LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB

852 objects
The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2018 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
OIDNameAccessStatusDescription
1.3.6.1.4.1.476.1.42.1.11.1IdentityliebertGlobalProductsFlexibleConditionsModuleThe MIB module used to register Liebert SNMP OIDs. Copyright 2000-2018 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on…
1.3.6.1.4.1.476.1.42.3.2.7.1NodelgpFlexConditionsWellKnown
1.3.6.1.4.1.476.1.42.3.2.7.1.4122IdentitylgpCondId4122SystemInputPowerProblemcurrentThe input is not qualified to provide power to the system.
1.3.6.1.4.1.476.1.42.3.2.7.1.4132IdentitylgpCondId4132BypassOverloadPhaseAcurrentAn overload exists on output phase A while operating on the bypass.
1.3.6.1.4.1.476.1.42.3.2.7.1.4133IdentitylgpCondId4133BypassOverloadPhaseBcurrentAn overload exists on output phase B while operating on the bypass.
1.3.6.1.4.1.476.1.42.3.2.7.1.4134IdentitylgpCondId4134BypassOverloadPhaseCcurrentAn overload exists on output phase C while operating on the bypass.
1.3.6.1.4.1.476.1.42.3.2.7.1.4135IdentitylgpCondId4135BypassNotAvailablecurrentA problem associated with the bypass has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4137IdentitylgpCondId4137BypassAutoRetransferPrimedcurrentAutomatic retransfer from bypass to inverter is possible.
1.3.6.1.4.1.476.1.42.3.2.7.1.4138IdentitylgpCondId4138BypassAutoRetransferFailedcurrentAfter performing a recoverable transfer to bypass, an attempt to auto retransfer from bypass to inverter failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4139IdentitylgpCondId4139BypassExcessAutoRetransferscurrentThe number of auto retransfers, from bypass to inverter, has exceeded the maximum for a specified time interval.
1.3.6.1.4.1.476.1.42.3.2.7.1.4140IdentitylgpCondId4140BypassRestartInhibitExternalcurrentRestart of the bypass is inhibited by the state of an external signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.4141IdentitylgpCondId4141BypassBreakerClosedcurrentThe bypass breaker is closed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4142IdentitylgpCondId4142BypassStaticSwitchOverloadcurrentBypass off due to static switch overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.4143IdentitylgpCondId4143BypassStaticSwitchUnavailablecurrentThe static bypass is unavailable to support the critical load.
1.3.6.1.4.1.476.1.42.3.2.7.1.4144IdentitylgpCondId4144BypassExcessivePulseParallelcurrentThe system has performed too many pulse parallel operations within a specified time interval.
1.3.6.1.4.1.476.1.42.3.2.7.1.4145IdentitylgpCondId4145BypassAutoTransferFailedcurrentAn automatic transfer to static bypass failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4146IdentitylgpCondId4146SystemInputPhsRotationErrorcurrentThe power conductors on the input line are not wired to the UPS in the sequence preferred for the rectifier (A-B-C).
1.3.6.1.4.1.476.1.42.3.2.7.1.4147IdentitylgpCondId4147SystemInputCurrentLimitcurrentThe RMS input current has reached the input current limit threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4162IdentitylgpCondId4162BatteryLowcurrentThe calculated battery time remaining has reached the low battery threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4163IdentitylgpCondId4163OutputOffEndofDischargecurrentOutput turned off due to battery reaching end-of-discharge.
1.3.6.1.4.1.476.1.42.3.2.7.1.4164IdentitylgpCondId4164BatteryChargingErrorcurrentThe battery is not charging properly.
1.3.6.1.4.1.476.1.42.3.2.7.1.4165IdentitylgpCondId4165BatteryChargingReducedExtrnlcurrentUsing a reduced battery charging algorithm due to an external signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.4166IdentitylgpCondId4166BatteryCapacityLowcurrentBattery capacity is low.
1.3.6.1.4.1.476.1.42.3.2.7.1.4167IdentitylgpCondId4167OutputOffcurrentOutput is off.
1.3.6.1.4.1.476.1.42.3.2.7.1.4168IdentitylgpCondId4168BatteryDischargingcurrentThe battery is discharging.
1.3.6.1.4.1.476.1.42.3.2.7.1.4169IdentitylgpCondId4169BatteryTemperatureImbalancecurrentExcessive temperature differences between battery sensors detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4170IdentitylgpCondId4170BatteryEqualizecurrentThe rectifier output voltage is increased to equalize the battery voltage level.
1.3.6.1.4.1.476.1.42.3.2.7.1.4171IdentitylgpCondId4171BatteryManualTestInProgresscurrentManual battery test is in progress.
1.3.6.1.4.1.476.1.42.3.2.7.1.4172IdentitylgpCondId4172BatteryAutoTestInProgresscurrentAutomatic battery test is in progress.
1.3.6.1.4.1.476.1.42.3.2.7.1.4173IdentitylgpCondId4173MainBatteryDisconnectOpencurrentMain battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4174IdentitylgpCondId4174BatteryTemperatureSensorFaultcurrentA battery temperature sensor fault has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4175IdentitylgpCondId4175BypassFrequencyErrorcurrentThe bypass frequency is outside the inverter synchronization limits.
1.3.6.1.4.1.476.1.42.3.2.7.1.4176IdentitylgpCondId4176BatteryCircuitBreaker1OpencurrentBattery circuit breaker 1 is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4177IdentitylgpCondId4177BatteryBreaker1OpenFailurecurrentBattery circuit breaker 1 failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4178IdentitylgpCondId4178BatteryBreaker1CloseFailurecurrentBattery circuit breaker 1 failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4179IdentitylgpCondId4179BatteryCircuitBreaker2OpencurrentBattery circuit breaker 2 is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4180IdentitylgpCondId4180BatteryBreaker2OpenFailurecurrentBattery circuit breaker 2 failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4181IdentitylgpCondId4181BatteryBreaker2CloseFailurecurrentBattery circuit breaker 2 failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4182IdentitylgpCondId4182BatteryCircuitBreaker3OpencurrentBattery circuit breaker 3 is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4183IdentitylgpCondId4183BatteryBreaker3OpenFailurecurrentBattery circuit breaker 3 failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4184IdentitylgpCondId4184BatteryBreaker3CloseFailurecurrentBattery circuit breaker 3 failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4185IdentitylgpCondId4185BatteryCircuitBreaker4OpencurrentBattery circuit breaker 4 is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4186IdentitylgpCondId4186BatteryBreaker4OpenFailurecurrentBattery circuit breaker 4 failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4187IdentitylgpCondId4187BatteryBreaker4CloseFailurecurrentBattery circuit breaker 4 failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4188IdentitylgpCondId4188BatteryCircuitBreaker5OpencurrentBattery circuit breaker 5 is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4189IdentitylgpCondId4189BatteryBreaker5OpenFailurecurrentBattery circuit breaker 5 failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4190IdentitylgpCondId4190BatteryBreaker5CloseFailurecurrentBattery circuit breaker 5 failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4191IdentitylgpCondId4191BatteryCircuitBreaker6OpencurrentBattery circuit breaker 6 is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4192IdentitylgpCondId4192BatteryBreaker6OpenFailurecurrentBattery circuit breaker 6 failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4193IdentitylgpCondId4193BatteryBreaker6CloseFailurecurrentBattery circuit breaker 6 failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4194IdentitylgpCondId4194BatteryCircuitBreaker7OpencurrentBattery circuit breaker 7 is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4195IdentitylgpCondId4195BatteryBreaker7OpenFailurecurrentBattery circuit breaker 7 failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4196IdentitylgpCondId4196BatteryBreaker7CloseFailurecurrentBattery circuit breaker 7 failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4197IdentitylgpCondId4197BatteryCircuitBreaker8OpencurrentBattery circuit breaker 8 is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4198IdentitylgpCondId4198BatteryBreaker8OpenFailurecurrentBattery circuit breaker 8 failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4199IdentitylgpCondId4199BatteryBreaker8CloseFailurecurrentBattery circuit breaker 8 failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4200IdentitylgpCondId4200BatteryChargingInhibitedcurrentBattery charging is inhibited due to an external inhibit signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.4213IdentitylgpCondId4213SystemShutdownEPOcurrentSystem shutdown due to Emergency Power Off (EPO).
1.3.6.1.4.1.476.1.42.3.2.7.1.4214IdentitylgpCondId4214SystemShutdownREPOcurrentSystem shutdown due to Remote Emergency Power Off (REPO).
1.3.6.1.4.1.476.1.42.3.2.7.1.4215IdentitylgpCondId4215SystemOutputOffcurrentThe system output is off.
1.3.6.1.4.1.476.1.42.3.2.7.1.4216IdentitylgpCondId4216BypassBackfeedDetectedcurrentThe system detected a voltage on the bypass when none was expected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4217IdentitylgpCondId4217BypassManualXfrInhibitedcurrentManual transfer from inverter to bypass is inhibited - bypass not qualified.
1.3.6.1.4.1.476.1.42.3.2.7.1.4218IdentitylgpCondId4218BypassManualRexfrInhibitedcurrentManual transfer from bypass to inverter is inhibited - inverter output not qualified.
1.3.6.1.4.1.476.1.42.3.2.7.1.4219IdentitylgpCondId4219BatteryOverTemperaturecurrentA battery temperature sensor is reporting a value above a threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4220IdentitylgpCondId4220BatteryExternalMonitor1currentExternal battery monitor 1 - battery maintenance required.
1.3.6.1.4.1.476.1.42.3.2.7.1.4221IdentitylgpCondId4221BatteryExternalMonitor2currentExternal battery monitor 2 - battery maintenance required.
1.3.6.1.4.1.476.1.42.3.2.7.1.4222IdentitylgpCondId4222BatteryGroundFaultcurrentBattery system ground fault amperage exceeds the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4229IdentitylgpCondId4229EmergencyPowerOffLatchedcurrentSystem output is off - 'Emergency Power Off (EPO) - latched' requires manual reset.
1.3.6.1.4.1.476.1.42.3.2.7.1.4230IdentitylgpCondId4230SystemOutputLowPowerFactorcurrentThe system output power factor is low, resulting in reduced output capacity.
1.3.6.1.4.1.476.1.42.3.2.7.1.4231IdentitylgpCondId4231OutputCurrentExceedsThresholdcurrentOutput current for one or more phases exceeds a threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4233IdentitylgpCondId4233InverterFailurecurrentInverter failure - inverter output is off.
1.3.6.1.4.1.476.1.42.3.2.7.1.4234IdentitylgpCondId4234InverterOverloadPhaseAcurrentInverter is operating with an overload on phase A.
1.3.6.1.4.1.476.1.42.3.2.7.1.4235IdentitylgpCondId4235InverterOverloadPhaseBcurrentInverter is operating with an overload on phase B.
1.3.6.1.4.1.476.1.42.3.2.7.1.4236IdentitylgpCondId4236InverterOverloadPhaseCcurrentInverter is operating with an overload on phase C.
1.3.6.1.4.1.476.1.42.3.2.7.1.4237IdentitylgpCondId4237InverterInhibitExternalcurrentRestart of the inverter is inhibited by an external signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.4238IdentitylgpCondId4238InverterOutBreakerOpenFailcurrentInverter output breaker failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4239IdentitylgpCondId4239InverterOutBreakerCloseFailcurrentInverter output breaker failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4270IdentitylgpCondId4270InputContact01currentThe external input contact 1.
1.3.6.1.4.1.476.1.42.3.2.7.1.4271IdentitylgpCondId4271InputContact02currentThe external input contact 2.
1.3.6.1.4.1.476.1.42.3.2.7.1.4272IdentitylgpCondId4272InputContact03currentThe external input contact 3.
1.3.6.1.4.1.476.1.42.3.2.7.1.4273IdentitylgpCondId4273InputContact04currentThe external input contact 4.
1.3.6.1.4.1.476.1.42.3.2.7.1.4274IdentitylgpCondId4274InputContact05currentThe external input contact 5.
1.3.6.1.4.1.476.1.42.3.2.7.1.4275IdentitylgpCondId4275InputContact06currentThe external input contact 6.
1.3.6.1.4.1.476.1.42.3.2.7.1.4276IdentitylgpCondId4276InputContact07currentThe external input contact 7.
1.3.6.1.4.1.476.1.42.3.2.7.1.4277IdentitylgpCondId4277InputContact08currentThe external input contact 8.
1.3.6.1.4.1.476.1.42.3.2.7.1.4278IdentitylgpCondId4278InputContact09currentThe external input contact 9.
1.3.6.1.4.1.476.1.42.3.2.7.1.4279IdentitylgpCondId4279InputContact10currentThe external input contact 10.
1.3.6.1.4.1.476.1.42.3.2.7.1.4280IdentitylgpCondId4280InputContact11currentThe external input contact 11.
1.3.6.1.4.1.476.1.42.3.2.7.1.4281IdentitylgpCondId4281InputContact12currentThe external input contact 12.
1.3.6.1.4.1.476.1.42.3.2.7.1.4282IdentitylgpCondId4282InputContact13currentThe external input contact 13.
1.3.6.1.4.1.476.1.42.3.2.7.1.4283IdentitylgpCondId4283InputContact14currentThe external input contact 14.
1.3.6.1.4.1.476.1.42.3.2.7.1.4284IdentitylgpCondId4284InputContact15currentThe external input contact 15.
1.3.6.1.4.1.476.1.42.3.2.7.1.4285IdentitylgpCondId4285InputContact16currentThe external input contact 16.
1.3.6.1.4.1.476.1.42.3.2.7.1.4286IdentitylgpCondId4286OutputAmpOverUserLimitPhsAcurrentThe phase A output has exceeded the user amperage threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4287IdentitylgpCondId4287OutputAmpOverUserLimitPhsBcurrentThe phase B output has exceeded the user amperage threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4288IdentitylgpCondId4288OutputAmpOverUserLimitPhsCcurrentThe phase C output has exceeded the user amperage threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4289IdentitylgpCondId4289InverterTransferInhibitExtcurrentTransfer of critical bus source to inverter is inhibited by an external signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.4290IdentitylgpCondId4290InverterShutdownOverloadcurrentThe inverter has shutdown due to a sustained overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.4294IdentitylgpCondId4294InletAirOverTemperaturecurrentThe inlet air exceeds the maximum temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4295IdentitylgpCondId4295RectifierFailurecurrentRectifier failure - rectifier is off.
1.3.6.1.4.1.476.1.42.3.2.7.1.4296IdentitylgpCondId4296RectifierOperationInhibitExtcurrentThe operation of the rectifier is inhibited by an external signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.4297IdentitylgpCondId4297UPSOutputonInvertercurrentThe output power is supplied by the inverter.
1.3.6.1.4.1.476.1.42.3.2.7.1.4298IdentitylgpCondId4298UPSOutputonBypasscurrentThe output power is supplied by the bypass.
1.3.6.1.4.1.476.1.42.3.2.7.1.4299IdentitylgpCondId4299OutputLoadonMaintBypasscurrentThe output power is supplied by the maintenance bypass.
1.3.6.1.4.1.476.1.42.3.2.7.1.4300IdentitylgpCondId4300InternalCommunicationsFailurecurrentThe control has detected a communication failure of a component on the internal communication bus.
1.3.6.1.4.1.476.1.42.3.2.7.1.4308IdentitylgpCondId4308DCBusGroundFaultPositivecurrentA ground fault has been detected on the positive DC Bus link.
1.3.6.1.4.1.476.1.42.3.2.7.1.4309IdentitylgpCondId4309DCBusGroundFaultNegativecurrentA ground fault has been detected on the negative DC Bus link.
1.3.6.1.4.1.476.1.42.3.2.7.1.4310IdentitylgpCondId4310EquipmentOverTemperaturecurrentEquipment over temperature summary event.
1.3.6.1.4.1.476.1.42.3.2.7.1.4311IdentitylgpCondId4311SystemFanFailurecurrentSystem fan failure - one or more fans have failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4313IdentitylgpCondId4313PasswordChangedcurrentPassword changed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4314IdentitylgpCondId4314PowerSupplyFailurecurrentPower supply failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4315IdentitylgpCondId4315OnGeneratorcurrentA generator is supplying the power to the system.
1.3.6.1.4.1.476.1.42.3.2.7.1.4316IdentitylgpCondId4316AutoRestartInProgresscurrentAuto restart is in progress.
1.3.6.1.4.1.476.1.42.3.2.7.1.4317IdentitylgpCondId4317AutoRestartInhibitedExtcurrentAuto restart inhibited due to an external signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.4320IdentitylgpCondId4320InitiatedTransfertoBypasscurrentUser initiated manual transfer to bypass.
1.3.6.1.4.1.476.1.42.3.2.7.1.4321IdentitylgpCondId4321InitiatedTransfertoInvertercurrentUser initiated manual transfer to inverter.
1.3.6.1.4.1.476.1.42.3.2.7.1.4322IdentitylgpCondId4322BatteryTestPassedcurrentBattery test passed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4323IdentitylgpCondId4323BatteryTestFailedcurrentBattery test failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4324IdentitylgpCondId4324BatteryTestManuallyStoppedcurrentThe battery test was manually stopped prior to completion.
1.3.6.1.4.1.476.1.42.3.2.7.1.4325IdentitylgpCondId4325BackfeedBreakerOpencurrentThe backfeed breaker is in the open position.
1.3.6.1.4.1.476.1.42.3.2.7.1.4341IdentitylgpCondId4341VelocityAuthenticationFailurecurrentNotification of a message rejected by Velocity due to an authentication failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4360IdentitylgpCondId4360ReceptacleOverCurrentcurrentThe system has detected a receptacle over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4361IdentitylgpCondId4361ReceptacleUnderCurrentcurrentThe system has detected a receptacle under current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4382IdentitylgpCondId4382SystemInputCurrentImbalancecurrentSystem Input Currents are Imbalanced.
1.3.6.1.4.1.476.1.42.3.2.7.1.4383IdentitylgpCondId4383BypassStaticSwitchOffExtrnlcurrentBypass static switch is off due to the state of an external signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.4384IdentitylgpCondId4384BatteryEoDDisconnectcurrentBattery disconnect due to end-of-discharge.
1.3.6.1.4.1.476.1.42.3.2.7.1.4389IdentitylgpCondId4389SystemOutputFaultcurrentA fault has been detected in the system output.
1.3.6.1.4.1.476.1.42.3.2.7.1.4390IdentitylgpCondId4390InverterOffExternalcurrentInverter is off (operation is inhibited) due to external signal state.
1.3.6.1.4.1.476.1.42.3.2.7.1.4391IdentitylgpCondId4391InverterStaticSwitchSCRShortcurrentThe system has detected a short across one or more inverter static switch Silicon Controlled Rectifiers (SCR).
1.3.6.1.4.1.476.1.42.3.2.7.1.4392IdentitylgpCondId4392TemperatureSensorErrorcurrentOne or more temperature sensors cannot provide a valid temperature reading (i.e. sensor failure, wiring failure, sense circuit failure, etc).
1.3.6.1.4.1.476.1.42.3.2.7.1.4406IdentitylgpCondId4406BranchOverCurrentcurrentThe system has detected a module over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4407IdentitylgpCondId4407BranchUnderCurrentcurrentThe system has detected a module under current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4416IdentitylgpCondId4416BranchOverCurrentcurrentThe system has detected a module over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4417IdentitylgpCondId4417BranchUnderCurrentcurrentThe system has detected a module under current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4421IdentitylgpCondId4421BranchFailurecurrentOne or more conditions indicate a Branch Receptacle Module failure , service is required.
1.3.6.1.4.1.476.1.42.3.2.7.1.4436IdentitylgpCondId4436PDUOverCurrentcurrentThe system has detected a module over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4437IdentitylgpCondId4437PDUUnderCurrentcurrentThe system has detected a module under current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4438IdentitylgpCondId4438SystemInternalTemperatureRisecurrentExcessive temperature rise internal to the system (i.e. difference between the output versus input temperature is too large).
1.3.6.1.4.1.476.1.42.3.2.7.1.4439IdentitylgpCondId4439AutomaticRestartFailedcurrentAutomatic restart failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4440IdentitylgpCondId4440FuseFailurecurrentA summary event indicating one or more fuse failures.
1.3.6.1.4.1.476.1.42.3.2.7.1.4441IdentitylgpCondId4441SystemControllerErrorcurrentSystem controller internal error.
1.3.6.1.4.1.476.1.42.3.2.7.1.4442IdentitylgpCondId4442SystemBreakersOpenFailurecurrentOne or more breakers in the system failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4448IdentitylgpCondId4448PDUOverCurrentcurrentThe system has detected a module over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4449IdentitylgpCondId4449PDUUnderCurrentcurrentThe system has detected a module under current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4468IdentitylgpCondId4468PDUOverCurrentL1currentThe system has detected a module over current condition on line 1.
1.3.6.1.4.1.476.1.42.3.2.7.1.4469IdentitylgpCondId4469PDUOverCurrentL2currentThe system has detected a module over current condition on line 2.
1.3.6.1.4.1.476.1.42.3.2.7.1.4470IdentitylgpCondId4470PDUOverCurrentL3currentThe system has detected a module over current condition on line 3.
1.3.6.1.4.1.476.1.42.3.2.7.1.4471IdentitylgpCondId4471PDUUnderCurrentL1currentThe system has detected a module under current condition on line 1.
1.3.6.1.4.1.476.1.42.3.2.7.1.4472IdentitylgpCondId4472PDUUnderCurrentL2currentThe system has detected a module under current condition on line 2.
1.3.6.1.4.1.476.1.42.3.2.7.1.4473IdentitylgpCondId4473PDUUnderCurrentL3currentThe system has detected a module under current condition on line 3.
1.3.6.1.4.1.476.1.42.3.2.7.1.4492IdentitylgpCondId4492ReceptaclePowerStateOncurrentThe receptacle power state changed to the ON state.
1.3.6.1.4.1.476.1.42.3.2.7.1.4493IdentitylgpCondId4493ReceptaclePowerStateOffcurrentThe receptacle power state changed to the OFF state.
1.3.6.1.4.1.476.1.42.3.2.7.1.4494IdentitylgpCondId4494BranchBreakerOpencurrentThe Branch Receptacle Module's input breaker is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.4495IdentitylgpCondId4495DeviceConfigurationChangecurrentDevice Configuration Change.
1.3.6.1.4.1.476.1.42.3.2.7.1.4496IdentitylgpCondId4496BasicDisplayModuleRemovedcurrentBasic Display Module Removed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4497IdentitylgpCondId4497BasicDisplayModuleDiscoveredcurrentBasic Display Module Discovered.
1.3.6.1.4.1.476.1.42.3.2.7.1.4500IdentitylgpCondId4500PDUOverCurrentcurrentThe system has detected a power module over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4501IdentitylgpCondId4501PDUUnderCurrentcurrentThe system has detected a power module under current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4502IdentitylgpCondId4502PDUFailurecurrentOne or more conditions indicate a power module failure, service is required.
1.3.6.1.4.1.476.1.42.3.2.7.1.4503IdentitylgpCondId4503PDUCommunicationFailcurrentInternal communications failure with the Power Module.
1.3.6.1.4.1.476.1.42.3.2.7.1.4504IdentitylgpCondId4504BranchRemovedcurrentBranch Receptacle Module Removed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4505IdentitylgpCondId4505BranchDiscoveredcurrentBranch Receptacle Module Discovered.
1.3.6.1.4.1.476.1.42.3.2.7.1.4506IdentitylgpCondId4506BranchOverCurrentcurrentThe system has detected a Branch Receptacle Module over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4507IdentitylgpCondId4507BranchCurrentcurrentThe system has detected a Branch Receptacle Module under current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4508IdentitylgpCondId4508ReceptacleLoadRemovedcurrentThe receptacle's load stopped drawing power.
1.3.6.1.4.1.476.1.42.3.2.7.1.4509IdentitylgpCondId4509ReceptacleLoadAddedcurrentThe receptacle's load started to draw power.
1.3.6.1.4.1.476.1.42.3.2.7.1.4523IdentitylgpCondId4523ModuleRemovedcurrentModule Removed.
1.3.6.1.4.1.476.1.42.3.2.7.1.4524IdentitylgpCondId4524ModuleAddedcurrentModule Added.
1.3.6.1.4.1.476.1.42.3.2.7.1.4550IdentitylgpCondId4550FirmwareUpdateRequiredcurrentModule compatibility error requires a system firmware update to resolve.
1.3.6.1.4.1.476.1.42.3.2.7.1.4551IdentitylgpCondId4551GenericTestEventcurrentA generic test event designed to evaluate system handling of events.
1.3.6.1.4.1.476.1.42.3.2.7.1.4580IdentitylgpCondId4580OverTemperaturecurrentAn over temperature condition was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4581IdentitylgpCondId4581UnderTemperaturecurrentAn under temperature condition was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4588IdentitylgpCondId4588OverRelativeHumiditycurrentAn over relative humidity condition was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4589IdentitylgpCondId4589UnderRelativeHumiditycurrentAn under relative humidity condition was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4601IdentitylgpCondId4601ExternalAirSensorAOverTemperaturecurrent[Ext Air Sensor A Temperature] has exceeded [External Air Over Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.4604IdentitylgpCondId4604ExternalAirSensorBOverTemperaturecurrent[Ext Air Sensor B Temperature] has exceeded [External Air Over Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.4608IdentitylgpCondId4608ExtAirSensorAUnderTemperaturecurrent[Ext Air Sensor A Temperature] has dropped below [Ext Air Under Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.4611IdentitylgpCondId4611ExtAirSensorBUnderTemperaturecurrent[Ext Air Sensor B Temperature] has dropped below [Ext Air Under Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.4615IdentitylgpCondId4615ExtDewPointOverTemperaturecurrentAt least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded [Ext Dew Point Over Temp Thre…
1.3.6.1.4.1.476.1.42.3.2.7.1.4618IdentitylgpCondId4618ExternalAirSensorAIssuecurrentThe external air sensor A is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.4621IdentitylgpCondId4621ExternalAirSensorBIssuecurrentThe external air sensor B is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.4626IdentitylgpCondId4626SupplyChilledWaterOverTempcurrent[Supply Fluid Temperature] has exceeded [High Supply Fluid Temperature Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.4629IdentitylgpCondId4629SupplyChilledWaterTempSensorIssuecurrentThe supply chilled water temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.4634IdentitylgpCondId4634SupplyRefrigerantOverTempcurrentEvent that is activated when [Supply Refrigerant Temperature] exceeds [Supply Refrig Over Temp Threshold]. The event is deactivated when the temperature drops …
1.3.6.1.4.1.476.1.42.3.2.7.1.4637IdentitylgpCondId4637SupplyRefrigerantUnderTempcurrent[Supply Refrigerant Temperature] has dropped below a specified threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4640IdentitylgpCondId4640SupplyRefrigerantTempSensorIssuecurrentThe supply refrigeramt temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.4645IdentitylgpCondId4645SupplyFluidOverTempcurrent[Supply Fluid Temperature] has exceeded [Supply Fluid Over Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.4648IdentitylgpCondId4648SupplyFluidUnderTempcurrent[Supply Fluid Temperature] has dropped below a specified threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.4651IdentitylgpCondId4651SupplyFluidTempSensorIssuecurrentThe supply fluid temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.4656IdentitylgpCondId4656Pump1LossofFlowcurrentLoss of flow is detected in pump 1. The loss of flow condition occurs when no differential pressure is detected across the pump.
1.3.6.1.4.1.476.1.42.3.2.7.1.4659IdentitylgpCondId4659Pump2LossofFlowcurrentLoss of flow is detected in pump 2. The loss of flow condition occurs when no differential pressure is detected across the pump.
1.3.6.1.4.1.476.1.42.3.2.7.1.4662IdentitylgpCondId4662PumpShortCyclecurrentPumps have short cycled. A short cycle is defined as turning on and off a number of times over a set time period.
1.3.6.1.4.1.476.1.42.3.2.7.1.4669IdentitylgpCondId4669Compressor1AHighHeadPressurecurrentCompressor 1A high head pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4672IdentitylgpCondId4672Compressor1BHighHeadPressurecurrentCompressor 1B high head pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4675IdentitylgpCondId4675Compressor2AHighHeadPressurecurrentCompressor 2A high head pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4678IdentitylgpCondId4678Compressor2BHighHeadPressurecurrentCompressor 2B high head pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4681IdentitylgpCondId4681Compressor1AShortCyclecurrentCompressor 1A short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
1.3.6.1.4.1.476.1.42.3.2.7.1.4684IdentitylgpCondId4684Compressor1BShortCyclecurrentCompressor 1B short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
1.3.6.1.4.1.476.1.42.3.2.7.1.4687IdentitylgpCondId4687Compressor2AShortCyclecurrentCompressor 2A short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
1.3.6.1.4.1.476.1.42.3.2.7.1.4690IdentitylgpCondId4690Compressor2BShortCyclecurrentCompressor 2B short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
1.3.6.1.4.1.476.1.42.3.2.7.1.4693IdentitylgpCondId4693Tandem1LowSuctionPressurecurrent'Tandem compressors' 1 low suction pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4696IdentitylgpCondId4696Tandem2LowSuctionPressurecurrent'Tandem compressors' 2 low suction pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4703IdentitylgpCondId4703ChilledWaterControlValvePositioncurrentChilled water valve out of position. Chilled water control valve position does not match expected value.
1.3.6.1.4.1.476.1.42.3.2.7.1.4711IdentitylgpCondId4711SystemCondensationDetectedcurrentSystem condensation detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4714IdentitylgpCondId4714ShutdownLossOfPowercurrentSystem lost power. This event becomes active when the unit is powered on following an unexpected loss of power.
1.3.6.1.4.1.476.1.42.3.2.7.1.4720IdentitylgpCondId4720SmokeDetectedcurrentSmoke detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4723IdentitylgpCondId4723WaterUnderFloorcurrentWater under the floor is detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4726IdentitylgpCondId4726ServiceRequiredcurrentUnit requires servicing.
1.3.6.1.4.1.476.1.42.3.2.7.1.4729IdentitylgpCondId4729FanIssuecurrentOne or more fans are not operating within their operational parameters.
1.3.6.1.4.1.476.1.42.3.2.7.1.4732IdentitylgpCondId4732ReceptacleLoadDroppedcurrentThe receptacle's load is not drawing power.
1.3.6.1.4.1.476.1.42.3.2.7.1.4740IdentitylgpCondId4740BatteryAutomaticTestInhibitedcurrentAutomatic (scheduled) battery tests are inhibited.
1.3.6.1.4.1.476.1.42.3.2.7.1.4741IdentitylgpCondId4741BatterySelfTestcurrentBattery self test is in progress.
1.3.6.1.4.1.476.1.42.3.2.7.1.4742IdentitylgpCondId4742BatteryLowShutdowncurrentBattery disconnect due to end-of-discharge.
1.3.6.1.4.1.476.1.42.3.2.7.1.4747IdentitylgpCondId4747EquipmentTemperatureSensorFailcurrentOne or more temperature sensors report a temperature outside of the range of expected operation.
1.3.6.1.4.1.476.1.42.3.2.7.1.4749IdentitylgpCondId4749SystemFanFailureRedundantcurrentRedundant system fan failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4750IdentitylgpCondId4750MultipleFanFailurecurrentMultiple fan failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.4753IdentitylgpCondId4753MainControllerFaultcurrentA Main Controller fault has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.4754IdentitylgpCondId4754SystemBreakersCloseFailurecurrentOne or more breakers in the system failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.4755IdentitylgpCondId4755InputFilterCycleLockcurrentThe input filter disconnect is open due to exceeding the maximum number of cycles.
1.3.6.1.4.1.476.1.42.3.2.7.1.4756IdentitylgpCondId4756ServiceCodeActivecurrentService code is running.
1.3.6.1.4.1.476.1.42.3.2.7.1.4757IdentitylgpCondId4757LBSActivecurrentThe Load Bus Sync option is active.
1.3.6.1.4.1.476.1.42.3.2.7.1.4758IdentitylgpCondId4758LBSInhibitedcurrentThe system has detected that conditions to perform Load Bus Sync are not satisfied.
1.3.6.1.4.1.476.1.42.3.2.7.1.4759IdentitylgpCondId4759LeadingPowerFactorcurrentThe leading output Power Factor has fallen below a specified value.
1.3.6.1.4.1.476.1.42.3.2.7.1.4760IdentitylgpCondId4760ControlsResetRequiredcurrentA controls reset is required due to one or more critical settings changing.
1.3.6.1.4.1.476.1.42.3.2.7.1.4823IdentitylgpCondId4823ParallelCommWarningcurrentParallel communication bus warning.
1.3.6.1.4.1.476.1.42.3.2.7.1.4824IdentitylgpCondId4824SystemCommFailcurrentFailure of a device on the multi-module system communication bus.
1.3.6.1.4.1.476.1.42.3.2.7.1.4825IdentitylgpCondId4825LossofRedundancycurrentThe multi-module collection doesn't have enough modules to satisfy the redundancy configuration.
1.3.6.1.4.1.476.1.42.3.2.7.1.4826IdentitylgpCondId4826BPSSStartupInhibitcurrentThe Bypass Static Switch startup is inhibited.
1.3.6.1.4.1.476.1.42.3.2.7.1.4827IdentitylgpCondId4827MMSTransferInhibitcurrentThe critical load can not be manually transferred from inverter to bypass.
1.3.6.1.4.1.476.1.42.3.2.7.1.4828IdentitylgpCondId4828MMSRetransferInhibitcurrentThe critical load can not be manually retransferred from bypass to inverter.
1.3.6.1.4.1.476.1.42.3.2.7.1.4830IdentitylgpCondId4830MMSLossofSyncPulsecurrentMulti-module system loss of sync pulse.
1.3.6.1.4.1.476.1.42.3.2.7.1.4831IdentitylgpCondId4831MMSOverloadcurrentMulti-module system overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.4834IdentitylgpCondId4834MMSOnBatterycurrentThe multi-module system is on battery.
1.3.6.1.4.1.476.1.42.3.2.7.1.4835IdentitylgpCondId4835MMSLowBatteryWarningcurrentMulti-module system low battery warning.
1.3.6.1.4.1.476.1.42.3.2.7.1.4906IdentitylgpCondId4906LowAmbientTemperaturecurrentThe system has detected a low ambient temperature condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4907IdentitylgpCondId4907HighAmbientTemperaturecurrentThe system has detected a high ambient temperature condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4908IdentitylgpCondId4908LowOverallVoltagecurrentThe system has detected a low battery string overall voltage condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4909IdentitylgpCondId4909HighOverallVoltagecurrentThe system has detected a high battery string overall voltage condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4910IdentitylgpCondId4910HighBatteryStringCurrentcurrentThe system has detected a high battery string current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4911IdentitylgpCondId4911LowBatteryStringFloatCurrentcurrentThe system has detected a low battery string float current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4912IdentitylgpCondId4912HighBatteryStringFloatCurrentcurrentThe system has detected a high battery string float current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4913IdentitylgpCondId4913HighBatteryStringRippleCurrentcurrentThe system has detected a high battery string ripple current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4914IdentitylgpCondId4914BatteryStringDischargeDetectedcurrentThe system has detected a battery string discharge condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4915IdentitylgpCondId4915MaximumDischargeTimeExceededcurrentThe system has detected an excessive discharge time condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4916IdentitylgpCondId4916DischargeLowOverallVoltagecurrentThe system has detected a low battery string overall voltage condition during a discharge.
1.3.6.1.4.1.476.1.42.3.2.7.1.4917IdentitylgpCondId4917DischargeLowCellVoltagecurrentThe system has detected a low cell voltage condition during a discharge.
1.3.6.1.4.1.476.1.42.3.2.7.1.4918IdentitylgpCondId4918DischargeHighBatteryStringCurrentcurrentThe system has detected a high battery string current condition during a discharge.
1.3.6.1.4.1.476.1.42.3.2.7.1.4919IdentitylgpCondId4919ExcessiveCelltoCellTemperatureDeviationcurrentThe system has detected an excessive cell to cell temperature deviation condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4920IdentitylgpCondId4920ExcessiveCelltoAmbientTemperatureDeviationcurrentThe system has detected an excessive cell to ambient temperature deviation condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4964IdentitylgpCondId4964LowCellVoltagecurrentThe system has detected a low cell voltage condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4965IdentitylgpCondId4965HighCellVoltagecurrentThe system has detected a high cell voltage condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4966IdentitylgpCondId4966LowCellTemperaturecurrentThe system has detected a low cell temperature condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4967IdentitylgpCondId4967HighCellTemperaturecurrentThe system has detected a high cell temperature condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4968IdentitylgpCondId4968LowInternalResistancecurrentThe system has detected a low internal resistance condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4969IdentitylgpCondId4969HighInternalResistancecurrentThe system has detected a high internal resistance condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4970IdentitylgpCondId4970HighIntercellResistancecurrentThe system has detected a high intercell resistance condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4978IdentitylgpCondId4978IntertierResistanceHighcurrentThe system has detected a high intertier resistance condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.4980IdentitylgpCondId4980SupplyChilledWaterLossofFlowcurrentSupply chilled water or glycol flow is too low.
1.3.6.1.4.1.476.1.42.3.2.7.1.4983IdentitylgpCondId4983SupplyRefrigOverTempBand1current[Supply Refrigerant Temperature] is above the upper threshold specified by [Supply Refrig Temp Band 1].
1.3.6.1.4.1.476.1.42.3.2.7.1.4986IdentitylgpCondId4986SupplyRefrigUnderTempBand1current[Supply Refrigerant Temperature] is below the lower threshold specified by [Supply Refrig Temp Band 1].
1.3.6.1.4.1.476.1.42.3.2.7.1.4990IdentitylgpCondId4990SupplyRefrigOverTempBand2current[Supply Refrigerant Temperature] is above the upper threshold specified by [Supply Refrig Temp Band 2].
1.3.6.1.4.1.476.1.42.3.2.7.1.4993IdentitylgpCondId4993SupplyRefrigUnderTempBand2current[Supply Refrigerant Temperature] is below the lower threshold specified by [Supply Refrig Temp Band 2].
1.3.6.1.4.1.476.1.42.3.2.7.1.4996IdentitylgpCondId4996Inverter1ShortCyclecurrentInverter for pump 1 has short cycled and is temporarily locked out from further operation to protect from thermal overload. A short cycle is defined as powerin…
1.3.6.1.4.1.476.1.42.3.2.7.1.4999IdentitylgpCondId4999Inverter2ShortCyclecurrentInverter for pump 2 has short cycled and is temporarily locked out from further operation to protect from thermal overload. A short cycle is defined as powerin…
1.3.6.1.4.1.476.1.42.3.2.7.1.5015IdentitylgpCondId5015SupplyAirOverTemperaturecurrent[Supply Air Temperature] has exceeded [High Supply Air Temperature Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5019IdentitylgpCondId5019SupplyAirUnderTemperaturecurrent[Supply Air Temperature] has dropped below [Low Supply Air Temperature Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5023IdentitylgpCondId5023ReturnAirOverTemperaturecurrent[Return Air Temperature] has exceeded [High Return Air Temperature Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5026IdentitylgpCondId5026SupplyAirSensorIssuecurrentThe air sensor at the outlet of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5034IdentitylgpCondId5034HighReturnHumiditycurrent[Return Humidity] has exceeded [High Return Humidity Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5036IdentitylgpCondId5036LowReturnHumiditycurrent[Return Humidity] has dropped below [Low Return Humidity Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5037IdentitylgpCondId5037HumidifierHoursExceededcurrentOperating hours for the humidifier have exceeded the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5038IdentitylgpCondId5038DehumidifierHoursExceededcurrentOperating hours for the dehumidifier have exceeded the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5039IdentitylgpCondId5039HumidifierUnderCurrentcurrentThe electrical current to the humidifier has dropped below its lower threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5040IdentitylgpCondId5040HumidifierOverCurrentcurrentThe electrical current to the humidifier has exceeded its upper threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5041IdentitylgpCondId5041HumidifierLowWatercurrentThe water level in the humidifier has dropped below its threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5042IdentitylgpCondId5042HumidifierCylinderWorncurrentHumidifier cylinder is not operating properly and needs to be replaced.
1.3.6.1.4.1.476.1.42.3.2.7.1.5043IdentitylgpCondId5043HumidifierIssuecurrentHumidifier issue detected, causing it to be locked out.
1.3.6.1.4.1.476.1.42.3.2.7.1.5044IdentitylgpCondId5044ExtHumidifierLockoutcurrentThe humidifier is shut down and disabled by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5045IdentitylgpCondId5045HumidifierControlBoardNotDetectedcurrentHumidifier control board is required to be connected, but no signal is detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5046IdentitylgpCondId5046ReturnHumidityOutOfProportionalBandcurrent[Return Humidity] has exceeded the upper limit of [Dehumidification Proportional Band], or has dropped below the lower limit of [Humidification Proportional Ba…
1.3.6.1.4.1.476.1.42.3.2.7.1.5053IdentitylgpCondId5053LossofAirFlowcurrentNo air flow through the unit due to failure of all fans.
1.3.6.1.4.1.476.1.42.3.2.7.1.5054IdentitylgpCondId5054FanHoursExceededcurrentOperating hours for the unit blower fan have exceeded the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5055IdentitylgpCondId5055TopFanIssuecurrentThe top fan is not operating within its normal parameters.
1.3.6.1.4.1.476.1.42.3.2.7.1.5056IdentitylgpCondId5056BottomFanIssuecurrentThe bottom fan is not operating within its normal parameters.
1.3.6.1.4.1.476.1.42.3.2.7.1.5060IdentitylgpCondId5060RemoteSensorIssuecurrentRemote sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5062IdentitylgpCondId5062Compressor1LowSuctionPressurecurrentCompressor 1 low suction pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.5063IdentitylgpCondId5063Compressor1HoursExceededcurrentOperating hours for compressor 1 have exceeded the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5064IdentitylgpCondId5064DigScrollComp1TempSensorIssuecurrentDigital scroll compressor 1 temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5065IdentitylgpCondId5065DigScrollComp1OverTempcurrentDigital scroll compressor 1 shut off because its head temperature has exceeded the upper threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5066IdentitylgpCondId5066Compressor1LowPressureTransducerIssuecurrentCompressor 1 low pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5067IdentitylgpCondId5067ExtCompressorLockoutcurrentThe compressor is shut down and disabled by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5068IdentitylgpCondId5068ReheaterOverTemperaturecurrentThe temperature of the reheater has exceeded its threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5069IdentitylgpCondId5069ElectricReheater1HoursExceededcurrentOperating hours for electric reheater 1 have exceeded the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5070IdentitylgpCondId5070ExtReheatLockoutcurrentThe reheater is shut down and disabled by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5071IdentitylgpCondId5071Condenser1IssuecurrentCondenser 1 is not operating within its normal parameters.
1.3.6.1.4.1.476.1.42.3.2.7.1.5072IdentitylgpCondId5072CondenserVFDIssuecurrentThe condenser fan Variable Frequency Drive is offline.
1.3.6.1.4.1.476.1.42.3.2.7.1.5073IdentitylgpCondId5073CondenserTVSSIssuecurrentThe condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5104IdentitylgpCondId5104ExtOverTemperaturecurrentA temperature has exceeded its threshold, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5105IdentitylgpCondId5105ExtLossofFlowcurrentLoss of flow is detected, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5106IdentitylgpCondId5106ExtCondenserPumpHighWatercurrentHigh water is detected in the condensate pump by the auxiliary float, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5107IdentitylgpCondId5107ExtStandbyGlycolPumpOncurrentThe standby glycol pump is on, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5108IdentitylgpCondId5108ExternalFireDetectedcurrentFire detected, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5109IdentitylgpCondId5109UnitOncurrentUnit was turned on.
1.3.6.1.4.1.476.1.42.3.2.7.1.5110IdentitylgpCondId5110UnitOffcurrentUnit was turned off.
1.3.6.1.4.1.476.1.42.3.2.7.1.5111IdentitylgpCondId5111UnitStandbycurrentUnit was placed in standby mode.
1.3.6.1.4.1.476.1.42.3.2.7.1.5112IdentitylgpCondId5112UnitPartialShutdowncurrentAn event has occurred requiring some system components to be shutdown and disabled.
1.3.6.1.4.1.476.1.42.3.2.7.1.5113IdentitylgpCondId5113UnitShutdowncurrentAn event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system.
1.3.6.1.4.1.476.1.42.3.2.7.1.5114IdentitylgpCondId5114WaterLeakageDetectorSensorIssuecurrentThe water leakage detector sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5115IdentitylgpCondId5115BMSCommunicationsTimeoutcurrentBuilding Management System (or external monitoring system) has not communicated with the system within the expected timeframe.
1.3.6.1.4.1.476.1.42.3.2.7.1.5116IdentitylgpCondId5116MaintenanceDuecurrentThe calculated maintenance date has been reached.
1.3.6.1.4.1.476.1.42.3.2.7.1.5117IdentitylgpCondId5117MaintenanceCompletedcurrentMaintenance has been completed on the unit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5118IdentitylgpCondId5118CloggedAirFiltercurrentAir filter is dirty and needs to be (cleaned or) replaced.
1.3.6.1.4.1.476.1.42.3.2.7.1.5119IdentitylgpCondId5119RAMBatteryIssuecurrentRAM or RAM backup battery is not operating correctly.
1.3.6.1.4.1.476.1.42.3.2.7.1.5120IdentitylgpCondId5120MasterUnitCommunicationLostcurrentCommunication with master unit has been lost.
1.3.6.1.4.1.476.1.42.3.2.7.1.5121IdentitylgpCondId5121HighPowerShutdowncurrentSupply to high power components has been shutdown.
1.3.6.1.4.1.476.1.42.3.2.7.1.5126IdentitylgpCondId5126DigScrollComp2OverTempcurrentDigital scroll compressor 2 shut off because its head temperature has exceeded the upper threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5144IdentitylgpCondId5144OutputOfUfcurrentThe output frequency has exceeded a specified range for a specified period of time.
1.3.6.1.4.1.476.1.42.3.2.7.1.5145IdentitylgpCondId5145MMSModuleAlarmActivecurrentActive alarm or fault of any module in a multi-module system.
1.3.6.1.4.1.476.1.42.3.2.7.1.5146IdentitylgpCondId5146CompressorPumpDownIssuecurrentUnable to pump down suction-side pressure during compressor shutdown.
1.3.6.1.4.1.476.1.42.3.2.7.1.5147IdentitylgpCondId5147ReturnAirSensorIssuecurrentThe air sensor at the inlet of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5148IdentitylgpCondId5148CompressorHighPressureTransducerIssuecurrentCompressor high pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5149IdentitylgpCondId5149BatteryNotQualifiedcurrentThe UPS battery voltage is not qualified. This event will be detected even in the absence of battery disconnect or when it is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.5150IdentitylgpCondId5150BatteryTerminalsReversedcurrentThe measured battery voltage is a negative value due to reverse battery terminal connections.
1.3.6.1.4.1.476.1.42.3.2.7.1.5151IdentitylgpCondId5151BatteryConverterFailurecurrentBattery converter failure. This is a summary event caused by one or more power sub-modules in a UPS module.
1.3.6.1.4.1.476.1.42.3.2.7.1.5152IdentitylgpCondId5152InverterSCROpencurrentThe system has detected an open across one or more inverter static switch Silicon Controlled Rectifiers.
1.3.6.1.4.1.476.1.42.3.2.7.1.5153IdentitylgpCondId5153LoadSharingFaultcurrentDifference between any phase inverter current of unit and the relevant average output current of parallel system is more than a specific percent of nominal cur…
1.3.6.1.4.1.476.1.42.3.2.7.1.5154IdentitylgpCondId5154DCBusAbnormalcurrentThe system has detected an abnormal DC Bus Voltage.
1.3.6.1.4.1.476.1.42.3.2.7.1.5155IdentitylgpCondId5155MainsInputNeutralLostcurrentLoss of neutral in the input source is detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5156IdentitylgpCondId5156LoadImpactTransfercurrentOn bypass as result of load impact.
1.3.6.1.4.1.476.1.42.3.2.7.1.5157IdentitylgpCondId5157UserOperationInvalidcurrentUser attempted an invalid operation.
1.3.6.1.4.1.476.1.42.3.2.7.1.5158IdentitylgpCondId5158PowerSubModuleFaultcurrentOne or more failures detected in power module, inverter or rectifier.
1.3.6.1.4.1.476.1.42.3.2.7.1.5178IdentitylgpCondId5178OutputOvervoltagecurrentOne or more of the output phase voltages has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5179IdentitylgpCondId5179OutputUndervoltagecurrentOne or more of the output phase voltages has dropped below the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5180IdentitylgpCondId5180OutputOvercurrentcurrentOne or more of the phase currents has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5181IdentitylgpCondId5181NeutralOvercurrentcurrentThe system's neutral current has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5182IdentitylgpCondId5182GroundOvercurrentcurrentSystem ground current has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5183IdentitylgpCondId5183OutputVoltageTHDcurrentThe Total Harmonic Distortion of the voltage on one or more of the output phases has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5184IdentitylgpCondId5184OutputFrequencyErrorcurrentThe output frequency is outside a specified range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5185IdentitylgpCondId5185TransformerOvertemperaturecurrentIndicates a unit transformer overtemperature condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5212IdentitylgpCondId5212PanelSummaryStatuscurrentThe status for the panel. Detects and annunciates upon occurrence of any branch or panelboard main breaker active event.
1.3.6.1.4.1.476.1.42.3.2.7.1.5213IdentitylgpCondId5213PanelOvervoltagecurrentOne or more of the phase voltages of this panel has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5214IdentitylgpCondId5214PanelUndervoltagecurrentOne or more of the phase voltages of this panel is less than the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5215IdentitylgpCondId5215PanelOvercurrentcurrentOne or more of the phase currents of this panel has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5216IdentitylgpCondId5216PanelNeutralOvercurrentcurrentThe Neutral current of this panel has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5217IdentitylgpCondId5217PanelGroundOvercurrentcurrentThe Ground current of this panel has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5226IdentitylgpCondId5226BranchOvercurrentcurrentThe current in one or more phases of this branch exceeds the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5227IdentitylgpCondId5227BranchUndercurrentcurrentThe current in one or more phases of this branch is less than the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5245IdentitylgpCondId5245SubfeedPhaseOvercurrentcurrentOne or more of the phase currents in this subfeed has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5246IdentitylgpCondId5246SubfeedNeutralOvercurrentcurrentThe Neutral current in this subfeed has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5247IdentitylgpCondId5247SubfeedGroundOvercurrentcurrentThe Ground current of this subfeed has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5249IdentitylgpCondId5249EventStatecurrentThe present state of this digital event input.
1.3.6.1.4.1.476.1.42.3.2.7.1.5263IdentitylgpCondId5263CompressorNotStoppingcurrentCompressor commanded to stop, but continues to run.
1.3.6.1.4.1.476.1.42.3.2.7.1.5269IdentitylgpCondId5269CompressorHoursExceededcurrent[Compressor Hours] has exceeded [Compressor Hours Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5270IdentitylgpCondId5270CompressorHighHeadPressurecurrentCompressor is shut down due to high head pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.5271IdentitylgpCondId5271CompressorLowSuctionPressurecurrentCompressor is shut down due to low suction pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.5272IdentitylgpCondId5272CompressorThermalOverloadcurrentCompressor is shut down due to thermal overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.5273IdentitylgpCondId5273CompressorLowOilPressurecurrentCompressor low oil pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.5274IdentitylgpCondId5274CompressorHeadPressureOverThresholdcurrentCompressor head pressure has exceeded an upper threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5275IdentitylgpCondId5275CompressorLossofDifferentialPressurecurrentCompressor is shut down due to low differential pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.5277IdentitylgpCondId5277CondenserFanIssuecurrentCondenser fan is not operating within its operational parameters.
1.3.6.1.4.1.476.1.42.3.2.7.1.5278IdentitylgpCondId5278LowCondenserRefrigerantPressurecurrentRefrigerant pressure in condenser coil is too low.
1.3.6.1.4.1.476.1.42.3.2.7.1.5280IdentitylgpCondId5280LowFluidPressurecurrent[Fluid Pressure] has dropped below a specified threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5293IdentitylgpCondId5293ReturnFluidOverTempcurrent[Return Fluid Temperature] has exceeded a specified threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5294IdentitylgpCondId5294ReturnFluidUnderTempcurrent[Return Fluid Temperature] has dropped below a specified threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5295IdentitylgpCondId5295ReturnFluidTempSensorIssuecurrentThe return fluid temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5296IdentitylgpCondId5296TeamworkReturnFluidTempSensorIssuecurrentThe return fluid temperature sensors for all Teamwork units are disconnected or the signals are out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5297IdentitylgpCondId5297AllPumpsLossofFlowcurrentSystem is shut down due to loss of flow in all available pumps.
1.3.6.1.4.1.476.1.42.3.2.7.1.5300IdentitylgpCondId5300PumpHoursExceededcurrent[Pump Hours] has exceeded [Pump Hours Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5306IdentitylgpCondId5306FreeCoolingValveHoursExceededcurrent[Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5308IdentitylgpCondId5308EvaporatorInletTempSensorIssuecurrentThe evaporator inlet temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5309IdentitylgpCondId5309TeamworkEvaporatorInletTempSensorIssuecurrentThe evaporator inlet temperature sensors for all Teamwork units are disconnected or the signals are out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5310IdentitylgpCondId5310EvaporatorFluidFreezeAutoResetcurrentEvaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down, but will restart when the temperature rises above th…
1.3.6.1.4.1.476.1.42.3.2.7.1.5311IdentitylgpCondId5311EvaporatorFluidFreezeManualResetRequiredcurrentEvaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down and requires a manual reset.
1.3.6.1.4.1.476.1.42.3.2.7.1.5315IdentitylgpCondId5315SubgroupEventOccurredDuringCommunicationLosscurrentWhile subgroup unit communication was lost, an event occurred on the subgroup unit. Please check subgroup unit event log.
1.3.6.1.4.1.476.1.42.3.2.7.1.5335IdentitylgpCondId5335ReturnAirUnderTemperaturecurrent[Return Air Temperature] has dropped below [Low Return Air Temperature Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5349IdentitylgpCondId5349ExtAirSensorAHighHumiditycurrent[Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High Humidity Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5351IdentitylgpCondId5351ExtAirSensorALowHumiditycurrent[Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A Low Humidity Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5352IdentitylgpCondId5352CompressorShortCyclecurrentCompressor short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
1.3.6.1.4.1.476.1.42.3.2.7.1.5354IdentitylgpCondId5354DigScrollCompDischargeTempSensorIssuecurrentDigital scroll compressor discharge temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5355IdentitylgpCondId5355DigScrollCompOverTempcurrentDigital scroll compressor is shut down due to head temperature exceeding an upper threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5361IdentitylgpCondId5361ExtFreeCoolingLockoutcurrentFree cooling is disabled by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5362IdentitylgpCondId5362FreeCoolingTempSensorIssuecurrentThe free cooling fluid temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5365IdentitylgpCondId5365HotWaterHotGasValveHoursExceededcurrent[Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot Gas Valve Hours Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5368IdentitylgpCondId5368ElectricReheaterHoursExceededcurrent[Electric Reheater Hours] has exceeded [Electric Reheaters Hours Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5376IdentitylgpCondId5376MainFanOverloadcurrentMain fan is shut down due to thermal overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.5377IdentitylgpCondId5377CondensercurrentCondenser is not operating within its operational parameters.
1.3.6.1.4.1.476.1.42.3.2.7.1.5415IdentitylgpCondId5415ExtLossofAirBlowercurrentLoss of air blower is detected, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5416IdentitylgpCondId5416ExtStandbyUnitOncurrentStandby unit is on, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5417IdentitylgpCondId5417DigitalOutputBoardNotDetectedcurrentDigital output board is required to be connected, but no signal is detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5418IdentitylgpCondId5418UnitCodeMissingcurrentUnit code has not been entered and saved.
1.3.6.1.4.1.476.1.42.3.2.7.1.5419IdentitylgpCondId5419UnitCommunicationLostcurrentMaster has lost communication with one or more networked units.
1.3.6.1.4.1.476.1.42.3.2.7.1.5422IdentitylgpCondId5422OvertemperaturePowerOffcurrentPower turned off because equipment over temperature limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5423IdentitylgpCondId5423TooManySensorscurrentThe number of sensors connected to the PDU exceeds the allowable limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5432IdentitylgpCondId5432TransformerOvertemperaturePowerOffcurrentOutput power shutdown due to high transformer temperature.
1.3.6.1.4.1.476.1.42.3.2.7.1.5433IdentitylgpCondId5433TransformerOvertemperaturecurrentTransformer temperature has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5434IdentitylgpCondId5434TransformerTemperatureSensorFailcurrentTransformer temperature sensor has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5436IdentitylgpCondId5436LowAmbientTemperatureProbeTwocurrentThe system has detected a low ambient temperature condition on temperature probe 2.
1.3.6.1.4.1.476.1.42.3.2.7.1.5437IdentitylgpCondId5437HighAmbientTemperatureProbeTwocurrentThe system has detected a high ambient temperature condition on temperature probe 2.
1.3.6.1.4.1.476.1.42.3.2.7.1.5438IdentitylgpCondId5438ThermalRunawayDetectedcurrentThe system has detected a thermal runaway condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5439IdentitylgpCondId5439BatteryStringEqualizecurrentThe system has detected a battery string equalize condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5440IdentitylgpCondId5440BatteryStringOfflinecurrentThe system has detected the battery string is offline.
1.3.6.1.4.1.476.1.42.3.2.7.1.5442IdentitylgpCondId5442DischargeLowCellVoltagecurrentThe system has detected a low cell voltage condition during a discharge.
1.3.6.1.4.1.476.1.42.3.2.7.1.5447IdentitylgpCondId5447MMSPowerSharingcurrentA module is not sharing power with the other modules in a multi -module system.
1.3.6.1.4.1.476.1.42.3.2.7.1.5453IdentitylgpCondId5453ModuleInStandbyIntelligentParallelingcurrentModule is placed into standby operation per Intelligent Paralleling.
1.3.6.1.4.1.476.1.42.3.2.7.1.5456IdentitylgpCondId5456ECOModeActivecurrentConditions for Activation or Automatic Reactivation have been satisfied.
1.3.6.1.4.1.476.1.42.3.2.7.1.5457IdentitylgpCondId5457ECOModeSuspendedcurrentECO Mode session is suspended.
1.3.6.1.4.1.476.1.42.3.2.7.1.5458IdentitylgpCondId5458ExcessECOSuspendscurrentNumber of automatic suspensions has exceeded the ECO Mode - Maximum Auto Suspensions setting.
1.3.6.1.4.1.476.1.42.3.2.7.1.5471IdentitylgpCondId5471DoorOpencurrentAn open door was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5472IdentitylgpCondId5472DoorSensorDisconnectedcurrentDoor sensor disconnect detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5479IdentitylgpCondId5479ContactClosureOpencurrentAn open circuit was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5480IdentitylgpCondId5480ContactClosureClosedcurrentA closed circuit was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5492IdentitylgpCondId5492ExtSystemCondensationDetectedcurrentExternal system condensation detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5495IdentitylgpCondId5495ExtFanIssuecurrentOne or more fans are not operating within their operational parameters.
1.3.6.1.4.1.476.1.42.3.2.7.1.5500IdentitylgpCondId5500ExtRemoteShutdowncurrentUnit is shut down by a remote signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5505IdentitylgpCondId5505HotAisleTempOutofRangecurrentThe air temperature in the Hot aisle is either above [Hot Aisle Over Temp Threshold] or below [Hot Aisle Under Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5508IdentitylgpCondId5508ColdAisleTempOutofRangecurrentThe air temperature in the cold aisle is either above [Cold Aisle Over Temp Threshold] or below [Cold Aisle Under Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5512IdentitylgpCondId5512RemoteShutdowncurrentUnit is shut down by a remote signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5513IdentitylgpCondId5513CompressorCapacityReducedcurrentCompressor capacity has been reduced.
1.3.6.1.4.1.476.1.42.3.2.7.1.5514IdentitylgpCondId5514CompressorLowPressureTransducerIssuecurrentCompressor low pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5524IdentitylgpCondId5524PDUNeutralOverCurrentcurrentThe system has detected a neutral over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5531IdentitylgpCondId5531CondenserCommunicationLostcurrentCommunication with condenser unit has been lost.
1.3.6.1.4.1.476.1.42.3.2.7.1.5535IdentitylgpCondId5535CondenserOutsideAirTempSensorIssuecurrentCondenser outside air temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5536IdentitylgpCondId5536CondenserOutsideAirTempOutofOperatingRangecurrent[Condenser Outside Air Temperature] is either above an upper threshold or below a lower threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5537IdentitylgpCondId5537CondenserControlBoardIssuecurrentThe condenser control board is reporting an issue.
1.3.6.1.4.1.476.1.42.3.2.7.1.5539IdentitylgpCondId5539CondenserRefrigerantPressureOverThresholdcurrentCondenser refrigerant pressure has exceeded a threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5540IdentitylgpCondId5540CondenserRefrigerantPressureUnderThresholdcurrentCondenser refrigerant pressure has dropped below a threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5541IdentitylgpCondId5541CondenserRefrigerantPressureSensorIssuecurrentCondenser refrigerant pressure sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5542IdentitylgpCondId5542CondenserSupplyRefrigerantOverTempcurrentCondenser supply refrigerant temperature has exceeded a threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5543IdentitylgpCondId5543CondenserSupplyRefrigerantUnderTempcurrentCondenser supply refrigerant temperature has dropped below a specified threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5544IdentitylgpCondId5544CondenserSupplyRefrigerantTempSensorIssuecurrentCondenser supply refrigerant temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5545IdentitylgpCondId5545CondenserMaxFanSpeedOverridecurrentFan speed exceeding the maximum set point in order to alleviate a high temperature or pressure condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5559IdentitylgpCondId5559EvaporatorReturnFluidOverTempcurrent[Evaporator Return Fluid Temperature] has exceeded a threshold. The event is deactivated when the temperature drops below the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5560IdentitylgpCondId5560EvaporatorReturnFluidUnderTempcurrent[Evaporator Return Fluid Temperature] has dropped below a threshold. The event is deactivated when the temperature rises above the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5561IdentitylgpCondId5561LBSActiveMastercurrentThis UPS system has been selected as the functional Master Load Bus Synchronization (LBS) system.
1.3.6.1.4.1.476.1.42.3.2.7.1.5562IdentitylgpCondId5562LBSActiveSlavecurrentThis UPS system is synchronized to the output bus of the UPS system that has been selected as the Master Load Bus Synchronization (LBS) system.
1.3.6.1.4.1.476.1.42.3.2.7.1.5563IdentitylgpCondId5563DCBusLowFaultcurrentThe DC Bus voltage has reached a critical low level.
1.3.6.1.4.1.476.1.42.3.2.7.1.5564IdentitylgpCondId5564FanContactorOpencurrentThe fan contactor is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.5565IdentitylgpCondId5565FanContactorOpenFailcurrentThe fan contactor failed to open.
1.3.6.1.4.1.476.1.42.3.2.7.1.5566IdentitylgpCondId5566FanContactorCloseFailcurrentThe fan contactor failed to close.
1.3.6.1.4.1.476.1.42.3.2.7.1.5567IdentitylgpCondId5567IPInhibitcurrentThe intelligent paralleling operation is inhibited.
1.3.6.1.4.1.476.1.42.3.2.7.1.5568IdentitylgpCondId5568InputUndervoltagecurrentOne or more of the input phase voltages has dropped below the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5569IdentitylgpCondId5569InputOvervoltagecurrentOne or more of the input phase voltages has exceeded the limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5573IdentitylgpCondId5573AmbientAirSensorIssuecurrentAmbient air sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5577IdentitylgpCondId5577ExtDewPointUnderTemperaturecurrentAt least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped below [Ext Dew Point Under Tem…
1.3.6.1.4.1.476.1.42.3.2.7.1.5578IdentitylgpCondId5578DewPointOverTemperaturecurrentDew point temperature reading has exceeded the upper threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5579IdentitylgpCondId5579DewPointUnderTemperaturecurrentDew point temperature reading has dropped below the lower threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5588IdentitylgpCondId5588UnspecifiedGeneralEventcurrentOne or more unspecified events active. See local unit display for further details.
1.3.6.1.4.1.476.1.42.3.2.7.1.5593IdentitylgpCondId5593RemoteSensorAverageOverTemperaturecurrent[Remote Sensor Average Temperature] has exceeded [Remote Sensor Over Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5594IdentitylgpCondId5594RemoteSensorAverageUnderTemperaturecurrent[Remote Sensor Average Temperature] has dropped below [Remote Sensor Under Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5595IdentitylgpCondId5595RemoteSensorSystemAverageOverTemperaturecurrent[Remote Sensor System Average Temperature] has exceeded [Remote Sensor Over Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5596IdentitylgpCondId5596RemoteSensorSystemAverageUnderTemperaturecurrent[Remote Sensor System Average Temperature] has dropped below [Remote Sensor Under Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5597IdentitylgpCondId5597RemoteSensorOverTemperaturecurrent[Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5598IdentitylgpCondId5598RemoteSensorUnderTemperaturecurrent[Remote Sensor Temperature] has dropped below [Remote Sensor Under Temp Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.5600IdentitylgpCondId5600AirEconomizerEmergencyOverridecurrentIndoor room temperature has exceeded its upper threshold and the outdoor air damper has been opened for emergency cooling.
1.3.6.1.4.1.476.1.42.3.2.7.1.5601IdentitylgpCondId5601AirEconomizerReducedAirflowcurrentAir economizer filter is dirty and needs to be cleaned or replaced.
1.3.6.1.4.1.476.1.42.3.2.7.1.5604IdentitylgpCondId5604CompressorSuperheatOverThresholdcurrentCompressor discharge refrigerant superheat temperature has exceeded an upper threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5609IdentitylgpCondId5609ThermalRunawayCelltoAmbientTemperatureEventcurrentThe delta temperature between a cell temperature and the ambient temperature has exceeded the thermal runaway cell to ambient temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5610IdentitylgpCondId5610ThermalRunawayCelltoCellTemperatureEventcurrentThe delta temperature between two cells has exceeded the thermal runaway cell to cell temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5611IdentitylgpCondId5611ThermalRunawayChargerCurrentLevelOneEventcurrentThe Battery-String charger current has exceeded the thermal runaway charger current level one threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5612IdentitylgpCondId5612ThermalRunawayChargerCurrentLevelTwoEventcurrentThe Battery-String charger current has exceeded the thermal runaway charger current level two threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.5617IdentitylgpCondId5617TemperatureControlSensorIssuecurrentThe air sensor selected for cooling control is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5621IdentitylgpCondId5621EEVSuperheatBelowThresholdcurrentElectronic expansion valve refrigerant low superheat event.
1.3.6.1.4.1.476.1.42.3.2.7.1.5622IdentitylgpCondId5622EEVDischargeTempAboveThresholdcurrentElectronic expansion valve refrigerant high discharge temperature event.
1.3.6.1.4.1.476.1.42.3.2.7.1.5623IdentitylgpCondId5623EEVBatteryIssuecurrentElectronic expansion valve battery cannot be recharged and needs to be replaced.
1.3.6.1.4.1.476.1.42.3.2.7.1.5624IdentitylgpCondId5624EEVPowerIssuecurrentElectronic expansion valve lost power and is running on battery backup.
1.3.6.1.4.1.476.1.42.3.2.7.1.5625IdentitylgpCondId5625EEVUnspecifiedGeneralEventcurrentOne or more unspecified electronic expansion valve events active. See local unit display for further details.
1.3.6.1.4.1.476.1.42.3.2.7.1.5629IdentitylgpCondId5629StaticPressureSensorIssuecurrentThe static pressure sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5630IdentitylgpCondId5630HighStaticPressurecurrentHigh static pressure event.
1.3.6.1.4.1.476.1.42.3.2.7.1.5631IdentitylgpCondId5631LowStaticPressurecurrentLow static pressure event.
1.3.6.1.4.1.476.1.42.3.2.7.1.5636IdentitylgpCondId5636PumpUnspecifiedGeneralEventcurrentOne or more unspecified pump events active. See local unit display for further details.
1.3.6.1.4.1.476.1.42.3.2.7.1.5637IdentitylgpCondId5637CondenserUnitUnspecifiedGeneralEventcurrentOne or more unspecified condenser unit events active. See local unit display for further details.
1.3.6.1.4.1.476.1.42.3.2.7.1.5638IdentitylgpCondId5638CondenserCircuitUnspecifiedGeneralEventcurrentOne or more unspecified condenser circuit events active. See local unit display for further details.
1.3.6.1.4.1.476.1.42.3.2.7.1.5642IdentitylgpCondId5642SFAReservedEvent1currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5643IdentitylgpCondId5643SFAReservedEvent2currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5644IdentitylgpCondId5644SFAReservedEvent3currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5645IdentitylgpCondId5645SFAReservedEvent4currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5646IdentitylgpCondId5646SFAReservedEvent5currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5647IdentitylgpCondId5647SFAReservedEvent6currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5648IdentitylgpCondId5648SFAReservedEvent7currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5649IdentitylgpCondId5649SFAReservedEvent8currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5650IdentitylgpCondId5650SFAReservedEvent9currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5651IdentitylgpCondId5651SFAReservedEvent10currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5652IdentitylgpCondId5652SFAReservedEvent11currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5653IdentitylgpCondId5653SFAReservedEvent12currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5654IdentitylgpCondId5654SFAReservedEvent13currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5655IdentitylgpCondId5655SFAReservedEvent14currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5656IdentitylgpCondId5656SFAReservedEvent15currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5657IdentitylgpCondId5657SFAReservedEvent16currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5658IdentitylgpCondId5658SFAReservedEvent17currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5659IdentitylgpCondId5659SFAReservedEvent18currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5660IdentitylgpCondId5660SFAReservedEvent19currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5661IdentitylgpCondId5661SFAReservedEvent20currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5662IdentitylgpCondId5662SFAReservedEvent21currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5663IdentitylgpCondId5663SFAReservedEvent22currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5664IdentitylgpCondId5664SFAReservedEvent23currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5665IdentitylgpCondId5665SFAReservedEvent24currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5666IdentitylgpCondId5666SFAReservedEvent25currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.5768IdentitylgpCondId5768OutletAirOvertemperatureLimitcurrentThe difference between the outlet air temperature and inlet air temperature exceeds a specified maximum temperature.
1.3.6.1.4.1.476.1.42.3.2.7.1.5769IdentitylgpCondId5769EMOShutdowncurrentAn Emergency Module Off command has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5770IdentitylgpCondId5770TopOutletFanFaultcurrentTop outlet fan fault - one or more top outlet fans have failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5771IdentitylgpCondId5771MMSOverCapacitycurrentThe multi-module system load is larger than the apparent power limit setting.
1.3.6.1.4.1.476.1.42.3.2.7.1.5773IdentitylgpCondId5773CompressorCapacityNormalcurrentCompressor has returned to normal load capacity.
1.3.6.1.4.1.476.1.42.3.2.7.1.5774IdentitylgpCondId5774CompressorContactorIssuecurrentCompressor contactor is not closing during compressor startup or is not opening during compressor shutdown.
1.3.6.1.4.1.476.1.42.3.2.7.1.5775IdentitylgpCondId5775UnitShutdownUnspecifiedGeneralEventcurrentOne or more unspecified unit shutdown events active. See local unit display for further details.
1.3.6.1.4.1.476.1.42.3.2.7.1.5776IdentitylgpCondId5776PDULowVoltageLNcurrentThe system has detected a module under voltage condition (LN).
1.3.6.1.4.1.476.1.42.3.2.7.1.5777IdentitylgpCondId5777PDULowVoltageLLcurrentThe system has detected a module under voltage condition (LL).
1.3.6.1.4.1.476.1.42.3.2.7.1.5778IdentitylgpCondId5778PDULowVoltageL1L2currentThe system has detected a line-to-line under voltage condition (L1 -L2).
1.3.6.1.4.1.476.1.42.3.2.7.1.5779IdentitylgpCondId5779PDULowVoltageL2L3currentThe system has detected a line-to-line under voltage condition (L2 -L3).
1.3.6.1.4.1.476.1.42.3.2.7.1.5780IdentitylgpCondId5780PDULowVoltageL3L1currentThe system has detected a line-to-line under voltage condition (L3 -L1).
1.3.6.1.4.1.476.1.42.3.2.7.1.5781IdentitylgpCondId5781PDULowVoltageL1NcurrentThe system has detected a line to neutral under voltage condition (L1-N).
1.3.6.1.4.1.476.1.42.3.2.7.1.5782IdentitylgpCondId5782PDULowVoltageL2NcurrentThe system has detected a line to neutral under voltage condition (L2-N).
1.3.6.1.4.1.476.1.42.3.2.7.1.5783IdentitylgpCondId5783PDULowVoltageL3NcurrentThe system has detected a line to neutral under voltage condition (L3-N).
1.3.6.1.4.1.476.1.42.3.2.7.1.5784IdentitylgpCondId5784BranchLowVoltageLNcurrentThe system has detected a module under voltage condition (LN).
1.3.6.1.4.1.476.1.42.3.2.7.1.5785IdentitylgpCondId5785BranchLowVoltageLLcurrentThe system has detected a module under voltage condition (LL).
1.3.6.1.4.1.476.1.42.3.2.7.1.5786IdentitylgpCondId5786BranchLowVoltagecurrentThe system has detected a module under voltage condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5788IdentitylgpCondId5788ContTieActivecurrentContinuous Power Tie Active.
1.3.6.1.4.1.476.1.42.3.2.7.1.5792IdentitylgpCondId5792UserkWhResetcurrentThe user kWh accumulator was reset to zero by the operator.
1.3.6.1.4.1.476.1.42.3.2.7.1.5796IdentitylgpCondId5796PeakkWResetcurrentThe Peak kW was reset.
1.3.6.1.4.1.476.1.42.3.2.7.1.5798IdentitylgpCondId5798BypassOverloadcurrentBypass overloaded, reduce load immediately.
1.3.6.1.4.1.476.1.42.3.2.7.1.5801IdentitylgpCondId5801LowBatteryShutdownImminentcurrentIf active and guaranteed shutdown is enabled, a low battery reserve condition exists that will shutdown the UPS.
1.3.6.1.4.1.476.1.42.3.2.7.1.5806IdentitylgpCondId5806OutputOverloadcurrentAn overload exists on the output.
1.3.6.1.4.1.476.1.42.3.2.7.1.5807IdentitylgpCondId5807OutputOffPendingcurrentOutput off pending - shutdown imminent.
1.3.6.1.4.1.476.1.42.3.2.7.1.5808IdentitylgpCondId5808SystemShutdownOutputShortcurrentShutdown was due to a short on the output.
1.3.6.1.4.1.476.1.42.3.2.7.1.5809IdentitylgpCondId5809SystemShutdownLowBatterycurrentShutdown was due to a low battery condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5810IdentitylgpCondId5810SystemShutdownRemoteShutdowncurrentShutdown was due to a remote communications shutdown command.
1.3.6.1.4.1.476.1.42.3.2.7.1.5811IdentitylgpCondId5811SystemShutdownHardwareFaultcurrentShutdown was due to an externally applied hardware control signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5817IdentitylgpCondId5817LossofRedundancycurrentThe system has an insufficient number of power modules to provide redundancy.
1.3.6.1.4.1.476.1.42.3.2.7.1.5818IdentitylgpCondId5818PowerModuleFailurecurrentOne or more conditions indicate a power module failure, service is required.
1.3.6.1.4.1.476.1.42.3.2.7.1.5819IdentitylgpCondId5819PowerModuleWarningcurrentOne or more power modules is reporting a warning condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5838IdentitylgpCondId5838PowerModuleFanFaultcurrentThe Power Module has detected a fan fault.
1.3.6.1.4.1.476.1.42.3.2.7.1.5839IdentitylgpCondId5839PowerModuleOverTemperaturecurrentThe Power Module has detected an over temperature condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5840IdentitylgpCondId5840PowerModuleShutdownOverTemperaturecurrentPower Module has shutdown due to over temperature.
1.3.6.1.4.1.476.1.42.3.2.7.1.5842IdentitylgpCondId5842ChargerModuleFanFaultcurrentThe Charger Module has detected a fan fault.
1.3.6.1.4.1.476.1.42.3.2.7.1.5847IdentitylgpCondId5847BatteryModuleTemperatureSensorFaultcurrentA Battery Module temperature sensor fault has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5848IdentitylgpCondId5848BatteryModuleOverTemperaturecurrentThe Battery Module has detected an over temperature condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5849IdentitylgpCondId5849ReplaceBatteryModulecurrentThe Battery Module needs to be replaced.
1.3.6.1.4.1.476.1.42.3.2.7.1.5850IdentitylgpCondId5850SystemShutdownTransformerOverTemperaturecurrentSystem shutdown due to transformer over temperature.
1.3.6.1.4.1.476.1.42.3.2.7.1.5851IdentitylgpCondId5851MaximumLoadAlarmcurrentMaximum load alarm indicating load setting has been exceeded.
1.3.6.1.4.1.476.1.42.3.2.7.1.5856IdentitylgpCondId5856BatteryModuleFaultcurrentOne or more battery modules are reporting a fault condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5857IdentitylgpCondId5857BatteryModuleWarningcurrentOne or more battery modules are reporting a warning condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5862IdentitylgpCondId5862CheckAirFiltercurrentPlease check air filter, it may need to be cleaned or replaced.
1.3.6.1.4.1.476.1.42.3.2.7.1.5863IdentitylgpCondId5863TransformerFanFaultcurrentThe transformer fan has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5865IdentitylgpCondId5865NoLoadWarningcurrentIndicates the UPS has output voltage but the output current is below a set threshold [No Load Warning Current Threshold] for a set period of time [No Load Warn…
1.3.6.1.4.1.476.1.42.3.2.7.1.5871IdentitylgpCondId5871BatteryOverTemperatureLimitcurrentA battery temperature sensor is reporting a value above a predetermined limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5873IdentitylgpCondId5873UnexpectedMainBatteryDisconnectClosurecurrentThe main battery disconnect has closed unexpectedly.
1.3.6.1.4.1.476.1.42.3.2.7.1.5874IdentitylgpCondId5874BatteryOverVoltagecurrentThe system has detected that the battery voltage has exceeded a predetermined limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.5875IdentitylgpCondId5875BatteryFuseFaultcurrentOne or more battery fuse faults has occurred.
1.3.6.1.4.1.476.1.42.3.2.7.1.5878IdentitylgpCondId5878MainBatteryDisconnectForcedToUnlockcurrentThe main battery disconnect is forced to the unlocked state.
1.3.6.1.4.1.476.1.42.3.2.7.1.5879IdentitylgpCondId5879VdcBackfeedcurrentThe voltage between battery and DC bus measurements is out of tolerance.
1.3.6.1.4.1.476.1.42.3.2.7.1.5880IdentitylgpCondId5880RectifierConfigurationChangeRequestcurrentThis event indicates that the battery is not configured and PFC is not enabled.
1.3.6.1.4.1.476.1.42.3.2.7.1.5881IdentitylgpCondId5881RegenerationActivecurrentRegeneration operation is active.
1.3.6.1.4.1.476.1.42.3.2.7.1.5882IdentitylgpCondId5882RegenerationOperationTerminatedcurrentRegeneration operation is not active.
1.3.6.1.4.1.476.1.42.3.2.7.1.5883IdentitylgpCondId5883RegenerationOperationFailurecurrentRegeneration operation has been terminated due to bypass source instability or unit misoperation.
1.3.6.1.4.1.476.1.42.3.2.7.1.5884IdentitylgpCondId5884ProgramInputContact01currentWhen the signal from [Program Input Contact 01] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5885IdentitylgpCondId5885ProgramInputContact02currentWhen the signal from [Program Input Contact 02] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5886IdentitylgpCondId5886ProgramInputContact03currentWhen the signal from [Program Input Contact 03] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5887IdentitylgpCondId5887ProgramInputContact04currentWhen the signal from [Program Input Contact 04] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5888IdentitylgpCondId5888ProgramInputContact05currentWhen the signal from [Program Input Contact 05] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5889IdentitylgpCondId5889ProgramInputContact06currentWhen the signal from [Program Input Contact 06] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5890IdentitylgpCondId5890ProgramInputContact07currentWhen the signal from [Program Input Contact 07] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5891IdentitylgpCondId5891ProgramInputContact08currentWhen the signal from [Program Input Contact 08] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5892IdentitylgpCondId5892ProgramInputContact09currentWhen the signal from [Program Input Contact 09] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5893IdentitylgpCondId5893ProgramInputContact10currentWhen the signal from [Program Input Contact 10] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5894IdentitylgpCondId5894ProgramInputContact11currentWhen the signal from [Program Input Contact 11] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5895IdentitylgpCondId5895ProgramInputContact12currentWhen the signal from [Program Input Contact 12] is active the function assigned to this contact is executed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5896IdentitylgpCondId5896GroundFaultDetectedcurrentThe system has detected a ground fault on a Battery-String.
1.3.6.1.4.1.476.1.42.3.2.7.1.5902IdentitylgpCondId5902ReturnHumiditySensorIssuecurrentThe humidity sensor at the inlet of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5903IdentitylgpCondId5903CompressorLowDifferentialPressureLockoutcurrentCompressor exceeded maximum startup attempts due to low differential pressure. Compressor is shutdown and has been disabled.
1.3.6.1.4.1.476.1.42.3.2.7.1.5906IdentitylgpCondId5906AirflowSensorIssuecurrentAirflow sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5907IdentitylgpCondId5907ExtAirDamperPositionIssuecurrentAir damper position does not match expected value, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5908IdentitylgpCondId5908ExtPowerSourceAFailurecurrentUnit main power source A failure, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5909IdentitylgpCondId5909ExtPowerSourceBFailurecurrentUnit main power source B failure, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.5910IdentitylgpCondId5910StaticPressureSensorOutofRangecurrentStatic pressure sensor signal is out of its configured range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5911IdentitylgpCondId5911FluidTemperatureSensorIssuecurrentThe fluid temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5912IdentitylgpCondId5912FluidFlowSensorIssuecurrentThe fluid flow sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5914IdentitylgpCondId5914OverDifferentialPressurecurrentAn over differential pressure condition was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5915IdentitylgpCondId5915UnderDifferentialPressurecurrentAn under differential pressure condition was detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.5924IdentitylgpCondId5924MixedModeLockoutcurrentMixed mode has been entered too many times over a rolling time period and has been temporarily disabled. Mixed mode is defined as the use of a compressor on on…
1.3.6.1.4.1.476.1.42.3.2.7.1.5928IdentitylgpCondId5928UnbalancedLoadConditioncurrentThe system has detected a line-to-line unbalanced load condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.5939IdentitylgpCondId5939BranchOverCurrentProtectioncurrentThe Branch Receptacle Module's over current protection is triggered.
1.3.6.1.4.1.476.1.42.3.2.7.1.5948IdentitylgpCondId5948BranchLowVoltageLLcurrentThe system has detected a module under voltage condition (LL).
1.3.6.1.4.1.476.1.42.3.2.7.1.5957IdentitylgpCondId5957BypassInputVoltageFaultcurrentThe system has detected the bypass voltage is unqualified.
1.3.6.1.4.1.476.1.42.3.2.7.1.5958IdentitylgpCondId5958BatteryTemperatureOutofRangecurrentBattery temperature is outside of acceptable range.
1.3.6.1.4.1.476.1.42.3.2.7.1.5960IdentitylgpCondId5960InverterOverloadcurrentInverter in overload fault.
1.3.6.1.4.1.476.1.42.3.2.7.1.5966IdentitylgpCondId5966AuxAirTempDeviceCommunicationLostcurrentCommunication with external auxiliary device providing an air temperature value has been lost.
1.3.6.1.4.1.476.1.42.3.2.7.1.5967IdentitylgpCondId5967ModbusPowerMeterCommunicationLostcurrentCommunication with Modbus power meter has been lost.
1.3.6.1.4.1.476.1.42.3.2.7.1.5968IdentitylgpCondId5968InverterDesaturationcurrentInverter Desaturation.
1.3.6.1.4.1.476.1.42.3.2.7.1.5969IdentitylgpCondId5969GenericDICFaultcurrentThe control board reports a fault - Service required.
1.3.6.1.4.1.476.1.42.3.2.7.1.5970IdentitylgpCondId5970GroundFaultcurrentAn AC phase to ground fault or three phase fault to ground exists on the output of the UPS.
1.3.6.1.4.1.476.1.42.3.2.7.1.5973IdentitylgpCondId5973InputBreakerOpencurrentThe main input breaker is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.5974IdentitylgpCondId5974NeutralBreakerOpencurrentThe neutral breaker is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.5975IdentitylgpCondId5975OutputBreakerOpencurrentThe output breaker is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.5976IdentitylgpCondId5976MaintenanceBypassBreakerClosedcurrentThe maintenance bypass breaker is closed.
1.3.6.1.4.1.476.1.42.3.2.7.1.5977IdentitylgpCondId5977BatteryBreakerOpencurrentThe battery circuit is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.5978IdentitylgpCondId5978RectifierIsolationBreakerRFBOpencurrentThe rectifier isolation breaker (RFB) indicates that it is in the open position.
1.3.6.1.4.1.476.1.42.3.2.7.1.5982IdentitylgpCondId5982BypassBreakerSBBOpencurrentThe bypass circuit breaker (SBB) indicates that it is in the open position.
1.3.6.1.4.1.476.1.42.3.2.7.1.5983IdentitylgpCondId5983BypassIsolationBreakerBIBOpencurrentThe bypass isolation breaker (BIB) indicates that it is in the open position.
1.3.6.1.4.1.476.1.42.3.2.7.1.5984IdentitylgpCondId5984BypassUndervoltageWarningcurrentThe voltage on one or more bypass phases is less than a specified percentage of the nominal voltage.
1.3.6.1.4.1.476.1.42.3.2.7.1.5985IdentitylgpCondId5985BypassStaticSwitchBPSSOncurrentThe Bypass Static Switch has been turned on.
1.3.6.1.4.1.476.1.42.3.2.7.1.5998IdentitylgpCondId5998BattOvtempWarningcurrentA battery temperature sensor is reporting a value above the setpoint.
1.3.6.1.4.1.476.1.42.3.2.7.1.6009IdentitylgpCondId6009InverterOutputBreakerOpencurrentThe inverter output breaker indicates that it is in the open position.
1.3.6.1.4.1.476.1.42.3.2.7.1.6011IdentitylgpCondId6011EquipmentOverTempWarningcurrentEquipment over temperature warning is a summary event based on the detection of at least one measured temperature exceeding a threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6012IdentitylgpCondId6012EquipmentOvertemperatureLimitcurrentThe equipment air temperature has exceeded its maximum set point.
1.3.6.1.4.1.476.1.42.3.2.7.1.6045IdentitylgpCondId6045RectifierInputBreakerOpencurrentThe rectifier isolation breaker indicates that it is in the open position.
1.3.6.1.4.1.476.1.42.3.2.7.1.6046IdentitylgpCondId6046LoadonUPScurrentThe output is being supplied power from the inverter.
1.3.6.1.4.1.476.1.42.3.2.7.1.6047IdentitylgpCondId6047Core2CoreFuseFailurecurrentCore-2-core fuse failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.6052IdentitylgpCondId6052SystemOutputBreakerOpencurrentThe system output breaker is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6059IdentitylgpCondId6059InverterRelayFaultcurrentThe inverter relay has malfunctioned.
1.3.6.1.4.1.476.1.42.3.2.7.1.6060IdentitylgpCondId6060TransfertoBypassSystemOverloadcurrentThe UPS System has transferred to bypass because the active power modules cannot support the critical load.
1.3.6.1.4.1.476.1.42.3.2.7.1.6061IdentitylgpCondId6061InputSourceBackfeedcurrentThe battery is backfeeding the input source.
1.3.6.1.4.1.476.1.42.3.2.7.1.6062IdentitylgpCondId6062LossofSynchronizationcurrentThe inverter and bypass are no longer synchronized. .
1.3.6.1.4.1.476.1.42.3.2.7.1.6063IdentitylgpCondId6063BatteryConverterCurrentLimitcurrentThe battery converter has reached is maximum current limit. .
1.3.6.1.4.1.476.1.42.3.2.7.1.6064IdentitylgpCondId6064LBSCableFailurecurrentLoad Bus Sync communications is abnormal. A problem with the LBS cable may exist.
1.3.6.1.4.1.476.1.42.3.2.7.1.6065IdentitylgpCondId6065BatteryChargeEqualizationTimeoutcurrentThe battery equalizing is time out.
1.3.6.1.4.1.476.1.42.3.2.7.1.6066IdentitylgpCondId6066ParallelCableFailurecurrentThe UPS parallel system communications is abnormal. A problem with the parallel cable may exist.
1.3.6.1.4.1.476.1.42.3.2.7.1.6067IdentitylgpCondId6067BatteryFaultcurrentA short circuit exists in the battery system.
1.3.6.1.4.1.476.1.42.3.2.7.1.6068IdentitylgpCondId6068BatteryRoomAlarmcurrentThe ambient temperature of the battery room is abnormal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6080IdentitylgpCondId6080UPSCCommunicationFailurecurrentThe UPSC has failed to communicate in a designated time period.
1.3.6.1.4.1.476.1.42.3.2.7.1.6092IdentitylgpCondId6092Compressor1BThermalOverloadcurrentFixed compressor 1B is shut down due to thermal overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.6093IdentitylgpCondId6093Compressor2BThermalOverloadcurrentFixed compressor 2B is shut down due to thermal overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.6094IdentitylgpCondId6094Compressor1BHoursExceededcurrentFixed compressor 1B run hours have exceeded the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6095IdentitylgpCondId6095Compressor2BHoursExceededcurrentFixed compressor 2B run hours have exceeded the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6100IdentitylgpCondId6100CondenserRemoteShutdowncurrentCondenser is shut down by a remote signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6105IdentitylgpCondId6105ExternalCondenserTVSSIssuecurrentThe condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6106IdentitylgpCondId6106ExternalCondenserVFDIssuecurrentThe condenser fan Variable Frequency Drive is offline, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6107IdentitylgpCondId6107ExternalCondenserIssuecurrentCondenser is not operating within its operational parameters, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6119IdentitylgpCondId6119SlotsnotavailablecurrentThe number of sensors exceeds the number of allocated slots and cannot be displayed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6180IdentitylgpCondId6180BatteryUnderVoltagecurrentBattery voltage is too low.
1.3.6.1.4.1.476.1.42.3.2.7.1.6182IdentitylgpCondId6182ReplaceBatterycurrentThe battery is due for replacement.
1.3.6.1.4.1.476.1.42.3.2.7.1.6186IdentitylgpCondId6186InputFrequencyDeviationcurrentThe input frequency is outside of the normal range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6187IdentitylgpCondId6187ShutdownPendingcurrentShutdown is pending.
1.3.6.1.4.1.476.1.42.3.2.7.1.6194IdentitylgpCondId6194SystemRebootCommandIssuedcurrentReboot command issued to the system.
1.3.6.1.4.1.476.1.42.3.2.7.1.6203IdentitylgpCondId6203SensorAddedcurrentSensor Added.
1.3.6.1.4.1.476.1.42.3.2.7.1.6204IdentitylgpCondId6204SensorRemovedcurrentSensor Removed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6205IdentitylgpCondId6205WaterLeakDetectedcurrentWater leak detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6210IdentitylgpCondId6210FirmwareUpdateInProgresscurrentFirmware update has started and is in progress.
1.3.6.1.4.1.476.1.42.3.2.7.1.6211IdentitylgpCondId6211FirmwareUpdateCompletedSuccessfullycurrentFirmware update has completed successfully.
1.3.6.1.4.1.476.1.42.3.2.7.1.6212IdentitylgpCondId6212FirmwareUpdateCompletedUnsuccessfullycurrentFirmware update has completed, but was not successful.
1.3.6.1.4.1.476.1.42.3.2.7.1.6216IdentitylgpCondId6216PrechargeCircuitFailedcurrentDC Bus precharge/discharge didn't reach specified level within a specified time.
1.3.6.1.4.1.476.1.42.3.2.7.1.6217IdentitylgpCondId6217MemoryCardRemovedcurrentThe memory card on the control board has been removed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6218IdentitylgpCondId6218AutoCalibrationActivecurrentThe system is automatically calibrating ADC channels.
1.3.6.1.4.1.476.1.42.3.2.7.1.6219IdentitylgpCondId6219AutoCalibrationFailedcurrentADC channel calibration has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6220IdentitylgpCondId6220ModuleOutputBreakerOpencurrentThe module output breaker is open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6221IdentitylgpCondId6221NeutralVoltageFaultcurrentVoltage observed on neutral line.
1.3.6.1.4.1.476.1.42.3.2.7.1.6222IdentitylgpCondId6222BranchLoadLosscurrentLoss of load on branch detected. Branch circuit breaker might be open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6225IdentitylgpCondId6225RemoteSensorLowHumiditycurrentRemote sensor humidity has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6226IdentitylgpCondId6226RemoteSensorHighHumiditycurrentRemote sensor humidity has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6227IdentitylgpCondId6227RemoteSensorAverageLowHumiditycurrentThe average humidity of multiple remote sensors on the cooling unit has dropped below a lower threshold. The event is deactivated when the humidity rises above…
1.3.6.1.4.1.476.1.42.3.2.7.1.6228IdentitylgpCondId6228RemoteSensorAverageHighHumiditycurrentThe average humidity of multiple remote sensors on the cooling unit has exceeded an upper threshold. The event is deactivated when the humidity drops below the…
1.3.6.1.4.1.476.1.42.3.2.7.1.6229IdentitylgpCondId6229RemoteSensorSystemAverageLowHumiditycurrentThe average humidity of multiple remote sensors on interconnected cooling units in a single system has dropped below a lower threshold. The event is deactivate…
1.3.6.1.4.1.476.1.42.3.2.7.1.6230IdentitylgpCondId6230RemoteSensorSystemAverageHighHumiditycurrentThe average humidity of multiple remote sensors on interconnected cooling units in a single system has exceeded an upper threshold. The event is deactivated wh…
1.3.6.1.4.1.476.1.42.3.2.7.1.6231IdentitylgpCondId6231LowCompressorSuperheatcurrentCompressor suction superheat has dropped below a lower threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6232IdentitylgpCondId6232SECUnspecifiedGeneralEventcurrentOne or more unspecified events active for the Superheat and Envelope Controller. See local unit display for further details.
1.3.6.1.4.1.476.1.42.3.2.7.1.6233IdentitylgpCondId6233SECCommunicationLostcurrentCommunication with the Superheat and Envelope Controller has been lost. The event is deactivated when communication is re -established.
1.3.6.1.4.1.476.1.42.3.2.7.1.6236IdentitylgpCondId6236PowerSourceAIssuecurrentNo power is detected at power source input 'A'.
1.3.6.1.4.1.476.1.42.3.2.7.1.6237IdentitylgpCondId6237PowerSourceBIssuecurrentNo power is detected at power source input 'B'.
1.3.6.1.4.1.476.1.42.3.2.7.1.6239IdentitylgpCondId6239FluidValveHoursExceededcurrentOperating hours for the fluid valve have exceeded the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6253IdentitylgpCondId6253BoosterFailurecurrentBooster failure - boost is off.
1.3.6.1.4.1.476.1.42.3.2.7.1.6254IdentitylgpCondId6254ChargerFailurecurrentCharger Failure - Charger is off.
1.3.6.1.4.1.476.1.42.3.2.7.1.6274IdentitylgpCondId6274UnitTopReturnAirSensorFailurecurrentReturn air sensor at the top of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6275IdentitylgpCondId6275UnitMiddleReturnAirSensorFailurecurrentReturn air sensor in the middle of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6276IdentitylgpCondId6276UnitBottomReturnAirSensorFailurecurrentReturn air sensor at the bottom of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6277IdentitylgpCondId6277UnitTopSupplyAirSensorFailurecurrentSupply air sensor at the top of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6278IdentitylgpCondId6278UnitMiddleFirstSupplyAirSensorFailurecurrentFirst supply air sensor in the middle of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6279IdentitylgpCondId6279UnitBottomSupplyAirSensorFailurecurrentSupply air sensor at the bottom of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6284IdentitylgpCondId6284UnitMiddleSecondSupplyAirSensorFailurecurrentSecond supply air sensor in the middle of the unit is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6293IdentitylgpCondId6293ChilledWaterControlActivecurrentChilled water inlet temperature control function is enabled due to 'bad' water.
1.3.6.1.4.1.476.1.42.3.2.7.1.6294IdentitylgpCondId6294ChilledWaterFlowTransducerFailurecurrentChilled water flow transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6295IdentitylgpCondId6295ChilledWaterInletTemperatureSensorFailurecurrentChilled water inlet temperature sensor is disconnected or the signal is out of range. The sensor is mandatory for the chilled water flow function.
1.3.6.1.4.1.476.1.42.3.2.7.1.6296IdentitylgpCondId6296ChilledWaterHighInletTemperaturecurrentChilled water inlet temperature has exceeded an upper threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6297IdentitylgpCondId6297Modbus010VModuleCommunicationFailurecurrentModbus 0-10V module for managing the second Chilled Water circuit valve is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6299IdentitylgpCondId6299RackDoorsOpencurrentRack doors opened due to supply air temperature exceeding the [Rack Door Open High Supply Air Temperature Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.6303IdentitylgpCondId6303TeamStaticPressureSensorFailurecurrentThe team static pressure sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6304IdentitylgpCondId6304HeatingLockoutcurrentHeating is shut down and disabled.
1.3.6.1.4.1.476.1.42.3.2.7.1.6305IdentitylgpCondId6305FreeCoolingStoppedHighRoomTempcurrentFree cooling is temporarily disabled due to room temperature exceeding a preset delta above the the set point.
1.3.6.1.4.1.476.1.42.3.2.7.1.6306IdentitylgpCondId6306ColdAisleTemperatureHumidityTeamSensorFailurecurrentCold aisle team sensor measuring air temperature and humidity is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6309IdentitylgpCondId6309ColdAisleAirSensorFailurecurrentCold aisle sensor measuring air temperature and humidity is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6310IdentitylgpCondId6310ChilledWaterInletTemperatureControlActivecurrentChilled water inlet temperature control is active.
1.3.6.1.4.1.476.1.42.3.2.7.1.6313IdentitylgpCondId6313ChilledWaterInletTemperatureSensorFailurecurrentChilled water inlet temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6314IdentitylgpCondId6314ChilledWaterOutletTemperatureSensorFailurecurrentChilled water outlet temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6315IdentitylgpCondId6315ChilledWaterFlowMeterSensorFailurecurrentChilled water flow meter sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6333IdentitylgpCondId6333BypassoutofsynccurrentBypass and Inverter inputs are not in sync.
1.3.6.1.4.1.476.1.42.3.2.7.1.6348IdentitylgpCondId6348SystemOutputoffasrequestedcurrentThe UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.4.1.476.1.42.3.2.7.1.6349IdentitylgpCondId6349SystemOffasrequestedcurrentThe entire UPS has shutdown as commanded.
1.3.6.1.4.1.476.1.42.3.2.7.1.6350IdentitylgpCondId6350GeneralFaultcurrentA general fault in the UPS has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6351IdentitylgpCondId6351UPSAwaitingPowercurrentThe UPS output is off and the UPS is awaiting the return of input power.
1.3.6.1.4.1.476.1.42.3.2.7.1.6352IdentitylgpCondId6352AutonomyCalibrationcurrentCalibration test occurred.
1.3.6.1.4.1.476.1.42.3.2.7.1.6353IdentitylgpCondId6353GeneralWarningcurrentA warning in the UPS has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6354IdentitylgpCondId6354BatteryChargingcurrentThe UPS battery is charging (battery charge percentage lower than 98).
1.3.6.1.4.1.476.1.42.3.2.7.1.6355IdentitylgpCondId6355BackfeedRelayFailurecurrentBypass SCR is wrongly on or commutated.
1.3.6.1.4.1.476.1.42.3.2.7.1.6356IdentitylgpCondId6356BatteryCircuitOpencurrentBattery Circuit Open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6357IdentitylgpCondId6357SystemRestartPendingcurrentA request for UPS restart has been received.
1.3.6.1.4.1.476.1.42.3.2.7.1.6358IdentitylgpCondId6358PipeTemperatureSensorFailurecurrentAir temperature sensor located in the pipe is not sending a valid value.
1.3.6.1.4.1.476.1.42.3.2.7.1.6362IdentitylgpCondId6362SFAReservedEvent26currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6363IdentitylgpCondId6363SFAReservedEvent27currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6364IdentitylgpCondId6364SFAReservedEvent28currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6365IdentitylgpCondId6365SFAReservedEvent29currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6366IdentitylgpCondId6366SFAReservedEvent30currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6367IdentitylgpCondId6367SFAReservedEvent31currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6368IdentitylgpCondId6368SFAReservedEvent32currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6369IdentitylgpCondId6369SFAReservedEvent33currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6370IdentitylgpCondId6370SFAReservedEvent34currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6371IdentitylgpCondId6371SFAReservedEvent35currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6372IdentitylgpCondId6372SFAReservedEvent36currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6373IdentitylgpCondId6373SFAReservedEvent37currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6374IdentitylgpCondId6374SFAReservedEvent38currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6375IdentitylgpCondId6375SFAReservedEvent39currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6376IdentitylgpCondId6376SFAReservedEvent40currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6377IdentitylgpCondId6377SFAReservedEvent41currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6378IdentitylgpCondId6378SFAReservedEvent42currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6379IdentitylgpCondId6379SFAReservedEvent43currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6380IdentitylgpCondId6380SFAReservedEvent44currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6381IdentitylgpCondId6381SFAReservedEvent45currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6382IdentitylgpCondId6382SFAReservedEvent46currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6383IdentitylgpCondId6383SFAReservedEvent47currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6384IdentitylgpCondId6384SFAReservedEvent48currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6385IdentitylgpCondId6385SFAReservedEvent49currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6386IdentitylgpCondId6386SFAReservedEvent50currentReserved event for SFA use.
1.3.6.1.4.1.476.1.42.3.2.7.1.6438IdentitylgpCondId6438PowerModuleInputCurrentAbnormalcurrentInput current of the power module is abnormal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6439IdentitylgpCondId6439PowerModuleBalancerofDCBusFailurecurrentBalancer of DC Bus in the power module has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6440IdentitylgpCondId6440PowerModuleFuseFailurecurrentA summary event indicating one or more fuse failures in the power module.
1.3.6.1.4.1.476.1.42.3.2.7.1.6441IdentitylgpCondId6441PowerModulePowerSupplyFailurecurrentPower module power supply failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.6450IdentitylgpCondId6450PDUPoweredOncurrentThe PDU was powered on.
1.3.6.1.4.1.476.1.42.3.2.7.1.6453IdentitylgpCondId6453InputWiringFaultcurrentThe neutral/ground conductors on the input wiring are not properly bonded, or the line/neutral conductors have been swapped.
1.3.6.1.4.1.476.1.42.3.2.7.1.6454IdentitylgpCondId6454DCtoDCConverterFaultcurrentA failure has occurred in the battery discharge circuit.
1.3.6.1.4.1.476.1.42.3.2.7.1.6455IdentitylgpCondId6455LeakSensorCableFaultcurrentA fault is detected in the 'Leak Sensor' cable.
1.3.6.1.4.1.476.1.42.3.2.7.1.6518IdentitylgpCondId6518StandbyUnitActivatedDuetoChillerFailurecurrentExternal chiller unit has failed for this unit, so the standby cooling unit has been activated.
1.3.6.1.4.1.476.1.42.3.2.7.1.6522IdentitylgpCondId6522PDUResidualOverCurrentcurrentThe system has detected a PDU residual over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.6527IdentitylgpCondId6527PDUOverCurrentProtectioncurrentThe PDU over current protection is triggered.
1.3.6.1.4.1.476.1.42.3.2.7.1.6528IdentitylgpCondId6528PowerModuleLeverUnlockedcurrentThe power module is inactive because the lever is in the unlocked position.
1.3.6.1.4.1.476.1.42.3.2.7.1.6529IdentitylgpCondId6529HardwareMismatchcurrentThe assigned system model settings do not match the actual installed hardware. The module count is wrong, or a module of the wrong type is installed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6530IdentitylgpCondId6530SupplyNTCAirSensorIssuecurrentThe supply NTC air sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6531IdentitylgpCondId6531ExternalAirSensorCIssuecurrentThe external air sensor C is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6532IdentitylgpCondId6532ExternalAirSensorDIssuecurrentThe external air sensor D is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6533IdentitylgpCondId6533ExternalAirSensorEIssuecurrentThe external air sensor E is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6534IdentitylgpCondId6534PumpThermalOverloadcurrentPump is shut down due to thermal overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.6535IdentitylgpCondId6535XDModuleCommunicationLostcurrentCommunication with XD Module has been lost.
1.3.6.1.4.1.476.1.42.3.2.7.1.6536IdentitylgpCondId6536MMSCapacityExceededcurrentThe critical load is larger than the redundant rating of a 1+N redundant multi-module system.
1.3.6.1.4.1.476.1.42.3.2.7.1.6538IdentitylgpCondId6538TSAControlInputIssuecurrentThe analog input used to set the air temperature set point for cooling control is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6539IdentitylgpCondId6539ChilledWaterValveHoursExceededcurrent[Chilled Water Valve Hours] has exceeded [Chilled Water Valve Operating Hours Threshold].
1.3.6.1.4.1.476.1.42.3.2.7.1.6540IdentitylgpCondId6540FSAControlInputIssuecurrentThe analog input used to set the air temperature set point for fan speed control is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6541IdentitylgpCondId6541AutoTuneLicenseExpiringcurrentLicense for the AutoTune feature has not been refreshed in 30 days and will be expiring soon.
1.3.6.1.4.1.476.1.42.3.2.7.1.6542IdentitylgpCondId6542AutoTuneLicenseExpiredcurrentLicense for the AutoTune feature has expired.
1.3.6.1.4.1.476.1.42.3.2.7.1.6543IdentitylgpCondId6543UnitInStandbyDueToCoolingLosscurrentUnit forced into standby because it is unable to provide any cooling.
1.3.6.1.4.1.476.1.42.3.2.7.1.6544IdentitylgpCondId6544ControlUnitsRemoteShutdownMismatchcurrentThe remote shutdown status of the primary control unit does not match the remote shutdown status of the secondary control unit.
1.3.6.1.4.1.476.1.42.3.2.7.1.6545IdentitylgpCondId6545SecondaryControlUnitCommunicationLostcurrentThe primary control unit has lost Ethernet communications with the secondary control unit.
1.3.6.1.4.1.476.1.42.3.2.7.1.6546IdentitylgpCondId6546ControlUnitsUnitCodeMismatchcurrentUnit codes for the primary and secondary control units do not match.
1.3.6.1.4.1.476.1.42.3.2.7.1.6547IdentitylgpCondId6547SSAControlInputIssuecurrentThe analog input used to set the static pressure set point for fan speed control is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6574IdentitylgpCondId6574SubfeedPhaseUndercurrentcurrentSubfeed breaker phase current has dropped below the threshold.
1.3.6.1.4.1.476.1.42.3.2.7.1.6587IdentitylgpCondId6587TransferCountClearedcurrentA system event indicating the transfer count has been cleared.
1.3.6.1.4.1.476.1.42.3.2.7.1.6588IdentitylgpCondId6588EnergyCounterClearedcurrentA system event indicating the energy counter (e.g. KWH) has been cleared.
1.3.6.1.4.1.476.1.42.3.2.7.1.6589IdentitylgpCondId6589HistoryLogsFullcurrentThe history logs are full.
1.3.6.1.4.1.476.1.42.3.2.7.1.6590IdentitylgpCondId6590HistoryLogsClearedcurrentHistory logs have been cleared.
1.3.6.1.4.1.476.1.42.3.2.7.1.6591IdentitylgpCondId6591EventLogClearedcurrentAll past alarms and faults have been cleared.
1.3.6.1.4.1.476.1.42.3.2.7.1.6592IdentitylgpCondId6592SystemDateChangedcurrentThe system date has been updated.
1.3.6.1.4.1.476.1.42.3.2.7.1.6593IdentitylgpCondId6593SystemTimeChangedcurrentThe system time has been updated.
1.3.6.1.4.1.476.1.42.3.2.7.1.6594IdentitylgpCondId6594AccessPasswordChangedcurrentThe access password has been changed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6595IdentitylgpCondId6595ConfigModifiedcurrentA setpoint has been updated.
1.3.6.1.4.1.476.1.42.3.2.7.1.6612IdentitylgpCondId6612SCRShortcurrentThe SCR is in a short condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.6613IdentitylgpCondId6613SCROpencurrentThe SCR is in an open condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.6614IdentitylgpCondId6614ACPowerSupplyFailcurrentA failure of the AC Power Supply has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6615IdentitylgpCondId6615DCPowerSupplyFailcurrentA failure of the DC Power Supply has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6616IdentitylgpCondId6616VoltageSensorFailcurrentA voltage sensor failure has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6617IdentitylgpCondId6617SCRSensorFailcurrentThe SCR sensor module failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6618IdentitylgpCondId6618CurrentSensorFailcurrentThe current sensor module failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6619IdentitylgpCondId6619GateDriveFailcurrentThe Gate Drive module failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6620IdentitylgpCondId6620SurgeFailcurrentThe surge module failed for the input source.
1.3.6.1.4.1.476.1.42.3.2.7.1.6621IdentitylgpCondId6621FastUnderVoltagecurrentFast under voltage detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6622IdentitylgpCondId6622SlowUnderVoltagecurrentSlow under voltage detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6623IdentitylgpCondId6623OverVoltagecurrentOver voltage detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6624IdentitylgpCondId6624OverUnderFrequencyFailcurrentAn over or under frequency condition has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6625IdentitylgpCondId6625GeneralSourceFailurecurrentA non-specific failure has been detected in the source.
1.3.6.1.4.1.476.1.42.3.2.7.1.6626IdentitylgpCondId6626OverCurrentcurrentAn over current has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6627IdentitylgpCondId6627PeakCurrentOffLimitcurrentThe peak current has exceeded the setpoint defined by I-PK Xfer Lockout.
1.3.6.1.4.1.476.1.42.3.2.7.1.6628IdentitylgpCondId6628SyncFailcurrentA phase rotation/out of synchronization failure has been detected.
1.3.6.1.4.1.476.1.42.3.2.7.1.6629IdentitylgpCondId6629InputOverVoltagecurrentInput over voltage.
1.3.6.1.4.1.476.1.42.3.2.7.1.6630IdentitylgpCondId6630InputUnderVoltagecurrentInput under voltage.
1.3.6.1.4.1.476.1.42.3.2.7.1.6631IdentitylgpCondId6631InputOverUnderFrequencycurrentInput over/under frequency.
1.3.6.1.4.1.476.1.42.3.2.7.1.6635IdentitylgpCondId6635VoltageSenseFailcurrentOutput voltage sense failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.6636IdentitylgpCondId6636LoadonAlternateSourcecurrentThe load is on the alternate source.
1.3.6.1.4.1.476.1.42.3.2.7.1.6637IdentitylgpCondId6637UnderVoltageFailcurrentOutput under voltage failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.6638IdentitylgpCondId6638OutputOverCurrentcurrentOutput is over current.
1.3.6.1.4.1.476.1.42.3.2.7.1.6639IdentitylgpCondId6639GroundOverCurrentcurrentGround is over current.
1.3.6.1.4.1.476.1.42.3.2.7.1.6640IdentitylgpCondId6640NeutralOverCurrentcurrentNeutral is over current.
1.3.6.1.4.1.476.1.42.3.2.7.1.6641IdentitylgpCondId6641LoadVoltageTHDcurrentLoad voltage THD has exceeded the set limit.
1.3.6.1.4.1.476.1.42.3.2.7.1.6662IdentitylgpCondId6662ControlLogicFailcurrentA control logic module has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6663IdentitylgpCondId6663PowerSupplyLogicFailcurrentA power supply module has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6664IdentitylgpCondId6664ExternalCommsFailurecurrentExternal communications failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.6665IdentitylgpCondId6665HeatSinkOverTempcurrentThe system heat sink temperature has exceeded design limits.
1.3.6.1.4.1.476.1.42.3.2.7.1.6666IdentitylgpCondId6666AutomaticTransferInhibitedcurrentAutomatic transfer is inhibited.
1.3.6.1.4.1.476.1.42.3.2.7.1.6667IdentitylgpCondId6667InputSourceTransferInhibitedcurrentInput source transfer is inhibited.
1.3.6.1.4.1.476.1.42.3.2.7.1.6676IdentitylgpCondId6676CB1ShuntTripcurrentCB1 Shunt Trip event.
1.3.6.1.4.1.476.1.42.3.2.7.1.6677IdentitylgpCondId6677CB2ShuntTripcurrentCB2 Shunt Trip event.
1.3.6.1.4.1.476.1.42.3.2.7.1.6678IdentitylgpCondId6678CB6NeutralOpencurrentCB6 neutral open event.
1.3.6.1.4.1.476.1.42.3.2.7.1.6679IdentitylgpCondId6679ContactorNeutralFailcurrentContactor Neutral Fail event.
1.3.6.1.4.1.476.1.42.3.2.7.1.6680IdentitylgpCondId6680CB1BreakerOpencurrentCB1 Breaker open event. Normal state is breaker closed. Latched state is breaker open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6681IdentitylgpCondId6681CB2BreakerOpencurrentCB2 Breaker open event. Normal state is breaker closed. Latched state is breaker open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6682IdentitylgpCondId6682CB4BreakerClosedcurrentCB4 breaker closed event. Normal state is breaker open. Latched state is breaker closed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6683IdentitylgpCondId6683CB5BreakerClosedcurrentCB5 breaker closed event. Normal state is breaker open. Latched state is breaker closed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6684IdentitylgpCondId6684CB3BreakerOpencurrentCB3 breaker open event. Normal state is breaker closed. Latched state is breaker open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6685IdentitylgpCondId6685CB3ABreakerOpencurrentCB3A breaker open event. Normal state is breaker closed. Latched state is breaker open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6686IdentitylgpCondId6686CB6BreakerOpencurrentCB6 breaker open event. Normal state is breaker closed. Latched state is breaker open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6687IdentitylgpCondId6687CB7BreakerOpencurrentCB7 breaker open event. Normal state is breaker closed. Latched state is breaker open.
1.3.6.1.4.1.476.1.42.3.2.7.1.6691IdentitylgpCondId6691GroupIndependentOncurrentThe group standby/cascade state for this unit has been overridden. The unit has been forced on.
1.3.6.1.4.1.476.1.42.3.2.7.1.6692IdentitylgpCondId6692GroupIndependentOffcurrentThe group standby/cascade state for this unit has been overridden. The unit has been forced off.
1.3.6.1.4.1.476.1.42.3.2.7.1.6693IdentitylgpCondId6693BranchResidualOverCurrentcurrentThe system has detected a branch residual over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.6694IdentitylgpCondId6694ReceptacleResidualOverCurrentcurrentThe system has detected a receptacle residual over current condition.
1.3.6.1.4.1.476.1.42.3.2.7.1.6728IdentitylgpCondId6728BuckOncurrentThe input voltage is currently being bucked (lowered) by the inverter.
1.3.6.1.4.1.476.1.42.3.2.7.1.6729IdentitylgpCondId6729BoostOncurrentThe input voltage is currently being boosted (raised) by the inverter.
1.3.6.1.4.1.476.1.42.3.2.7.1.6739IdentitylgpCondId6739Compressor1HighPressurecurrentCompressor 1 High Pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.6740IdentitylgpCondId6740Compressor2HighPressurecurrentCompressor 2 High Pressure.
1.3.6.1.4.1.476.1.42.3.2.7.1.6741IdentitylgpCondId6741Compressor1ThermalOverloadcurrentCompressor 1 Thermal Overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.6742IdentitylgpCondId6742Compressor2ThermalOverloadcurrentCompressor 2 Thermal Overload.
1.3.6.1.4.1.476.1.42.3.2.7.1.6758IdentitylgpCondId6758CompressorFreezeProtectioncurrentCompressor has entered the freeze protection phase.
1.3.6.1.4.1.476.1.42.3.2.7.1.6773IdentitylgpCondId6773FanTemperatureCompensationLimitReachedcurrentUnit is configured for fan temperature compensation, and the fan control set point cannot be reduced any further due to high remote air temperature sensor read…
1.3.6.1.4.1.476.1.42.3.2.7.1.6774IdentitylgpCondId6774ModbusECFanCommunicationLostcurrentCommunication with Modbus EC fan has been lost.
1.3.6.1.4.1.476.1.42.3.2.7.1.6785IdentitylgpCondId6785AnalogTemperatureControlIssuecurrentAnalog input used for creating the control temperature (instead of reading a sensor) is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6786IdentitylgpCondId6786SubgroupFirmwareUpdateRequiredcurrentMismatch of subgroup firmware. Both the primary and secondary control boards must be running the same firmware version.
1.3.6.1.4.1.476.1.42.3.2.7.1.6787IdentitylgpCondId6787SubgroupSecondaryControlUnitIssuecurrentSubgroup secondary control unit is reporting an unspecified issue.
1.3.6.1.4.1.476.1.42.3.2.7.1.6788IdentitylgpCondId6788EEVCommunicationLostcurrentCommunication with Electronic Expansion Valve unit has been lost.
1.3.6.1.4.1.476.1.42.3.2.7.1.6789IdentitylgpCondId6789EEVMotorIssuecurrentElectronic Expansion Valve stepper motor issue.
1.3.6.1.4.1.476.1.42.3.2.7.1.6790IdentitylgpCondId6790EEVFeedbackIssuecurrentElectronic Expansion Valve feedback error.
1.3.6.1.4.1.476.1.42.3.2.7.1.6791IdentitylgpCondId6791EEVPressureSensorIssuecurrentElectronic Expansion Valve refrigerant pressure sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6792IdentitylgpCondId6792EEVCoilTemperatureSensorIssuecurrentElectronic Expansion Valve coil temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6793IdentitylgpCondId6793EEVDischargeTemperatureSensorIssuecurrentElectronic Expansion Valve discharge temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6794IdentitylgpCondId6794EEVSumpTemperatureSensorIssuecurrentElectronic Expansion Valve sump temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6795IdentitylgpCondId6795EEVBatteryTestIssuecurrentElectronic Expansion Valve battery state cannot be determined.
1.3.6.1.4.1.476.1.42.3.2.7.1.6796IdentitylgpCondId6796EEVBatteryPersistentIssuecurrentElectronic Expansion Valve has continuously detected a 'bad' battery condition for an extended period of time.
1.3.6.1.4.1.476.1.42.3.2.7.1.6798IdentitylgpCondId6798PumpCycleLockOutcurrentPump is locked out due to multiple pump-to-compressor transitions at cold ambient air temperature.
1.3.6.1.4.1.476.1.42.3.2.7.1.6799IdentitylgpCondId6799PumpBoardFirmwareUpdateRequiredcurrentMismatch of pump board firmware. All pump boards must be running the same firmware version.
1.3.6.1.4.1.476.1.42.3.2.7.1.6800IdentitylgpCondId6800PumpControlBoardIssuecurrentPump is shut down due to a pump control board issue. Control board must be rebooted.
1.3.6.1.4.1.476.1.42.3.2.7.1.6801IdentitylgpCondId6801PumpInvalidDataShutdowncurrentPump is shut down due to invalid data.
1.3.6.1.4.1.476.1.42.3.2.7.1.6802IdentitylgpCondId6802PumpInputPressureSensorIssuecurrentPump input refrigerant pressure sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6803IdentitylgpCondId6803PumpInputTemperatureSensorIssuecurrentPump input refrigerant temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6804IdentitylgpCondId6804PumpOutputPressureSensorIssuecurrentPump output refrigerant pressure sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6805IdentitylgpCondId6805PumpOutputTemperatureSensorIssuecurrentPump output refrigerant temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.7.1.6806IdentitylgpCondId6806PumpCommunicationLostcurrentCommunication with pump unit has been lost.
1.3.6.1.4.1.476.1.42.3.2.7.1.6807IdentitylgpCondId6807PumpRemoteShutdowncurrentPump is shut down by a remote signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6808IdentitylgpCondId6808PumpUSBEthernetPortIssuecurrentPump control board USB or Ethernet interface has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6809IdentitylgpCondId6809PumpStartupFailurecurrentMultiple attempts to start the pump have failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6810IdentitylgpCondId6810PumpInverterFailurecurrentPump inverter is reporting a failure.
1.3.6.1.4.1.476.1.42.3.2.7.1.6811IdentitylgpCondId6811PumpTVSSIssuecurrentPump Transient Voltage Surge Suppressor or Surge Protection Device has failed.
1.3.6.1.4.1.476.1.42.3.2.7.1.6812IdentitylgpCondId6812PumpHighSuperheatcurrentPump inlet refrigerant superheat temperature is too high, or the pump has been running too long with the condenser fan off.
1.3.6.1.4.1.476.1.42.3.2.7.1.6813IdentitylgpCondId6813CondenserHighAmbientAirTempDeltacurrentThe difference between condenser measured ambient air temperatures has been too large for an extended period of time.
1.3.6.1.4.1.476.1.42.3.2.7.1.6814IdentitylgpCondId6814CondenserLeeTempOptionMismatchcurrentLee-Temp option configured at a condenser unit does not match Lee -Temp option configured at the control unit.
1.3.6.1.4.1.476.1.42.3.2.7.1.6815IdentitylgpCondId6815CondenserBoardFirmwareUpdateRequiredcurrentMismatch of condenser board firmware. All condenser boards must be running the same firmware version.
1.3.6.1.4.1.476.1.42.3.2.7.1.6816IdentitylgpCondId6816CondenserToPumpHighRefrigerantTempDeltacurrentTemperature delta between the condenser output refrigerant and pump inlet refrigerant is too large.
1.3.6.1.4.1.476.1.42.3.2.7.1.6817IdentitylgpCondId6817CondenserRefrigerantTypeMismatchcurrentRefrigerant type configured at condenser unit does not match refrigerant type configured at the control unit.
1.3.6.1.4.1.476.1.42.3.2.7.1.6818IdentitylgpCondId6818ExternalSupplyFluidHighTemperaturecurrentSupply fluid temperature has exceeded a threshold, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6819IdentitylgpCondId6819ExternalSupplyFluidTempSensorIssuecurrentSupply fluid temperature sensor is disconnected or the signal is out of range, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.7.1.6822IdentitylgpCondId6822AuditLogUpdatecurrentAudit log has been updated.
1.3.6.1.4.1.476.1.42.3.2.7.1.6824IdentitylgpCondId6824ExternalSupplyFluidFlowIssuecurrentSupply fluid flow issue, as indicated by an external input signal.