 | TableupsESystemOutputTable | not-accessible | mandatory | A list of output table entries. The number of entries is given by the value of upsESystemOutputNumPhase. |
| 1.3.6.1.4.1.935.10.1.1.2.18.1 | RowupsESystemOutputEntry | not-accessible | mandatory | An entry containing information applicable to a particular line. |
| 1.3.6.1.4.1.935.10.1.1.2.18.1.1 | ColumnupsESystemOutputPhase | not-accessible | mandatory | The number of the phase. Serves as index for output table |
| 1.3.6.1.4.1.935.10.1.1.2.18.1.2 | ColumnupsESystemOutputFrequency | read-only | mandatory | The measured output frequency from the UPS meters in 0.1Hz. |
| 1.3.6.1.4.1.935.10.1.1.2.18.1.3 | ColumnupsESystemOutputVoltage | read-only | mandatory | The measured output voltage from the UPS meters in 0.1 volts |
| 1.3.6.1.4.1.935.10.1.1.2.18.1.4 | ColumnupsESystemOutputCurrent | read-only | mandatory | The measured output mandatory from the UPS meters in 0.1 amps. |
| 1.3.6.1.4.1.935.10.1.1.2.18.1.5 | ColumnupsESystemOutputWatts | read-only | mandatory | The measured output real power in watts. |
| 1.3.6.1.4.1.935.10.1.1.2.18.1.6 | ColumnupsESystemOutputVA | read-only | mandatory | The measured output real complex power in VA. |
| 1.3.6.1.4.1.935.10.1.1.2.18.1.7 | ColumnupsESystemOutputLoad | read-only | mandatory | The UPS output load in percent of rated capacity. |
| 1.3.6.1.4.1.935.10.1.1.2.19 | ScalarupsESystemBypassNumPhase | read-only | mandatory | The number of bypass phases, serves as the table index. This value indicate the device initialized feature |
| 1.3.6.1.4.1.935.10.1.1.2.20 | TableupsESystemBypassTable | not-accessible | mandatory | A list of bypass table entries. The number of entries is given by the value of upsESystemBypassNumPhase. |
| 1.3.6.1.4.1.935.10.1.1.2.20.1 | RowupsESystemBypassEntry | not-accessible | mandatory | An entry containing information applicable to a particular line. |
| 1.3.6.1.4.1.935.10.1.1.2.20.1.1 | ColumnupsESystemBypassPhase | not-accessible | mandatory | The number of the phase. Serves as index for bypass table |
| 1.3.6.1.4.1.935.10.1.1.2.20.1.2 | ColumnupsESystemBypassFrequency | read-only | mandatory | The measured bypass frequency from the UPS meters in 0.1 Hz. |
| 1.3.6.1.4.1.935.10.1.1.2.20.1.3 | ColumnupsESystemBypassVoltage | read-only | mandatory | The measured bypass voltage from the UPS meters in 0.1 volts |
| 1.3.6.1.4.1.935.10.1.1.2.20.1.4 | ColumnupsESystemBypassCurrent | read-only | mandatory | The measured bypass mandatory from the UPS meters in 0.1 amps |
| 1.3.6.1.4.1.935.10.1.1.2.20.1.5 | ColumnupsESystemBypassWatts | read-only | mandatory | The measured bypass input real power in watts. |
| 1.3.6.1.4.1.935.10.1.1.2.21 | ScalarupsESystemConfigBelowCapacityLimit | read-write | mandatory | The UPS batteries capacity(%) limit for shutdown |
| 1.3.6.1.4.1.935.10.1.1.2.22 | ScalarupsESystemConfigBelowRemainTimeLimit | read-write | mandatory | The UPS batteries backup time(minute) limit for shutdown |
| 1.3.6.1.4.1.935.10.1.1.3 | NodeupsEBatterySystem | |||
| 1.3.6.1.4.1.935.10.1.1.3.1 | ScalarupsEBatteryStatus | read-only | mandatory | The status of UPS battery, a value of batteryLow indicates that the battery-low status bit has been set from device. A value of batteryDepleted indicates that … |
| 1.3.6.1.4.1.935.10.1.1.3.2 | ScalarupsESecondsOnBattery | read-only | mandatory | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res… |
| 1.3.6.1.4.1.935.10.1.1.3.3 | ScalarupsEBatteryEstimatedMinutesRemaining | read-only | mandatory | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and… |
| 1.3.6.1.4.1.935.10.1.1.3.4 | ScalarupsEBatteryEstimatedChargeRemaining | read-only | mandatory | An estimate of the battery charge remaining expressed as a percent of full charge |
| 1.3.6.1.4.1.935.10.1.1.3.5 | ScalarupsEPositiveBatteryVoltage | read-only | mandatory | The magnitude of the present positive battery voltage in 0.1 Volt DC |
| 1.3.6.1.4.1.935.10.1.1.3.6 | ScalarupsENegativeBatteryVoltage | read-only | mandatory | The magnitude of the present negative battery voltage in 0.1 Volt DC |
| 1.3.6.1.4.1.935.10.1.1.3.7 | ScalarupsEBatteryCellNumber | read-only | mandatory | This object indicate the cell number of each set. |
| 1.3.6.1.4.1.935.10.1.1.3.8 | ScalarupsEBatteryTemperature | read-only | mandatory | The ambient temperature at or near the UPS Battery casing in 0.1 degree. |
| 1.3.6.1.4.1.935.10.1.1.3.9 | ScalarupsEBatteryLastReplacedDate | read-only | mandatory | The date when the Batteries in this UPS were last replaced. The format should be DD/MM/YYYY. |
| 1.3.6.1.4.1.935.10.1.1.3.10 | ScalarupsEBatteryABMStatus | read-only | mandatory | The status of ABM. |
| 1.3.6.1.4.1.935.10.1.1.3.11 | ScalarupsEChargerModulesNum | read-only | mandatory | The number of charger modules inserted to UPS systems. served as the index of the upsEChargerModulesTable. The default value 0 indicate that the UPS system don… |
| 1.3.6.1.4.1.935.10.1.1.3.12 | TableupsEChargerModulesTable | not-accessible | mandatory | A list of charger modules entries. The number of entries is given by the value of upsEchargerModulesNum. |
| 1.3.6.1.4.1.935.10.1.1.3.12.1 | RowupsEChargerModulesEntry | not-accessible | mandatory | An entry containing information applicable to a particular charger module. |
| 1.3.6.1.4.1.935.10.1.1.3.12.1.1 | ColumnchargerModulesNum | not-accessible | mandatory | The number of charger modules. Serves as index for charger module table |
| 1.3.6.1.4.1.935.10.1.1.3.12.1.2 | ColumnchargerModulesAddress | read-only | mandatory | Charger Modules' address. |
| 1.3.6.1.4.1.935.10.1.1.3.12.1.3 | ColumnpositiveChargeVotlage | read-only | mandatory | The measured positive charger voltage from the UPS meters in 0.1 volts |
| 1.3.6.1.4.1.935.10.1.1.3.12.1.4 | ColumnnegativeChargeVoltage | read-only | mandatory | The measured nepositive charger voltage from the UPS meters in 0.1 volts |
| 1.3.6.1.4.1.935.10.1.1.3.12.1.5 | ColumnpositiveChargeCurrent | read-only | mandatory | The measured positive charger mandatory from the UPS meters in in 0.1 amps. |
| 1.3.6.1.4.1.935.10.1.1.3.12.1.6 | ColumnnegativeChargeCurrent | read-only | mandatory | The measured nepositive charger mandatory from the UPS meters in 0.1 amps. |
| 1.3.6.1.4.1.935.10.1.1.3.12.1.7 | ColumnchargerModulesTemperature | read-only | mandatory | The measured charger temperature from the UPS meters in 0.1 degree. |
| 1.3.6.1.4.1.935.10.1.1.3.12.1.8 | ColumnchargerModulesMode | read-only | mandatory | The working mode of charger modules. |
| 1.3.6.1.4.1.935.10.1.1.4 | NodeupsEPowerConverterSystem | |||
| 1.3.6.1.4.1.935.10.1.1.4.1 | ScalarupsEUPSModulesNum | read-only | mandatory | The number of UPS modules inserted to UPS systems. served as the index of the upsEModulesTable. the default value 0 indicate that the UPS system do not have se… |
| 1.3.6.1.4.1.935.10.1.1.4.2 | TableupsEModulesTable | not-accessible | mandatory | A list of UPS modules entries. The number of entries is given by the value of upsEModulesNum. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1 | RowupsEModulesEntry | not-accessible | mandatory | An entry containing information applicable to a particular upsE module. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.1 | ColumnupsEModulesNum | not-accessible | mandatory | The number of UPS modules. Serves as index for UPS module table |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.2 | ColumnupsEModuleAddress | read-only | mandatory | the address of UPS modules. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.3 | ColumnupsEModulePositiveBusVolt | read-only | mandatory | The measured positive upsE module voltage from the UPS meters in 0.1 volts |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.4 | ColumnupsEModuleNegativeBusVolt | read-only | mandatory | The measured nepositive upsE module voltage from the UPS meters in 0.1 volts |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.5 | ColumnupsEModuleTemperature | read-only | mandatory | The measured upsE module temperature from the UPS meters in 0.1 degree. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.6 | ColumnupsEModuleWorkingMode | read-only | mandatory | The working mode of UPS modules. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.7 | ColumnupsEModuleOutputCurrentR | read-only | mandatory | The measured upsE module output mandatory from the UPS meters in 0.1 A. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.8 | ColumnupsEModuleOutputWattR | read-only | mandatory | The measured upsE module output watts from the UPS meters in watts. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.9 | ColumnupsEModuleOutputLoadR | read-only | mandatory | The output load of UPS modules in %. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.10 | ColumnupsEModuleWarningCode | read-only | mandatory | The warning code of ups modules.Please refer the warning table of 'QU,XX' for details. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.11 | ColumnupsEModuleFaultCode | read-only | mandatory | The fault code of ups modules.Please refer command 'QU,XX' for details. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.12 | ColumnupsEModuleTrapState | read-only | mandatory | the values indicate the unrestored traps. For example, after AC fail, so the value of upsETrapState should be '1'. And then the AC restore, the value of upsEMo… |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.13 | ColumnupsEModuleConfigOutputVA | read-only | mandatory | The magnitude of the nominal Volt-Amp rating presented in VA. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.14 | ColumnupsEModuleOutputCurrentS | read-only | mandatory | The measured upsE module output mandatory from the UPS meters in 0.1 A. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.15 | ColumnupsEModuleOutputCurrentT | read-only | mandatory | The measured upsE module output mandatory from the UPS meters in 0.1 A. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.16 | ColumnupsEModuleOutputWattS | read-only | mandatory | The measured upsE module output watts from the UPS meters in watts. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.17 | ColumnupsEModuleOutputWattT | read-only | mandatory | The measured upsE module output watts from the UPS meters in watts. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.18 | ColumnupsEModuleOutputLoadS | read-only | mandatory | The output load of UPS modules in %. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.19 | ColumnupsEModuleOutputLoadT | read-only | mandatory | The output load of UPS modules in %. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.20 | ColumnupsEModuleOutputVAR | read-only | mandatory | The magnitude of the nominal Volt-Amp rating presented in VA. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.21 | ColumnupsEModuleOutputVAS | read-only | mandatory | The magnitude of the nominal Volt-Amp rating presented in VA. |
| 1.3.6.1.4.1.935.10.1.1.4.2.1.22 | ColumnupsEModuleOutputVAT | read-only | mandatory | The magnitude of the nominal Volt-Amp rating presented in VA. |
| 1.3.6.1.4.1.935.10.1.1.5 | NodeupsELoadSegment | |||
| 1.3.6.1.4.1.935.10.1.1.5.1 | ScalarupsELoadSegment1OffDelay | read-write | mandatory | Setting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less. Setting this object to 0 will cause the shutdown … |
| 1.3.6.1.4.1.935.10.1.1.5.2 | ScalarupsELoadSegment1OnDelay | read-write | mandatory | Setting this object will start the Load segment output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to … |
| 1.3.6.1.4.1.935.10.1.1.5.3 | ScalarupsELoadSegment1AutoOffTimer | read-write | mandatory | The load segment turns automatically off after the delay while the unit operates on battery, but the shutdown is cancelled if the utility return before the del… |
| 1.3.6.1.4.1.935.10.1.1.5.4 | ScalarupsELoadSegment1AutoOnTimer | read-write | mandatory | The load segment is automatically turned on after a selected delay if it has been shutdown due to on battery. |
| 1.3.6.1.4.1.935.10.1.1.5.5 | ScalarupsELoadSegment1State | read-only | mandatory | Load segment output state. |
| 1.3.6.1.4.1.935.10.1.1.5.6 | ScalarupsELoadSegment2OffDelay | read-write | mandatory | Setting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less. Setting this object to 0 will cause the shutdown … |
| 1.3.6.1.4.1.935.10.1.1.5.7 | ScalarupsELoadSegment2OnDelay | read-write | mandatory | Setting this object will start the Load segment output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to … |
| 1.3.6.1.4.1.935.10.1.1.5.8 | ScalarupsELoadSegment2AutoOffTimer | read-write | mandatory | The load segment turns automatically off after the delay while the unit operates on battery, but the shutdown is cancelled if the utility return before the del… |
| 1.3.6.1.4.1.935.10.1.1.5.9 | ScalarupsELoadSegment2AutoOnTimer | read-write | mandatory | The load segment is automatically turned on after a selected delay if it has been shutdown due to on battery. |
| 1.3.6.1.4.1.935.10.1.1.5.10 | ScalarupsELoadSegment2State | read-only | mandatory | Load segment output state. |
| 1.3.6.1.4.1.935.10.1.1.6 | NodeupsEEnvironment | |||
| 1.3.6.1.4.1.935.10.1.1.6.1 | NodeupsEEnvironmentTemperature | |||
| 1.3.6.1.4.1.935.10.1.1.6.1.1 | ScalarupsEEnvironmentCurrentTemperature | read-only | mandatory | The measurement of temperature sensor, in 0.1 degree |
| 1.3.6.1.4.1.935.10.1.1.6.1.2 | ScalarupsEEnvironmentTemperatureHighSetPoint | read-write | mandatory | The set point for high temperature warning, in 0.1 degrees. This value must be greater than upsEEnvironmentTemperatureLowSetPoint, and the least significant di… |
| 1.3.6.1.4.1.935.10.1.1.6.1.3 | ScalarupsEEnvironmentTemperatureHighStatus | read-write | mandatory | To enable/disable high set point check with sensor temperature. |
| 1.3.6.1.4.1.935.10.1.1.6.1.4 | ScalarupsEEnvironmentTemperatureLowSetPoint | read-write | mandatory | The set point for low temperature warning, in 0.1 degrees. This value must be less than upsEEnvironmentTemperatureHighSetPoint, and the least significant digit… |
| 1.3.6.1.4.1.935.10.1.1.6.1.5 | ScalarupsEEnvironmentTemperatureLowStatus | read-write | mandatory | To enable/disable low set point check with sensor temperature. |
| 1.3.6.1.4.1.935.10.1.1.6.1.6 | ScalarupsEEnvironmentTemperatureOffset | read-write | mandatory | The offset to calibrate temperature of EMD, in 0.1 degrees |
| 1.3.6.1.4.1.935.10.1.1.6.2 | NodeupsEEnvironmentHumidity | |||
| 1.3.6.1.4.1.935.10.1.1.6.2.1 | ScalarupsEEnvironmentCurrentHumidity | read-only | mandatory | The measurement of sensor humidity present in %. |
| 1.3.6.1.4.1.935.10.1.1.6.2.2 | ScalarupsEEnvironmentHumidityHighSetPoint | read-write | mandatory | The set point for high humidity warning, in %. This value must be greater than upsEEnvironmentHumidityLowSetPoint. |
| 1.3.6.1.4.1.935.10.1.1.6.2.3 | ScalarupsEEnvironmentHumidityHighStatus | read-write | mandatory | To enable/disable high set point check with emd humidity. |
| 1.3.6.1.4.1.935.10.1.1.6.2.4 | ScalarupsEEnvironmentHumidityLowSetPoint | read-write | mandatory | The set point for low humidity warning, in %. This value must be less than upsEEnvironmentHumidityHighSetPoint. |
| 1.3.6.1.4.1.935.10.1.1.6.2.5 | ScalarupsEEnvironmentHumidityLowStatus | read-write | mandatory | To enable/disable high set point check with emd humidity. |
| 1.3.6.1.4.1.935.10.1.1.6.2.6 | ScalarupsEEnvironmentHumidityOffset | read-write | mandatory | The offset to calibrate humidity of EMD, in %. |
| 1.3.6.1.4.1.935.10.1.1.6.3 | ScalarupsEEnvironmentContactsNum | read-only | mandatory | The number of environment contacts, serves as the table index. |
| 1.3.6.1.4.1.935.10.1.1.6.4 | TableupsEEnvironmentContactTable | not-accessible | mandatory | A list of contacts table entries. The number of entries is given by the value of upsEEnvironmentContactsNum |
| 1.3.6.1.4.1.935.10.1.1.6.4.1 | RowupsEEnvironmentContactEntry | not-accessible | mandatory | An entry containing information applicable to a particular contact |
| 1.3.6.1.4.1.935.10.1.1.6.4.1.1 | ColumnupsEEnvironmentContactIndex | not-accessible | mandatory | The number of environment contacts. Serves as index for environment contact table |
| 1.3.6.1.4.1.935.10.1.1.6.4.1.2 | ColumnupsEEnvironmentContactType | read-write | mandatory | operation type |
| 1.3.6.1.4.1.935.10.1.1.6.4.1.3 | ColumnupsEEnvironmentContactState | read-only | mandatory | The mandatory status. |
| 1.3.6.1.4.1.935.10.1.1.6.4.1.4 | ColumnupsEEnvironmentContactDescription | read-write | mandatory | Description of environment contact. |
| 1.3.6.1.4.1.935.10.1.1.7 | NodeupsEBatteryTest | |||
| 1.3.6.1.4.1.935.10.1.1.7.1 | ScalarupsEBatteryTestStart | read-write | mandatory | This object specify the battery test type and initiate battery test. If battTestWithTime selected, the test time is refer to upsEBatteryTestSettingTime. |
| 1.3.6.1.4.1.935.10.1.1.7.2 | ScalarupsEBatteryTestSettingTime | read-write | mandatory | The object specify the test time for battery test in seconds. |
| 1.3.6.1.4.1.935.10.1.1.7.3 | ScalarupsEBatteryTestResult | read-only | mandatory | This object indicate the test result of battery. |
| 1.3.6.1.4.1.935.10.1.1.7.4 | ScalarupsEBatteryTestStartTime | read-only | mandatory | The value of the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsETestBatt… |
| 1.3.6.1.4.1.935.10.1.1.7.5 | ScalarupsEBatteryTestElapsedTime | read-only | mandatory | The amount of time in format hh:mm:ss, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the valu… |
| 1.3.6.1.4.1.935.10.1.1.7.6 | TableupsEBatteryTestScheduleTable | not-accessible | mandatory | This table describes the schedule for automatically battery test. |
| 1.3.6.1.4.1.935.10.1.1.7.6.1 | RowupsEBatteryTestScheduleEntry | not-accessible | mandatory | An entry containing information applicable to schedule test. |
| 1.3.6.1.4.1.935.10.1.1.7.6.1.1 | ColumnupsEBatteryTestScheduleIndex | not-accessible | mandatory | The index of battery test scheduled. |
| 1.3.6.1.4.1.935.10.1.1.7.6.1.2 | ColumnupsEBatteryTestScheduleDay | read-write | mandatory | The weekday or specaial day on which the UPS should start battery test. |
| 1.3.6.1.4.1.935.10.1.1.7.6.1.3 | ColumnupsEBatteryTestScheduleTime | read-write | mandatory | The time that the battery test will be initiated in hh:mm format. |
| 1.3.6.1.4.1.935.10.1.1.7.6.1.5 | ColumnupsEBatteryTestScheduleType | read-write | mandatory | The type of battery test. |
| 1.3.6.1.4.1.935.10.1.1.7.6.1.6 | ColumnupsEBatteryTestScheduleTestWithTime | read-write | mandatory | The battery time of setting time test in seconds. |
| 1.3.6.1.4.1.935.10.1.1.7.6.1.7 | ColumnupsEBatteryTestScheduleSpecialDay | read-write | mandatory | The special day that the battery test will be initiated in dd/mm/yyyy format. |
| 1.3.6.1.4.1.935.10.1.1.8 | NodeupsEControl | |||
| 1.3.6.1.4.1.935.10.1.1.8.1 | ScalarupsEControlOutputOffDelay | read-write | mandatory | Setting this value to other than zero will cause the UPS output to turn off after the number of seconds. |
| 1.3.6.1.4.1.935.10.1.1.8.2 | ScalarupsEControlOutputOnDelay | read-write | mandatory | Setting this value to other than zero will cause the UPS output to turn on after the number of seconds. |
| 1.3.6.1.4.1.935.10.1.1.8.3 | ScalarupsEControlOutputOnOffControl | read-write | mandatory | upsEOutputOff ( 1 ) indicates the shutdown sequence, upsEOutputOffCancel ( 2 ) indicates cancel the shutdown sequence, upsESleep( 3 ) indicates shutdown UPS fi… |
| 1.3.6.1.4.1.935.10.1.1.8.4 | TableupsEShutdownEventsTable | not-accessible | mandatory | This table describes the parametes for shutdown process when shutdown event occurs |
| 1.3.6.1.4.1.935.10.1.1.8.4.1 | RowupsEShutdownEventsEntry | not-accessible | mandatory | An entry containing information applicable to a particular shutdown event line |
| 1.3.6.1.4.1.935.10.1.1.8.4.1.1 | ColumnupsEShutdownEvent | not-accessible | mandatory | The shutdown event identification |
| 1.3.6.1.4.1.935.10.1.1.8.4.1.2 | ColumnupsEShutdownEventAction | read-write | mandatory | Status of the corresponding shutdown Event. When set to disable(), shutdown process will not start when corresponding event occured. |
| 1.3.6.1.4.1.935.10.1.1.8.4.1.3 | ColumnupsEShutdownwarningPeriodTime | read-write | mandatory | The Delay in seconds after the occurance of the curresponding shutdown event, and warning message should be popped in this period. |
| 1.3.6.1.4.1.935.10.1.1.8.4.1.4 | ColumnupsEShutdownWarningPeriodInterval | read-write | mandatory | The frequency of sending warning messages to the connected clients when the curresponding shutdown event occurs. The value is in units of seconds. |
| 1.3.6.1.4.1.935.10.1.1.8.5 | TableupsEControlWeeklyScheduleTable | not-accessible | mandatory | The table to schedule shutting down the ups by weekly |
| 1.3.6.1.4.1.935.10.1.1.8.5.1 | RowupsEControlWeeklyScheduleEntry | not-accessible | mandatory | An entry containing information applicable to a particular line |
| 1.3.6.1.4.1.935.10.1.1.8.5.1.1 | ColumnupsEControlWeeklyScheduleIndex | not-accessible | mandatory | the index of schedule events. |
| 1.3.6.1.4.1.935.10.1.1.8.5.1.2 | ColumnupsEWeeklyScheduleShutdownDay | read-write | mandatory | the weekday on which upsE shoud shutdown |
| 1.3.6.1.4.1.935.10.1.1.8.5.1.3 | ColumnupsEWeeklyScheduleShutdownTime | read-write | mandatory | The time that the process of shutting down the UPS will be initiated in hh:mm format. |
| 1.3.6.1.4.1.935.10.1.1.8.5.1.4 | ColumnupsEWeeklyScheduleRestartDay | read-write | mandatory | the weekday on which the UPS should restart. |
| 1.3.6.1.4.1.935.10.1.1.8.5.1.5 | ColumnupsEWeeklyScheduleRestartTime | read-write | mandatory | The time the UPS will restart in hh:mm format. |
| 1.3.6.1.4.1.935.10.1.1.8.6 | TableupsEControlSpecialDayScheduleTable | not-accessible | mandatory | The table to schedule shutting down the ups. |
| 1.3.6.1.4.1.935.10.1.1.8.6.1 | RowupsEControlSpecialDayScheduleEntry | not-accessible | mandatory | An entry containing information applicable to a particular line. |
| 1.3.6.1.4.1.935.10.1.1.8.6.1.1 | ColumnupsEControlSpecialDayScheduleIndex | not-accessible | mandatory | The index of special day schedule. |
| 1.3.6.1.4.1.935.10.1.1.8.6.1.2 | ColumnupsESpecialDayScheduleShutdownDay | read-write | mandatory | The special day on which UPS should shutdown with the format of DD/MM/YYYY. |
| 1.3.6.1.4.1.935.10.1.1.8.6.1.3 | ColumnupsESpecialDayScheduleShutdownTime | read-write | mandatory | The time that the process of shutting down the UPS will be initiated in hh:mm format. |
| 1.3.6.1.4.1.935.10.1.1.8.6.1.4 | ColumnupsESpecialDayScheduleRestartDay | read-write | mandatory | The special day on which the UPS should restart with the format of DD/MM/YYYY. |
| 1.3.6.1.4.1.935.10.1.1.8.6.1.5 | ColumnupsESpecialDayScheduleRestartTime | read-write | mandatory | The time the UPS will restart in hh:mm format. |
| 1.3.6.1.4.1.935.10.1.1.8.7 | ScalarupsESystemMasterOffDelay | read-only | mandatory | The UPS output will shutdown after the indicated number of seconds, -1 indicate no action. |
| 1.3.6.1.4.1.935.10.1.1.8.8 | ScalarupsESystemMasterOnDelay | read-only | mandatory | The UPS output will start on after the indicated number of seconds, -1 indicate no action. |
| 1.3.6.1.4.1.935.10.1.1.9 | NodeupsETrapControl | |||
| 1.3.6.1.4.1.935.10.1.1.9.1 | TableupsETrapsReceiversTable | not-accessible | mandatory | This table list the managers'IP to send traps to. |
| 1.3.6.1.4.1.935.10.1.1.9.1.1 | RowupsETrapsReceiversEntry | not-accessible | mandatory | An entry containing information applicable to a particular input line. |
| 1.3.6.1.4.1.935.10.1.1.9.1.1.1 | ColumnupsETrapsReceiversIndex | not-accessible | mandatory | The index to a trap receiver entry |
| 1.3.6.1.4.1.935.10.1.1.9.1.1.2 | ColumnupsETrapsReceiverAddress | read-write | mandatory | The IP address of the manager to send a trap to. |
| 1.3.6.1.4.1.935.10.1.1.9.1.1.3 | ColumnupsETrapReceiverCommunityString | read-write | mandatory | The community name to use in the trap when sent to the manager. |
| 1.3.6.1.4.1.935.10.1.1.9.1.1.4 | ColumnupsETrapType | read-write | mandatory | The type of trap to be received by the manager. |
| 1.3.6.1.4.1.935.10.1.1.9.1.1.5 | ColumnupsETrapsSeverityLevel | read-write | mandatory | The severity level of traps to be received by this manager. |
| 1.3.6.1.4.1.935.10.1.1.9.1.1.6 | ColumnupsETrapReceiverDescription | read-write | mandatory | Description of trap receivers |
| 1.3.6.1.4.1.935.10.1.1.9.2 | ScalarupsETrapState | read-only | mandatory | the values indicate the unrestored traps. For example, after AC fail, the agent send the trap 1(AC Fail) and trap 7(battery on) to NMS. so the value of upsETra… |
| 1.3.6.1.4.1.935.10.1.2 | NodeupsETraps | |||
| 1.3.6.1.4.1.935.10.1.2.1 | NodeupsEPowerFail | WARNING: Utility power not available. | ||
| 1.3.6.1.4.1.935.10.1.2.2 | NodeupsEPowerRestored | INFORMATION: Utility power has restored. | ||
| 1.3.6.1.4.1.935.10.1.2.3 | NodeupsELowBattery | SEVERE: The UPS batteries are low and will soon be exhausted. | ||
| 1.3.6.1.4.1.935.10.1.2.4 | NodeupsEReturnFromLowBattery | INFORMATION: The UPS has return from a low battery condition. | ||
| 1.3.6.1.4.1.935.10.1.2.5 | NodeupsEFailed | SEVERE: The UPS is not working fine. | ||
| 1.3.6.1.4.1.935.10.1.2.6 | NodeupsEOk | INFORMATION: The UPS is working fine. | ||
| 1.3.6.1.4.1.935.10.1.2.7 | NodeupsEOnBattery | WARNING: The UPS has switched to battery backup power. | ||
| 1.3.6.1.4.1.935.10.1.2.8 | NodeupsENotOnBattery | INFORMATION: The UPS is not on battery power. | ||
| 1.3.6.1.4.1.935.10.1.2.9 | NodeupsETestInProgress | INFORMATION: The testing is going on ups. | ||
| 1.3.6.1.4.1.935.10.1.2.10 | NodeupsETestOver | INFORMATION: The testing of UPS is completed. | ||
| 1.3.6.1.4.1.935.10.1.2.11 | NodeupsEBypassOn | INFORMATION: The UPS has enabled bypass. | ||
| 1.3.6.1.4.1.935.10.1.2.12 | NodeupsEOnline | INFORMATION: The UPS is not on Bypass and return to normal status. | ||
| 1.3.6.1.4.1.935.10.1.2.13 | NodeupsECommunicationLost | SEVERE: Communication to the UPS has been lost. | ||
| 1.3.6.1.4.1.935.10.1.2.14 | NodeupsECommunicationEstablished | INFORMATION: Communication with the UPS has been established. | ||
| 1.3.6.1.4.1.935.10.1.2.15 | NodeupsEGoingShutdown | WARNING: The UPS is going to shutdown output. | ||
| 1.3.6.1.4.1.935.10.1.2.16 | NodeupsEShutdownCancelled | INFORMATION: The UPS is not going to shutdown output. | ||
| 1.3.6.1.4.1.935.10.1.2.17 | NodeupsEOutlet1GoingShutdown | WARNING: The UPS is going to shutdown outlet1. | ||
| 1.3.6.1.4.1.935.10.1.2.18 | NodeupsEOutlet1ShutdownCancelled | INFORMATION: The UPS is not going to shutdown outlet1. | ||
| 1.3.6.1.4.1.935.10.1.2.19 | NodeupsEOutlet2GoingShutdown | WARNING: The UPS is going to shutdown outlet2. | ||
| 1.3.6.1.4.1.935.10.1.2.20 | NodeupsEOutlet2ShutdownCancelled | INFORMATION: The UPS is not going to shutdown outlet2. | ||
| 1.3.6.1.4.1.935.10.1.2.21 | NodeupsESleeping | INFORMATION: UPS has entered sleep mode and power to load has been cut off. | ||
| 1.3.6.1.4.1.935.10.1.2.22 | NodeupsEWokeUp | INFORMATION: The UPS woke up from sleep mode and power to load has been restored. | ||
| 1.3.6.1.4.1.935.10.1.2.23 | NodeupsEOverTemperature | WARNING: The UPS temperature is over the setting limit. | ||
| 1.3.6.1.4.1.935.10.1.2.24 | NodeupsENotOverTemperature | INFORMATION: The UPS temperature is not over the setting limit. | ||
| 1.3.6.1.4.1.935.10.1.2.25 | NodeupsEOverLoad | WARNING: The UPS load is over the setting limit. | ||
| 1.3.6.1.4.1.935.10.1.2.26 | NodeupsENotOverLoad | INFORMATION: The UPS load is not over the setting limit. | ||
| 1.3.6.1.4.1.935.10.1.2.27 | NodeupsEModuleInserted | WARNING: UPS module or charger module plug-in. | ||
| 1.3.6.1.4.1.935.10.1.2.28 | NodeupsEModuleRemoved | WARNING: UPS module or charger module unplugs. | ||
| 1.3.6.1.4.1.935.10.1.2.29 | NodesensorTemperatureTooHigh | WARNING: Sensor Temperature over high Set point. | ||
| 1.3.6.1.4.1.935.10.1.2.30 | NodesensorTemperatureNotHigh | INFORMATION: Sensor Temperature not over high Set point. | ||
| 1.3.6.1.4.1.935.10.1.2.31 | NodesensorTemperatureTooLow | WARNING: Sensor Temperature under low Set point. | ||
| 1.3.6.1.4.1.935.10.1.2.32 | NodesensorTemperatureNotLow | INFORMATION: Sensor Temperature not under low Set point. | ||
| 1.3.6.1.4.1.935.10.1.2.33 | NodesensorHumidityTooHigh | WARNING: Sensor Humidity over high Set point. | ||
| 1.3.6.1.4.1.935.10.1.2.34 | NodesensorHumidityNotHigh | INFORMATION: Sensor Humidity not over high Set point. | ||
| 1.3.6.1.4.1.935.10.1.2.35 | NodesensorHumidityTooLow | WARNING: Sensor Humidity under low Set point. | ||
| 1.3.6.1.4.1.935.10.1.2.36 | NodesensorHumidityNotLow | INFORMATION: Sensor Humidity not under low Set point. | ||
| 1.3.6.1.4.1.935.10.1.2.37 | NodecontactAlarm1Active | WARNING: Contact Alarm-1 activated. | ||
| 1.3.6.1.4.1.935.10.1.2.38 | NodeconcactAlarm1Normal | INFORMATION: Contact Alarm-1 not active. | ||
| 1.3.6.1.4.1.935.10.1.2.39 | NodecontactAlarm2Active | WARNING: Contact Alarm-2 activated. | ||
| 1.3.6.1.4.1.935.10.1.2.40 | NodecontactAlarm2Normal | INFORMATION: Contact Alarm-2 not active. | ||
| 1.3.6.1.4.1.935.10.1.2.41 | NodeupsEInternalwarning | WARNING: Internal warning. | ||
| 1.3.6.1.4.1.935.10.1.2.42 | NodeupsEReturnFromInternalwarning | INFORMATION: Return from Internal warning. | ||
| 1.3.6.1.4.1.935.10.1.2.43 | NodeupsEEPOActive | WARNING: EPO Active. | ||
| 1.3.6.1.4.1.935.10.1.2.44 | NodeupsEReturnFromEPOActive | INFORMATION: Return from EPO Active. | ||
| 1.3.6.1.4.1.935.10.1.2.45 | NodeupsEModuleUnlock | WARNING: Module Unlock. | ||
| 1.3.6.1.4.1.935.10.1.2.46 | NodeupsEReturnFromModuleUnlock | INFORMATION: Return from Module Unlock. | ||
| 1.3.6.1.4.1.935.10.1.2.47 | NodeupsEMain1Neutralloss | WARNING: Main 1 Neutral loss. | ||
| 1.3.6.1.4.1.935.10.1.2.48 | NodeupsEReturnFromMain1Neutralloss | INFORMATION: Return from Main 1 Neutral loss. | ||
| 1.3.6.1.4.1.935.10.1.2.49 | NodeupsEMain1phaseerror | WARNING: Main 1 phase error. | ||
| 1.3.6.1.4.1.935.10.1.2.50 | NodeupsEReturnFromMain1phaseerror | INFORMATION: Return from Main 1 phase error. | ||
| 1.3.6.1.4.1.935.10.1.2.51 | NodeupsESitefault | WARNING: Site fault. | ||
| 1.3.6.1.4.1.935.10.1.2.52 | NodeupsEReturnFromSitefault | INFORMATION: Return from Site fault. | ||
| 1.3.6.1.4.1.935.10.1.2.53 | NodeupsEBypassAbnormal | WARNING: Bypass Abnormal. | ||
| 1.3.6.1.4.1.935.10.1.2.54 | NodeupsEReturnFromBypassAbnormal | INFORMATION: Return from Bypass Abnormal. | ||
| 1.3.6.1.4.1.935.10.1.2.55 | NodeupsEBypassPhaseError | WARNING: Bypass Phase Error. | ||
| 1.3.6.1.4.1.935.10.1.2.56 | NodeupsEReturnFromBypassPhaseError | INFORMATION: Return from Bypass Phase Error. | ||
| 1.3.6.1.4.1.935.10.1.2.57 | NodeupsEBatteryOpen | WARNING: Battery Open. | ||
| 1.3.6.1.4.1.935.10.1.2.58 | NodeupsEReturnFromBatteryOpen | INFORMATION: Return from Battery Open. | ||
| 1.3.6.1.4.1.935.10.1.2.59 | NodeupsEBatteryOverCharge | WARNING: Battery Over Charge. | ||
| 1.3.6.1.4.1.935.10.1.2.60 | NodeupsEReturnFromBatteryOverCharge | INFORMATION: Return from Battery Over Charge. | ||
| 1.3.6.1.4.1.935.10.1.2.61 | NodeupsEBatteryReverse | WARNING: Battery Reverse. | ||
| 1.3.6.1.4.1.935.10.1.2.62 | NodeupsEReturnFromBatteryReverse | INFORMATION: Return from Battery Reverse. | ||
| 1.3.6.1.4.1.935.10.1.2.63 | NodeupsEOverloadforewarning | WARNING: Overload forewarning. | ||
| 1.3.6.1.4.1.935.10.1.2.64 | NodeupsEReturnFromOverloadforewarning | INFORMATION: Return from Overload forewarning. | ||
| 1.3.6.1.4.1.935.10.1.2.65 | NodeupsEOverloadWarning | WARNING: Overload Warning. | ||
| 1.3.6.1.4.1.935.10.1.2.66 | NodeupsEReturnFromOverloadWarning | INFORMATION: Return from Overload Warning. | ||
| 1.3.6.1.4.1.935.10.1.2.67 | NodeupsEFanLock | WARNING: Fan Lock. | ||
| 1.3.6.1.4.1.935.10.1.2.68 | NodeupsEReturnFromFanLock | INFORMATION: Return from Fan Lock. | ||
| 1.3.6.1.4.1.935.10.1.2.69 | NodeupsEMaintaincoverisopen | WARNING: Maintain cover is open. | ||
| 1.3.6.1.4.1.935.10.1.2.70 | NodeupsEReturnFromMaintaincoverisopen | INFORMATION: Return from Maintain cover is open. | ||
| 1.3.6.1.4.1.935.10.1.2.71 | NodeupsEChargerfault | WARNING: Charger fault. | ||
| 1.3.6.1.4.1.935.10.1.2.72 | NodeupsEReturnFromChargerfault | INFORMATION: Return from Charger fault. | ||
| 1.3.6.1.4.1.935.10.1.2.73 | NodeupsEModulelocationerror | WARNING: Module location error. | ||
| 1.3.6.1.4.1.935.10.1.2.74 | NodeupsEReturnFromModulelocationerror | INFORMATION: Return from Module location error. | ||
| 1.3.6.1.4.1.935.10.1.2.75 | NodeupsETurnonabnormal | WARNING: Turn on abnormal. | ||
| 1.3.6.1.4.1.935.10.1.2.76 | NodeupsEReturnFromTurnonabnormal | INFORMATION: Return from Turn on abnormal. | ||
| 1.3.6.1.4.1.935.10.1.2.77 | NodeupsERedundancyloss | WARNING: Redundancy loss. | ||
| 1.3.6.1.4.1.935.10.1.2.78 | NodeupsEReturnFromRedundancyloss | INFORMATION: Return from Redundancy loss. | ||
| 1.3.6.1.4.1.935.10.1.2.79 | NodeupsEHotSwapActived | WARNING: Hot Swap Active. | ||
| 1.3.6.1.4.1.935.10.1.2.80 | NodeupsEReturnFromHotSwapActived | INFORMATION: Return from Hot Swap Active. | ||
| 1.3.6.1.4.1.935.10.1.2.81 | NodeupsEBatteryInform | WARNING: Battery Inform. | ||
| 1.3.6.1.4.1.935.10.1.2.82 | NodeupsEReturnFromBatteryInform | INFORMATION: Return from Battery Inform. | ||
| 1.3.6.1.4.1.935.10.1.2.83 | NodeupsEInspectionInform | WARNING: Inspection Inform. | ||
| 1.3.6.1.4.1.935.10.1.2.84 | NodeupsEReturnFromInspectionInform | INFORMATION: Return from Inspection Inform. | ||
| 1.3.6.1.4.1.935.10.1.2.85 | NodeupsEGuaranteeInform | WARNING: Guarantee Inform. | ||
| 1.3.6.1.4.1.935.10.1.2.86 | NodeupsEReturnFromGuaranteeInform | INFORMATION: Return from Guarantee Inform. | ||
| 1.3.6.1.4.1.935.10.1.2.87 | NodeupsETemperatureLow | WARNING: Temperature Low. | ||
| 1.3.6.1.4.1.935.10.1.2.88 | NodeupsEReturnFromTemperatureLow | INFORMATION: Return from Temperature Low. | ||
| 1.3.6.1.4.1.935.10.1.2.89 | NodeupsETemperatureHigh | WARNING: Temperature High. | ||
| 1.3.6.1.4.1.935.10.1.2.90 | NodeupsEReturnFromTemperatureHigh | INFORMATION: Return from Temperature High. | ||
| 1.3.6.1.4.1.935.10.1.2.91 | NodeupsEBatteryOverTemperature | WARNING: Battery Over Temperature. | ||
| 1.3.6.1.4.1.935.10.1.2.92 | NodeupsEReturnFromBatteryOverTemperature | INFORMATION: Return from Battery Over Temperature. | ||
| 1.3.6.1.4.1.935.10.1.2.93 | NodeupsEFanMaintainInform | WARNING: Fan Maintain Inform. | ||
| 1.3.6.1.4.1.935.10.1.2.94 | NodeupsEReturnFromFanMaintainInform | INFORMATION: Return from Fan Maintain Inform. | ||
| 1.3.6.1.4.1.935.10.1.2.95 | NodeupsEBusCapacitanceMaintainInform | WARNING: Bus Capacitance Maintain Inform. | ||
| 1.3.6.1.4.1.935.10.1.2.96 | NodeupsEReturnFromBusCapacitanceMaintainInform | INFORMATION: Return from Bus Capacitance Maintain Inform. | ||
| 1.3.6.1.4.1.935.10.1.2.97 | NodeupsESystemOverCapacity | WARNING: System Over Capacity. | ||
| 1.3.6.1.4.1.935.10.1.2.98 | NodeupsEReturnFromSystemOverCapacity | INFORMATION: Return from System Over Capacity. | ||
| 1.3.6.1.4.1.935.10.1.2.123 | NodeupsEBelowCapacityLimit | SEVERE: The UPS batteries capacity is lower than setting limit. | ||
| 1.3.6.1.4.1.935.10.1.2.124 | NodeupsENotBelowCapacityLimit | INFORMATION: The UPS batteries capacity is not lower than setting limit. | ||
| 1.3.6.1.4.1.935.10.1.2.125 | NodeupsEBelowRemainTimeLimit | SEVERE: The UPS batteries backup time is below the setting limit. | ||
| 1.3.6.1.4.1.935.10.1.2.126 | NodeupsENotBelowRemainTimeLimit | INFORMATION: The UPS batteries backup time is not below the setting limit. | ||
| 1.3.6.1.4.1.935.10.1.2.127 | NodeupsELoadSegment1Off | WARNING: Load segment 1 is off. | ||
| 1.3.6.1.4.1.935.10.1.2.128 | NodeupsELoadSegment1On | INFORMATION: Load segment 1 is on. | ||
| 1.3.6.1.4.1.935.10.1.2.129 | NodeupsELoadSegment2Off | WARNING: Load segment 2 is off. | ||
| 1.3.6.1.4.1.935.10.1.2.130 | NodeupsELoadSegment2On | INFORMATION: Load segment 2 is on. |