MIB Viewer

NEXT-UPS-MIB

676 objects
The MIB module to describe UPS, Inverter, Salor Power
Imported Objects
RFC-1215TRAP-TYPE
RFC1155-SMIenterprises
SNMPv2-SMIMODULE-IDENTITY OBJECT-IDENTITY OBJECT-TYPE
SNMPv2-TCDisplayString
UPS-MIBNonNegativeInteger PositiveInteger
OIDNameAccessStatusDescription
1.3.6.1.4.1.21111IdentityNextUPSSystemsThe MIB module to describe UPS, Inverter, Salor Power
1.3.6.1.4.1.21111.1Nodeproducts
1.3.6.1.4.1.21111.1.1Nodeups
1.3.6.1.4.1.21111.1.1.1NodeupsIdent
1.3.6.1.4.1.21111.1.1.1.1ScalarupsIdManufacturerread-onlymandatoryThe name of the UPS manufacturer.
1.3.6.1.4.1.21111.1.1.1.2ScalarupsIdProtocolread-onlymandatoryThe UPS Protocol id.
1.3.6.1.4.1.21111.1.1.1.3ScalarupsIdModelNameread-onlymandatoryThe UPS Model designation.
1.3.6.1.4.1.21111.1.1.1.4ScalarupsIdSerialNumberread-onlymandatoryThe UPS serial no.
1.3.6.1.4.1.21111.1.1.1.5ScalarupsIdNameread-writemandatoryA string identifying the UPS. This object should be set by the administrator.
1.3.6.1.4.1.21111.1.1.1.6ScalarupsIdFWVersionread-onlymandatoryMain CPU firmware version.
1.3.6.1.4.1.21111.1.1.1.7ScalarupsIdUPSTyperead-onlymandatoryUPS type.
1.3.6.1.4.1.21111.1.1.2NodeupsRating
1.3.6.1.4.1.21111.1.1.2.1ScalarupsRatinVoltageread-onlycurrentThe rating input voltage of UPS
1.3.6.1.4.1.21111.1.1.2.2ScalarupsRatoutVoltageread-onlycurrentThe rating output voltage of UPS
1.3.6.1.4.1.21111.1.1.2.3ScalarupsRatoutFrequencyread-onlycurrentThe rating output frequency of UPS
1.3.6.1.4.1.21111.1.1.2.4ScalarupsRatoutCurrentread-onlycurrentThe rating output current of UPS
1.3.6.1.4.1.21111.1.1.2.5ScalarupsRatoutApparentPowerread-onlycurrentThe rating output apparent power of UPS
1.3.6.1.4.1.21111.1.1.2.6ScalarupsRatoutTruePowerread-onlycurrentThe rating output true power of UPS
1.3.6.1.4.1.21111.1.1.2.7ScalarupsRatBatVoltageread-onlycurrentThe rating battery voltage of UPS
1.3.6.1.4.1.21111.1.1.3NodeupsBattery
1.3.6.1.4.1.21111.1.1.3.1ScalarupsBatStatusread-onlymandatoryThe indication of the status in the UPS system's batteries.
1.3.6.1.4.1.21111.1.1.3.2ScalarupsBatSecondsOnBatteryread-onlycurrentIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.21111.1.1.3.3ScalarupsBatEstMinutesRemainingread-onlycurrentAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.21111.1.1.3.4ScalarupsBatEstChargeRemainingread-onlycurrentAn estimate of the battery charge remaining expressed as a percent of full charge.
1.3.6.1.4.1.21111.1.1.3.5ScalarupsBatPBatVoltageread-onlycurrentThe magnitude of the present Positive battery voltage.
1.3.6.1.4.1.21111.1.1.3.6ScalarupsBatNBatVoltageread-onlycurrentThe magnitude of the present negative battery voltage.
1.3.6.1.4.1.21111.1.1.3.7ScalarupsBatPBatCurrentread-onlycurrentThe positive battery present current.
1.3.6.1.4.1.21111.1.1.3.8ScalarupsBatNBatCurrentread-onlycurrentThe present negative battery current.
1.3.6.1.4.1.21111.1.1.3.9ScalarupsBatPBatChargCurrentread-onlycurrentThe Positive battery charging current.
1.3.6.1.4.1.21111.1.1.3.10ScalarupsBatNBatchargCurrentread-onlycurrentThe present negative battery charging current.
1.3.6.1.4.1.21111.1.1.3.11ScalarupsBatPBatDischargCurrentread-onlycurrentThe present positive battery discharging current.
1.3.6.1.4.1.21111.1.1.3.12ScalarupsBatNBatDischargCurrentread-onlycurrentThe present negative battery discharging current.
1.3.6.1.4.1.21111.1.1.3.13ScalarupsBatTemperatureread-onlycurrentThe ambient temperature at or near the UPS Battery casing.
1.3.6.1.4.1.21111.1.1.3.14ScalarupsBatNumberInSeriesread-onlycurrentThe number of battery in series.
1.3.6.1.4.1.21111.1.1.3.15ScalarupsBatNumberInParallelread-onlycurrentThe number of battery in Parallel.
1.3.6.1.4.1.21111.1.1.3.16ScalarupsBatPBatDischargCurrent2read-onlycurrentThe present positive battery pipe2 discharging current.
1.3.6.1.4.1.21111.1.1.4NodeupsInput
1.3.6.1.4.1.21111.1.1.4.1ScalarupsInLineBadsread-onlycurrentA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i…
1.3.6.1.4.1.21111.1.1.4.2ScalarupsInTtlApparentPowerread-onlycurrentTotal input apparent power .
1.3.6.1.4.1.21111.1.1.4.3ScalarupsInTtlTruePowerread-onlycurrentTotal input active(true) power .
1.3.6.1.4.1.21111.1.1.4.4ScalarupsInNumLinesread-onlycurrentThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.
1.3.6.1.4.1.21111.1.1.4.5TableupsInTablenot-accessiblecurrentA list of input table entries. The number of entries is given by the value of upsInputNumLines.
1.3.6.1.4.1.21111.1.1.4.5.1RowupsInEntrynot-accessiblecurrentAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.21111.1.1.4.5.1.1ColumnupsInLineIndexread-onlycurrentThe number of output lines
1.3.6.1.4.1.21111.1.1.4.5.1.2ColumnupsInFrequencyread-onlycurrentThe present input frequency.
1.3.6.1.4.1.21111.1.1.4.5.1.3ColumnupsInVoltageread-onlycurrentThe input utility line voltage .
1.3.6.1.4.1.21111.1.1.4.5.1.4ColumnupsInCurrentread-onlycurrentThe magnitude of the present input current
1.3.6.1.4.1.21111.1.1.4.5.1.5ColumnupsInApparentPowerread-onlycurrentThe magnitude of the present input Apparent power.
1.3.6.1.4.1.21111.1.1.4.5.1.6ColumnupsInTruePowerread-onlycurrentThe magnitude of the present input true power.
1.3.6.1.4.1.21111.1.1.4.5.1.7ColumnupsInPowerFactorread-onlycurrentInput true power/apparent power factor
1.3.6.1.4.1.21111.1.1.4.5.1.8ColumnupsInLineVoltageread-onlycurrentThe input utility line voltage . if upsInLineIndex =1, upsInLineVoltage = Line voltage of RS phase; if upsInLineIndex =2, upsInLineVoltage = Line voltage of ST…
1.3.6.1.4.1.21111.1.1.4.6ScalarupsInTtlVoltageread-onlycurrentThe input utility line tatol voltage .
1.3.6.1.4.1.21111.1.1.4.7ScalarupsInTtlCurrentread-onlycurrentThe input utility line tatol current.
1.3.6.1.4.1.21111.1.1.5NodeupsOutput
1.3.6.1.4.1.21111.1.1.5.1ScalarupsOutSourceread-onlycurrentThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.21111.1.1.5.3ScalarupsOutTtlApparentPowerread-onlycurrentTotal output apparent power .
1.3.6.1.4.1.21111.1.1.5.4ScalarupsOutTtlTruePowerread-onlycurrentTotal output active(true) power .
1.3.6.1.4.1.21111.1.1.5.5ScalarupsOutTtlPercentLoadread-onlycurrentThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent…
1.3.6.1.4.1.21111.1.1.5.6ScalarupsOutNumLinesread-onlycurrentThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.
1.3.6.1.4.1.21111.1.1.5.7TableupsOutTablenot-accessiblecurrentA list of output table entries. The number of entries is given by the value of upsOutputNumLines.
1.3.6.1.4.1.21111.1.1.5.7.1RowupsOutEntrynot-accessiblecurrentAn entry containing information applicable to a particular output line.
1.3.6.1.4.1.21111.1.1.5.7.1.1ColumnupsOutLineIndexread-onlycurrentThe output line identifier.
1.3.6.1.4.1.21111.1.1.5.7.1.2ColumnupsOutVoltageread-onlycurrentThe output voltage of the UPS system.
1.3.6.1.4.1.21111.1.1.5.7.1.3ColumnupsOutCurrentread-onlycurrentThe output current of the UPS system
1.3.6.1.4.1.21111.1.1.5.7.1.4ColumnupsOutApparentPowerread-onlycurrentThe present output apparent power.
1.3.6.1.4.1.21111.1.1.5.7.1.5ColumnupsOutTruePowerread-onlycurrentThe present output true power.
1.3.6.1.4.1.21111.1.1.5.7.1.6ColumnupsOutPowerFactorread-onlycurrentOutput true power/apparent power factor
1.3.6.1.4.1.21111.1.1.5.7.1.7ColumnupsOutPercentLoadread-onlycurrentThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent…
1.3.6.1.4.1.21111.1.1.5.7.1.8ColumnupsOutLineVoltageread-onlycurrentThe output line voltage of the UPS system. if upsOutLineIndex =1, upsOutLineVoltage = Line voltage of RS phase; if upsOutLineIndex =2, upsOutLineVoltage = Line…
1.3.6.1.4.1.21111.1.1.5.7.1.9ColumnupsOutFrequencyread-onlycurrentThe present output frequency.
1.3.6.1.4.1.21111.1.1.5.8ScalarupsOutTtlVoltageread-onlycurrentTotal output voltage .
1.3.6.1.4.1.21111.1.1.5.9ScalarupsOutTtlCurrentread-onlycurrentTotal output current.
1.3.6.1.4.1.21111.1.1.5.10ScalarupsOutStatusread-onlycurrentFor HVDC device. char status[4]; status[0]status[1]:00, no output1; 01, line output1; 02, bat output1 status[2]status[3]:00, no output2; 01, line output2; 02, …
1.3.6.1.4.1.21111.1.1.5.11ScalarupsOutSource2read-onlycurrentFor HVDC(protocol:P12) machine. The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no…
1.3.6.1.4.1.21111.1.1.6NodeupsBypass
1.3.6.1.4.1.21111.1.1.6.1ScalarupsByFrequencyread-onlycurrentThe present bypass frequency.
1.3.6.1.4.1.21111.1.1.6.2ScalarupsByNumLinesread-onlycurrentThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
1.3.6.1.4.1.21111.1.1.6.3TableupsByTablenot-accessiblecurrentA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.
1.3.6.1.4.1.21111.1.1.6.3.1RowupsByEntrynot-accessiblecurrentAn entry containing information applicable to a particular bypass input.
1.3.6.1.4.1.21111.1.1.6.3.1.1ColumnupsByLineIndexread-onlycurrentThe bypass line identifier.
1.3.6.1.4.1.21111.1.1.6.3.1.2ColumnupsByVoltageread-onlycurrentThe present bypass voltage.
1.3.6.1.4.1.21111.1.1.6.3.1.3ColumnupsByCurrentread-onlycurrentThe present bypass current.
1.3.6.1.4.1.21111.1.1.6.3.1.4ColumnupsByPowerread-onlycurrentThe present true power conveyed by the bypass.
1.3.6.1.4.1.21111.1.1.6.3.1.5ColumnupsByLineVoltageread-onlycurrentThe present bypass line voltage. if upsByLineIndex=1,upsByLineVoltage=Line voltage of RS phase; if upsByLineIndex=2,upsByLineVoltage=Line voltage of ST phase; …
1.3.6.1.4.1.21111.1.1.7NodeupsTest
1.3.6.1.4.1.21111.1.1.7.1ScalarupsTstBatteryTestread-writecurrentThis object specify the battery test type and initiate battery test. If battTestWithTime selected, the test time is refer to upsTestBatteryTestTime.
1.3.6.1.4.1.21111.1.1.7.2ScalarupsTstBatteryTestResultread-onlymandatoryThe results of the current or last UPS diagnostics test performed. The values for donePassed(1), doneWarning(2), and doneError(3) indicate that the test comple…
1.3.6.1.4.1.21111.1.1.7.3ScalarupsTstBatteryTestStartTimeread-onlycurrentThe value of the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestBatte…
1.3.6.1.4.1.21111.1.1.7.4ScalarupsTstBatterySettingTimeread-writemandatoryThe object specify the test time for battery test, the unit is seconds
1.3.6.1.4.1.21111.1.1.8NodeupsControl
1.3.6.1.4.1.21111.1.1.8.1ScalarupsCtlShutdownDelayread-writecurrentThe delay in seconds the UPS remains on after being told to turn off. if value=-2 cancel shutdown, if value=-1 donothing, value=0 shutdown ups immediately
1.3.6.1.4.1.21111.1.1.8.2ScalarupsCtlSleepTimeread-writecurrentThe time in minutes for the UPS to go to sleep when instructed. When in sleep mode, the UPS will not provide output power regardless of the input line state. O…
1.3.6.1.4.1.21111.1.1.8.3ScalarupsCtlStartupAfterDelayread-writecurrentSetting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. -1 mean not startup. must set upsCtl…
1.3.6.1.4.1.21111.1.1.8.4ScalarupsCtlbuzzerread-writecurrentSetting this object to 'on' or 'off' to enable or disable buzzer
1.3.6.1.4.1.21111.1.1.8.5ScalarupsCtlRemoteControlUPSread-writecurrentSetting this object to turn 'on' or 'off' UPS
1.3.6.1.4.1.21111.1.1.8.6ScalarupsCtloutletPoweronwrite-onlycurrentSetting this object to 1 means 1st outlet,2 means 2nd outlet , immediately process
1.3.6.1.4.1.21111.1.1.8.7ScalarupsCtloutletPoweroffwrite-onlycurrentSetting this object to 1 means 1st outlet, 2 means 2nd outlet , immediately process
1.3.6.1.4.1.21111.1.1.8.8ScalarupsCtlOutlet1Powerofftimeread-writecurrentsetting this object to -1 means this control not effect, 0 means immediately process, >0 means wait times unit is minutes use in battery mode
1.3.6.1.4.1.21111.1.1.8.9ScalarupsCtlOutlet2Powerofftimeread-writecurrentsetting this object to -1 means this control not effect, 0 means immediately process , >0 means wait times unit is minutes .use in battery mode
1.3.6.1.4.1.21111.1.1.8.10ScalarupsCtlResetConfigureread-writecurrentreset all configure para to default.
1.3.6.1.4.1.21111.1.1.9NodeagentConfig
1.3.6.1.4.1.21111.1.1.9.1ScalaragentConfigDatetimeread-writecurrentThe datetime in agent, format is (MM/DD/YYYY hh:mm:ss)
1.3.6.1.4.1.21111.1.1.10NodecommConfig
1.3.6.1.4.1.21111.1.1.10.1ScalarcommBaudRateread-writecurrentThe UPS communicate baudrate
1.3.6.1.4.1.21111.1.1.10.2ScalarcommDatabitsread-writecurrentThe UPS communicate data bits
1.3.6.1.4.1.21111.1.1.10.3ScalarcommStopbitsread-writecurrentThe UPS communicate stop bits
1.3.6.1.4.1.21111.1.1.10.4ScalarcommParityread-writecurrentThe UPS communicate Parity
1.3.6.1.4.1.21111.1.1.10.5ScalarcommTimeoutread-writecurrentThe UPS communicate timeout
1.3.6.1.4.1.21111.1.1.11NodeupsConfig
1.3.6.1.4.1.21111.1.1.11.1ScalarupsCfgAlarmbypassread-writecurrentSetting this object enable /disable alarm bypass mode
1.3.6.1.4.1.21111.1.1.11.2ScalarupsCfgAlarmbatteryread-writecurrentSetting this object enable/disable alarm battery mode
1.3.6.1.4.1.21111.1.1.11.3ScalarupsCfgAutoRebootread-writecurrentSetting this object enable/disable auto reboot
1.3.6.1.4.1.21111.1.1.11.4ScalarupsCfgBypasswhenupsoffread-writecurrentSetting this object start/stop bypass when ups off
1.3.6.1.4.1.21111.1.1.11.5ScalarupsCfgBatterDDPread-writecurrentSetting this object to enable/disable battery deep-discharge protection
1.3.6.1.4.1.21111.1.1.11.6ScalarupsCfgConvertermoderead-writecurrentSetting this object to enable/disable converter mode
1.3.6.1.4.1.21111.1.1.11.7ScalarupsCfgECOmoderead-writecurrentSetting this object to enable/disable ECO mode
1.3.6.1.4.1.21111.1.1.11.8ScalarupsCfgAdvanceECOmoderead-writecurrentSetting this object to enable/disable advance ECO mode
1.3.6.1.4.1.21111.1.1.11.9ScalarupsCfgGreenPowerFunctionread-writecurrentSetting this object to enable/disable green power function
1.3.6.1.4.1.21111.1.1.11.10ScalarupsCfgBatteryOSCread-writecurrentSetting this object to enable/disable battery open status check
1.3.6.1.4.1.21111.1.1.11.11ScalarupsCfgAllowShort3timesread-writecurrentSetting this object to enable/disable short 3 times
1.3.6.1.4.1.21111.1.1.11.12ScalarupsCfgColdstartread-writecurrentSetting this object to cold start ups
1.3.6.1.4.1.21111.1.1.11.13ScalarupsCfgBypassNotAllowedread-writecurrentSetting this object to enable/disable bypass mode
1.3.6.1.4.1.21111.1.1.11.14ScalarupsCfgBatterylowprotectread-writecurrentSetting this object to enable/disable battery low protect
1.3.6.1.4.1.21111.1.1.11.15ScalarupsCfgP1progoutletcontrolread-writecurrentSetting this object to enable/disable p1 programmable outlet control (battery mode)
1.3.6.1.4.1.21111.1.1.11.16ScalarupsCfgP2progoutletcontrolread-writecurrentSetting this object to enable/disable p2 programmable outlet control (battery mode)
1.3.6.1.4.1.21111.1.1.11.17ScalarupsCfgInverterShortClearread-writecurrentSetting this object to enable/disable Inverter short clear function
1.3.6.1.4.1.21111.1.1.11.18ScalarupsCfgSitefaildetectionread-writecurrentSetting this object to enable/disable site fail detection
1.3.6.1.4.1.21111.1.1.11.19ScalarupsCfgBatNumInParallelread-writecurrentBattery numbers in parallel (battery numbers setting)
1.3.6.1.4.1.21111.1.1.11.20ScalarupsCfgBatNumInSeriesread-writecurrentBattery numbers in series (battery numbers setting)
1.3.6.1.4.1.21111.1.1.11.21ScalarupsCfgBypassmaxvoltageread-writecurrentBypass mode max voltage
1.3.6.1.4.1.21111.1.1.11.22ScalarupsCfgBypassminvoltageread-writecurrentBypass mode min voltage
1.3.6.1.4.1.21111.1.1.11.23ScalarupsCfgBypassmaxfrequencyread-writecurrentBypass mode max frequency ,for 50 HZ (510..600) for 60HZ (610..700)
1.3.6.1.4.1.21111.1.1.11.24ScalarupsCfgBypassminfrequencyread-writecurrentBypass mode min frequency, for 50HZ (400..490) for 60Hz (500..590)
1.3.6.1.4.1.21111.1.1.11.25ScalarupsCfgECOmaxvoltageread-writecurrentECO mode max voltage
1.3.6.1.4.1.21111.1.1.11.26ScalarupsCfgECOminvoltageread-writecurrentECO mode min voltage
1.3.6.1.4.1.21111.1.1.11.27ScalarupsCfgFreeRunMaxFrequencyread-writecurrentFree run mode max frequency
1.3.6.1.4.1.21111.1.1.11.28ScalarupsCfgFreeRunMinFrequencyread-writecurrentFree run mode min frequency
1.3.6.1.4.1.21111.1.1.11.29ScalarupsCfgEPOStatusread-onlycurrentGet EPO status,configured by mamual
1.3.6.1.4.1.21111.1.1.11.30ScalarupsCfgQSK1Statusread-onlycurrentGet QSK 1 status
1.3.6.1.4.1.21111.1.1.11.31ScalarupsCfgQSK2Statusread-onlycurrentGet QSK 2 status
1.3.6.1.4.1.21111.1.1.11.32ScalarupsCfgQSKT1Delaytimeread-onlycurrentGet QSKT 1 time delay
1.3.6.1.4.1.21111.1.1.11.33ScalarupsCfgQSKT2Delaytimeread-onlycurrentGet QSKT 2 time delay
1.3.6.1.4.1.21111.1.1.11.34ScalarupsCfgConstantPhaseAngleread-writecurrentsetting this object to Enable/disable Constant Phase Angle function
1.3.6.1.4.1.21111.1.1.11.35ScalarupsCfgInPhaseAngleread-onlycurrentGet input phase angle
1.3.6.1.4.1.21111.1.1.11.36ScalarupsCfgOutPhaseAngleread-writecurrentSet output phase angle
1.3.6.1.4.1.21111.1.1.11.37ScalarupsCfgLimiRunOnBatModeread-writecurrentEnable/disable limited runtime on battery mode
1.3.6.1.4.1.21111.1.1.11.38ScalarupsCfgChargingCurrentread-onlycurrentSet charging current to battery .
1.3.6.1.4.1.21111.1.1.11.39ScalarupsCfgBatSeftCheckVoltread-writecurrentBatTest until battery voltage lower than <nnn>
1.3.6.1.4.1.21111.1.1.11.40ScalarupsCfgOverChargVoltread-writecurrentset over charging voltage to per battery
1.3.6.1.4.1.21111.1.1.11.41ScalarupsCfgBattUnderVoltread-writecurrentset battery under voltage of setting value.value is a number ranging from 200V to 240V
1.3.6.1.4.1.21111.1.1.11.42ScalarupsCfgBattLowVoltread-writecurrentset battery low voltage of setting value.it is 10 to 40V high than battery under voltage. it is 10 to 40V high than battery under voltage.default 20. it means …
1.3.6.1.4.1.21111.1.1.11.43ScalarupsCfgIn1VoltHLossread-writecurrentset input1 voltage high loss point.
1.3.6.1.4.1.21111.1.1.11.44ScalarupsCfgIn1VoltLLossread-writecurrentset input1 voltage low loss point.
1.3.6.1.4.1.21111.1.1.11.45ScalarupsCfgIn2VoltHLossread-writecurrentset input2 voltage high loss point.
1.3.6.1.4.1.21111.1.1.11.46ScalarupsCfgIn2VoltLLossread-writecurrentset input2 voltage low loss point.
1.3.6.1.4.1.21111.1.1.11.47ScalarupsCfgBatteryTurnOnread-writecurrentEnable/disable battery turn on.
1.3.6.1.4.1.21111.1.1.12NodeupsTraps
1.3.6.1.4.1.21111.1.1.12.1NodecmpACFailureAC failure
1.3.6.1.4.1.21111.1.1.12.2NodecmpFanFailureFan failure
1.3.6.1.4.1.21111.1.1.12.3NodecmpUPSFailureUPS failure
1.3.6.1.4.1.21111.1.1.12.4NodecmpChargerFailureCharger failure
1.3.6.1.4.1.21111.1.1.12.5NodecmpOverloadFailureOverload failure
1.3.6.1.4.1.21111.1.1.12.6NodecmpOvertempFailureOver temperature fault.
1.3.6.1.4.1.21111.1.1.12.7NodecmpInvertershortcircuitedInverter short-circuited
1.3.6.1.4.1.21111.1.1.12.8NodecmpbatteryfusebeingocBattery fuse being open-dcircuited failure
1.3.6.1.4.1.21111.1.1.12.9NodecmpLowbatteryThe UPS has returned from a low battery condition.
1.3.6.1.4.1.21111.1.1.12.10NodecmpSysgotoshutdownSystem is going to shutdown
1.3.6.1.4.1.21111.1.1.12.11NodecmpSitefaultSite fault
1.3.6.1.4.1.21111.1.1.12.12NodecmpPhasesequenceincorrectPhase sequence incorrect
1.3.6.1.4.1.21111.1.1.12.13NodecmpPhasesequenceincorrectbypassPhase sequence incorrect in bypass
1.3.6.1.4.1.21111.1.1.12.14NodecmpFanalarmFan alarm.
1.3.6.1.4.1.21111.1.1.12.15NodecmpEPOenabledEPO enabled
1.3.6.1.4.1.21111.1.1.12.16NodecmpUnabletotrunonUPSUnalbe to turn on UPS
1.3.6.1.4.1.21111.1.1.12.17NodecmpOvertemperaturealarmOver temperature alarm
1.3.6.1.4.1.21111.1.1.12.18NodecmpInputfrequnstablebypassInput frequency unstable in bypass
1.3.6.1.4.1.21111.1.1.12.19NodecmpChargeralarmCharger alarm
1.3.6.1.4.1.21111.1.1.12.20NodecmpL1inputfusenotworkL1 input fuse not working
1.3.6.1.4.1.21111.1.1.12.21NodecmpNeutralnotConnectedNeutral not connected
1.3.6.1.4.1.21111.1.1.12.22NodecmpL2inputfusenotworkL2 input fuse not working
1.3.6.1.4.1.21111.1.1.12.23NodecmpL3inputfusenotworkL3 input fuse not working
1.3.6.1.4.1.21111.1.1.12.24NodecmpPositivePFCabnormalL1Positive PFC abnormal in L1
1.3.6.1.4.1.21111.1.1.12.25NodecmpNegativePFCabnormalL1Negative PFC abnormal in L1
1.3.6.1.4.1.21111.1.1.12.26NodecmpPositivePFCabnormalL2Positive PFC abnormal in L2
1.3.6.1.4.1.21111.1.1.12.27NodecmpNegativePFCabnormalL2Negative PFC abnormal in L2
1.3.6.1.4.1.21111.1.1.12.28NodecmpPositivePFCabnormalL3Positive PFC abnormal in L3
1.3.6.1.4.1.21111.1.1.12.29NodecmpNegativePFCabnormalL3Negative PFC abnormal in L3
1.3.6.1.4.1.21111.1.1.12.30NodecmpBusvoltagenotwdsBus voltage not within default setting
1.3.6.1.4.1.21111.1.1.12.31NodecmpBusvoltageovermaxvalueBus voltage over maxinum value
1.3.6.1.4.1.21111.1.1.12.32NodecmpBusvoltagebelowminvalueBus voltage below mininum value
1.3.6.1.4.1.21111.1.1.12.33NodecmpBusvoltagediffoutofrangeBus voltage differences out fo acceptable range
1.3.6.1.4.1.21111.1.1.12.34NodecmpBusvoltageofsloperatetoofastBus voltage of slope rate drops too fast
1.3.6.1.4.1.21111.1.1.12.35NodecmpOvercurrentinPFCIIWARNING:Over current in PFC input inductor.
1.3.6.1.4.1.21111.1.1.12.36NodecmpInvertervoloutofrangeInverter voltage not within default setting.
1.3.6.1.4.1.21111.1.1.12.37NodecmpInvertervolovermaxvalueInverter voltage over maximum value.
1.3.6.1.4.1.21111.1.1.12.38NodecmpInvertervolbelowminvalueInverter voltage below minimum value.
1.3.6.1.4.1.21111.1.1.12.39NodecmpBatteryoppositelyconnectedBattery oppositely connected.
1.3.6.1.4.1.21111.1.1.12.40NodecmpL2phaseshortcicuitedL2Phase inverter short-cicuited.
1.3.6.1.4.1.21111.1.1.12.41NodecmpL3phaseshortcicuitedL3Phase inverter short-cicuited.
1.3.6.1.4.1.21111.1.1.12.42NodecmpL1L2invertershortcicuitedL1L2Inverter short-cicuited.
1.3.6.1.4.1.21111.1.1.12.43NodecmpL2L3invertershortcicuitedL2L3Inverter short-cicuited.
1.3.6.1.4.1.21111.1.1.12.44NodecmpL3L1invertershortcicuitedL3L1Inverter short-cicuited.
1.3.6.1.4.1.21111.1.1.12.45NodecmpL1negativepoweroutofrangeL1 inverter negative powere out of acceptable range.
1.3.6.1.4.1.21111.1.1.12.46NodecmpL2negativepoweroutofrangeL2 inverter negative powere out of acceptable range.
1.3.6.1.4.1.21111.1.1.12.47NodecmpL3negativepoweroutofrangeL3 inverter negative powere out of acceptable range.
1.3.6.1.4.1.21111.1.1.12.48NodecmpBatterySCRshortcircuitedBattery SCR short-circuited.
1.3.6.1.4.1.21111.1.1.12.49NodecmpLineSCRshortcircuitedLine SCR short-circuited.
1.3.6.1.4.1.21111.1.1.12.50NodecmpInverterrelayopenfaultInverter relay open fault.
1.3.6.1.4.1.21111.1.1.12.51NodecmpInverterrelayshortcircuitedInverter relay short-circuited.
1.3.6.1.4.1.21111.1.1.12.52NodecmpInoutwiresoppositelyconnectedInput and output wires oppositely connected.
1.3.6.1.4.1.21111.1.1.12.53NodecmpabnormalcanbuscommunicationAbnormal in CAN-bus communication.
1.3.6.1.4.1.21111.1.1.12.54NodecmpcommfailurebcupsboardCommunication failure between cpus in control board.Or DSP and MCU communication error
1.3.6.1.4.1.21111.1.1.12.55NodecmpabnormalsyncsignalcircuitAbnomal in synchronous signal circuit.
1.3.6.1.4.1.21111.1.1.12.56NodecmpabnormalsyncpulsesignalcircuitAbnomal in synchronous pulse signal circuit.
1.3.6.1.4.1.21111.1.1.12.57Nodecmpcurrent3punbalancedetectedWarning for a three-phase input current unbalance detected.
1.3.6.1.4.1.21111.1.1.12.58NodecmpbatteryselftestfailureBattery self-test failure.
1.3.6.1.4.1.21111.1.1.12.59NodecmpintercurrentunbalanceInverter inter-current unbalance.
1.3.6.1.4.1.21111.1.1.12.60NodecmpbatterydisconnectedBattery disconnected.
1.3.6.1.4.1.21111.1.1.12.61NodecmpabnormalhostsignalcircuitAbnormal in host signal circuit.
1.3.6.1.4.1.21111.1.1.12.62NodecmpbatteryoverchargedBettery overcharged.
1.3.6.1.4.1.21111.1.1.12.63NodecmpbatteryvoltoohighBettery voltage is too high.
1.3.6.1.4.1.21111.1.1.12.64NodecmpbatteryvoltoolowBettery voltage is too low.
1.3.6.1.4.1.21111.1.1.12.65NodecmpfemaleconnectornotconnwellFemale connector of parallel cable not connected well.
1.3.6.1.4.1.21111.1.1.12.66NodecmpmaleconnectornotconnwellMale connector of parallel cable not connected well.
1.3.6.1.4.1.21111.1.1.12.67NodecmplockingbypassA3COW30MLocking inbypass mode after 3 consecutive overloads within 30 minutes
1.3.6.1.4.1.21111.1.1.12.68NodecmpparallelcabledisconnectedParallel cable disconnected
1.3.6.1.4.1.21111.1.1.12.69NodecmpsyncpulsecircuitfaultSynchronous pulse signal circuit fault
1.3.6.1.4.1.21111.1.1.12.70NodecmpsyncsignalcircuitfaltSynchronous signal circuit fault
1.3.6.1.4.1.21111.1.1.12.71NodecmphostsignalcircuitfaultHost signal circuit fault
1.3.6.1.4.1.21111.1.1.12.72NodecmpcanbuscommunicationfaultCan-bus communication fault
1.3.6.1.4.1.21111.1.1.12.73NodecmplowlosspointforvolinACmodeLow loss point for voltage in ac mode not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.74NodecmphighlosspointforvolinACmodeHigh loss point for voltage in ac mode not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.75NodecmplowlosspointforfreqinACmodeLow loss point for frequency in ac mode not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.76NodecmphighlosspointforfreqinACmodeHigh loss point for frequency in ac mode not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.77NodecmplowlosspointforvolinbypassmodeLow loss point for voltage in bypass mode not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.78NodecmphighlosspointforvolinbypassmodeHigh loss point for voltage in bypass mode not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.79NodecmplowlosspointforfreqinbypassmodeLow loss point for frequency in bypass mode not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.80NodecmphighlosspointforfreqinbypassmodeHigh loss point for frequency in bypass mode not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.81NodecmploadunbalancedLoad unbalanced
1.3.6.1.4.1.21111.1.1.12.82NodecmpoverloadalarmOverload alarm
1.3.6.1.4.1.21111.1.1.12.83NodecmpparallelnotconnectedwellParallel cable not connected well
1.3.6.1.4.1.21111.1.1.12.84NodecmpcommunicationlostCommunication lost
1.3.6.1.4.1.21111.1.1.12.85NodecmpbatteryconnnotsonsistentBattery connection not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.86NodecmpconverternotconsisstentConverter setting not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.87NodecmpbypassnotallownotconsistentBypass not allowed setting not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.88NodecmpACconnnotconsistentAC connection not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.89Nodecmpinput3pcurrentunbalanceWarning for three-phase ac input current unbalance
1.3.6.1.4.1.21111.1.1.12.90NodecmpbypassconnnotconsistentBypass connection not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.91NodecmpbatteryprotectionnotconsistentBattery protection setting not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.92NodecmpbatterydetectionnotconsistentBattery detection setting not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.93NodecmpupsmodeltypesnotconsistentUPS model types not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.94NodecmpbypassnotconsistentBypass setting not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.95NodecmpcapacitynotconsistentCapacity of upss not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.96NodecmpautorestartnotconsistentAuto restart setting not consistent in parallel systems
1.3.6.1.4.1.21111.1.1.12.97NodecmpBatteryReplaceBattery need to be replace
1.3.6.1.4.1.21111.1.1.12.100NodecmpACNormalAC normal
1.3.6.1.4.1.21111.1.1.12.103NodecmpOutputBadAlarmOutput bad alarm
1.3.6.1.4.1.21111.1.1.12.104NodecmpBypassBadAlarmBypass bad alarm
1.3.6.1.4.1.21111.1.1.12.105NodecmpOutputOffAlarmOutput off alarm
1.3.6.1.4.1.21111.1.1.12.106NodecmpUPSShutAlarmUPS shutdown alarm
1.3.6.1.4.1.21111.1.1.12.107NodecmpSystemOffAlarmSystem off alarm
1.3.6.1.4.1.21111.1.1.12.108NodecmpFuseFailureAlarmFuse failure alarm
1.3.6.1.4.1.21111.1.1.12.109NodecmpGenFailureAlarmGeneral failure alarm
1.3.6.1.4.1.21111.1.1.12.110NodecmpAwaitPowerAlarmAwaiting power alarm
1.3.6.1.4.1.21111.1.1.12.111NodecmpShutPendingAlarmShutdown pending alarm
1.3.6.1.4.1.21111.1.1.12.112NodecmpBatDepletedBattery depleted
1.3.6.1.4.1.21111.1.1.12.113NodecmpUnknowStatusBattery unknow status
1.3.6.1.4.1.21111.1.1.12.114NodecmpOutputOnOutput on
1.3.6.1.4.1.21111.1.1.12.115NodecmpTurntobypassUps turn to bypass mode
1.3.6.1.4.1.21111.1.1.12.116NodecmpTurntobatteryUps turn to battery mode
1.3.6.1.4.1.21111.1.1.12.117NodecmpOutBoosterTurn to booster
1.3.6.1.4.1.21111.1.1.12.118NodecmpOutReducerTurn to reducer
1.3.6.1.4.1.21111.1.1.12.119NodecmpOutBattestTurn to battery test mode
1.3.6.1.4.1.21111.1.1.12.120NodecmpOtherSourceOther source
1.3.6.1.4.1.21111.1.1.12.121NodecmpBatfailureBattery failure
1.3.6.1.4.1.21111.1.1.12.122NodecmpBatTestDonePassedBattery test passed
1.3.6.1.4.1.21111.1.1.12.123NodecmpBatTestDoneWarningBattery test done warning
1.3.6.1.4.1.21111.1.1.12.124NodecmpBatTestDoneAbortedBattery test done Aborted
1.3.6.1.4.1.21111.1.1.12.125NodecmpBatteryNormalBattery normal
1.3.6.1.4.1.21111.1.1.12.126NodecmpBatteryDischargingBattery Discharging
1.3.6.1.4.1.21111.1.1.12.127NodecmpP1cutoffprealarmP1 cut off pre-alarm
1.3.6.1.4.1.21111.1.1.12.128NodecmpInputPhaseErrorWarning for input phase error for LV 6-10K UPS
1.3.6.1.4.1.21111.1.1.12.129NodecmpMaintainSwitchOpenalarmWarning for maintain switch open
1.3.6.1.4.1.21111.1.1.12.130NodecmpEMDChAbnormal1EMD Channels 1 Abnormal
1.3.6.1.4.1.21111.1.1.12.131NodecmpEMDChAbnormal2EMD Channels 2 Abnormal
1.3.6.1.4.1.21111.1.1.12.132NodecmpEMDChAbnormal3EMD Channels 3 Abnormal
1.3.6.1.4.1.21111.1.1.12.133NodecmpEMDChAbnormal4EMD Channels 4 Abnormal
1.3.6.1.4.1.21111.1.1.12.134NodecmpEMDChAbnormal5EMD Channels 5 Abnormal: smoke alarm
1.3.6.1.4.1.21111.1.1.12.135NodecmpEMDChAbnormal6EMD Channels 6 Abnormal
1.3.6.1.4.1.21111.1.1.12.136NodecmpEMDChAbnormal7EMD Channels 7 Abnormal
1.3.6.1.4.1.21111.1.1.12.137NodecmpEMDChAbnormal8EMD Channels 8 Abnormal
1.3.6.1.4.1.21111.1.1.12.998Scalartrapleafnodev103not-accessiblecurrentThe share trap-node for send all traps,snmpcard V1-03 and later use this trap-node char trap[16]; trap[0]: trap[0]=1,fault trap ; trap[0]=0,warn trap
1.3.6.1.4.1.21111.1.1.12.999Scalartrapleafnodev1v2not-accessiblecurrentThe share trap-node for send all traps
1.3.6.1.4.1.21111.1.1.13Nodeextend
1.3.6.1.4.1.21111.1.1.13.1ScalarextendWorkTemperatureread-onlycurrentThe temperature of work environment
1.3.6.1.4.1.21111.1.1.13.2ScalarextendWorkhumidityread-onlycurrentThe humidity of work environment
1.3.6.1.4.1.21111.1.1.13.3ScalarextendSmokeScoperead-onlycurrentThe smokeScope of work environment
1.3.6.1.4.1.21111.1.1.13.4ScalarextendEMDAlarm1read-onlycurrentEnvironment detector alarm 1
1.3.6.1.4.1.21111.1.1.13.5ScalarextendEMDAlarm2read-onlycurrentEnvironment detector alarm 2
1.3.6.1.4.1.21111.1.1.13.6ScalarextendEMDAlarm3read-onlycurrentEnvironment detector alarm 3
1.3.6.1.4.1.21111.1.1.13.7ScalarextendEMDAlarm4read-onlycurrentEnvironment detector alarm 4
1.3.6.1.4.1.21111.1.2Nodeinverter
1.3.6.1.4.1.21111.1.2.1NodesolarIdent
1.3.6.1.4.1.21111.1.2.1.1ScalarsolarIdManufacturerread-onlymandatoryThe name of the solar manufacturer.
1.3.6.1.4.1.21111.1.2.1.2ScalarsolarIdProtocolread-onlymandatoryThe solar Protocol id.
1.3.6.1.4.1.21111.1.2.1.3ScalarsolarIdModelNameread-onlymandatoryThe solar Model designation.
1.3.6.1.4.1.21111.1.2.1.4ScalarsolarIdSerialNumberread-onlymandatoryThe solar serial no.
1.3.6.1.4.1.21111.1.2.1.5ScalarsolarIdFWVersionread-onlymandatoryMain CPU firmware version.
1.3.6.1.4.1.21111.1.2.1.6ScalarsolarIdFW2Versionread-onlymandatoryMain CPU 2 firmware version.
1.3.6.1.4.1.21111.1.2.1.7ScalarsolarIdSolarTyperead-onlymandatorysolar type.
1.3.6.1.4.1.21111.1.2.1.8ScalarsolarIdTopologyread-onlymandatorysolar Topology.
1.3.6.1.4.1.21111.1.2.1.9ScalarsolarIdCriterionread-onlymandatorysolar device criterion.
1.3.6.1.4.1.21111.1.2.2NodesolarRating
1.3.6.1.4.1.21111.1.2.2.1ScalarsolarRatOutPowerread-onlycurrentThe rating Output Power of solar inverter
1.3.6.1.4.1.21111.1.2.2.2ScalarsolarRatApparentPowerread-onlycurrentThe rating output apparent power of solar inverter
1.3.6.1.4.1.21111.1.2.2.3ScalarsolarRatGridVoltageread-onlycurrentThe rating output voltage of solar inverter
1.3.6.1.4.1.21111.1.2.2.4ScalarsolarRatGridFrequencyread-onlycurrentThe rating grid frequency of solar inverter
1.3.6.1.4.1.21111.1.2.2.5ScalarsolarRatGridCurrentread-onlycurrentThe rating grid current of solar inverter
1.3.6.1.4.1.21111.1.2.2.6ScalarsolarRatPerMPPTCurrentread-onlycurrentPer MPPT rating current
1.3.6.1.4.1.21111.1.2.2.7ScalarsolarRatPVInputVoltageread-onlycurrentNominal device Voltage,pv input Voltage
1.3.6.1.4.1.21111.1.2.2.8ScalarsolarRatACOutVoltageread-writecurrentThe rating AC output voltage of solar inverter
1.3.6.1.4.1.21111.1.2.2.9ScalarsolarRatACOutCurrentread-onlycurrentThe rating AC output current of solar inverter
1.3.6.1.4.1.21111.1.2.2.10ScalarsolarRatBatVoltageread-onlycurrentThe rating battery voltage of solar inverter
1.3.6.1.4.1.21111.1.2.3NodesolarBattery
1.3.6.1.4.1.21111.1.2.3.1ScalarsolarBatStatusread-onlymandatoryThe indication of the status in the solar system's batteries.
1.3.6.1.4.1.21111.1.2.3.2ScalarsolarBatSecondsOnBatteryread-onlycurrentIf the unit is on battery power, the elapsed time since the solar last switched to battery power, or the time since the network management subsystem was last r…
1.3.6.1.4.1.21111.1.2.3.3ScalarsolarBatEstMinutesRemainingread-onlycurrentAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.21111.1.2.3.4ScalarsolarBatEstChargeRemainingread-onlycurrentAn estimate of the battery charge remaining expressed as a percent of full charge.
1.3.6.1.4.1.21111.1.2.3.5ScalarsolarBatPBatVoltageread-onlycurrentThe magnitude of the present Positive battery voltage.
1.3.6.1.4.1.21111.1.2.3.6ScalarsolarBatNBatVoltageread-onlycurrentThe magnitude of the present negative battery voltage.
1.3.6.1.4.1.21111.1.2.3.7ScalarsolarBatPBatCurrentread-onlycurrentThe positive battery present current.
1.3.6.1.4.1.21111.1.2.3.8ScalarsolarBatNBatCurrentread-onlycurrentThe present negative battery current.
1.3.6.1.4.1.21111.1.2.3.9ScalarsolarBatPBatChargCurrentread-onlycurrentThe Positive battery charging current.
1.3.6.1.4.1.21111.1.2.3.10ScalarsolarBatNBatchargCurrentread-onlycurrentThe present negative battery charging current.
1.3.6.1.4.1.21111.1.2.3.11ScalarsolarBatPBatDischargCurrentread-onlycurrentThe present positive battery discharging current.
1.3.6.1.4.1.21111.1.2.3.12ScalarsolarBatNBatDischargCurrentread-onlycurrentThe present negative battery discharging current.
1.3.6.1.4.1.21111.1.2.3.13ScalarsolarBatTemperatureread-onlycurrentThe ambient temperature at or near the solar Battery casing.
1.3.6.1.4.1.21111.1.2.3.14ScalarsolarBatNumberInSeriesread-onlycurrentThe number of battery in series.
1.3.6.1.4.1.21111.1.2.3.15ScalarsolarBatNumberInParallelread-onlycurrentThe number of battery in Parallel.
1.3.6.1.4.1.21111.1.2.3.16ScalarsolarBatChargingCurrentread-onlycurrentCharging Current.
1.3.6.1.4.1.21111.1.2.4NodesolarGrid
1.3.6.1.4.1.21111.1.2.4.1ScalarsolarGridSourceread-onlycurrentThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.21111.1.2.4.2ScalarsolarGridTtlApparentPowerread-onlycurrentTotal grid output apparent power .
1.3.6.1.4.1.21111.1.2.4.3ScalarsolarGridTtlTruePowerread-onlycurrentTotal grid output active(true) power .
1.3.6.1.4.1.21111.1.2.4.4ScalarsolarGridFrequencyread-onlycurrentTotal grid frequency.
1.3.6.1.4.1.21111.1.2.4.5ScalarsolarGridNumLineread-onlycurrentThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.
1.3.6.1.4.1.21111.1.2.4.6ScalarsolarGridTemperatureread-onlycurrentMax Temperature of the detecting pointers.
1.3.6.1.4.1.21111.1.2.4.7ScalarsolarGridStatusread-onlycurrentDevice status. b31-b16:NG b15: NG b14: NG b13: NG b12: NG b11: Load status 0: Load off 1:Load on b10: Battery status b9: Battery status b10b9: 00: Do nothing 0…
1.3.6.1.4.1.21111.1.2.4.8TablesolarGridTablenot-accessiblecurrentA list of solar grid table entries. The number of entries is given by the value of solarGridputNumLines.
1.3.6.1.4.1.21111.1.2.4.8.1RowsolarGridEntrynot-accessiblecurrentAn entry containing information applicable to a particular grid line.
1.3.6.1.4.1.21111.1.2.4.8.1.1ColumnsolarGridLineIndexread-onlycurrentThe grid line identifier.
1.3.6.1.4.1.21111.1.2.4.8.1.2ColumnsolarGridVoltageread-onlycurrentThe Grid voltage of the solar inverter
1.3.6.1.4.1.21111.1.2.4.8.1.3ColumnsolarGridCurrentread-onlycurrentThe Grid current of the solar inverter
1.3.6.1.4.1.21111.1.2.4.8.1.4ColumnsolarGridPowerread-onlycurrentThe present Grid output true power.
1.3.6.1.4.1.21111.1.2.5NodesolarACOutput
1.3.6.1.4.1.21111.1.2.5.1ScalarsolarACOutNumLinesread-onlycurrentAC output lines number.
1.3.6.1.4.1.21111.1.2.5.2ScalarsolarACOutFrequencyread-onlycurrentAC output frequency .
1.3.6.1.4.1.21111.1.2.5.3ScalarsolarACOutTtlPowerread-onlycurrentTotal AC output total active(true) power .
1.3.6.1.4.1.21111.1.2.5.4ScalarsolarACOutTtlPercentLoadread-onlycurrentTotal AC output total percent load.
1.3.6.1.4.1.21111.1.2.5.5TablesolarACOutTablenot-accessiblecurrentA list of AC output table entries. The number of entries is given by the value of solarACOut NumLines.
1.3.6.1.4.1.21111.1.2.5.5.1RowsolarACOutEntrynot-accessiblecurrentAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.21111.1.2.5.5.1.1ColumnsolarACOutLineIndexread-onlycurrentThe number of PV line identifier.
1.3.6.1.4.1.21111.1.2.5.5.1.2ColumnsolarACOutVoltageread-onlycurrentThe AC output voltage .
1.3.6.1.4.1.21111.1.2.5.5.1.3ColumnsolarACOutTruePowerread-onlycurrentThe magnitude of the present AC output true power.
1.3.6.1.4.1.21111.1.2.5.5.1.4ColumnsolarACOutCurrentread-onlycurrentThe magnitude of the present AC output current.
1.3.6.1.4.1.21111.1.2.5.5.1.5ColumnsolarACOutPercentLoadread-onlycurrentThe magnitude of the present AC output percent load
1.3.6.1.4.1.21111.1.2.6NodesolarPV
1.3.6.1.4.1.21111.1.2.6.1ScalarsolarPVNumLinesread-writecurrentPV input lines number.
1.3.6.1.4.1.21111.1.2.6.2ScalarsolarPVTtlPowerread-onlycurrentTotal PV input active(true) power .
1.3.6.1.4.1.21111.1.2.6.3TablesolarPVTablenot-accessiblecurrentA list of solar PV input table entries. The number of entries is given by the value of solarPV NumLines.
1.3.6.1.4.1.21111.1.2.6.3.1RowsolarPVEntrynot-accessiblecurrentAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.21111.1.2.6.3.1.1ColumnsolarPVLineIndexread-onlycurrentThe number of PV line identifier.
1.3.6.1.4.1.21111.1.2.6.3.1.2ColumnsolarPVVoltageread-onlycurrentThe PV input voltage .
1.3.6.1.4.1.21111.1.2.6.3.1.3ColumnsolarPVPowerread-onlycurrentThe magnitude of the present input true power.
1.3.6.1.4.1.21111.1.2.7NodesolarEnergy
1.3.6.1.4.1.21111.1.2.7.1ScalarsolarEnergyFirstTimeEnergyread-onlycurrentthe time when the user fist storage capacity
1.3.6.1.4.1.21111.1.2.7.2ScalarsolarEnergyHourTread-writecurrentwrite the hour when we will inquiry energy in the hour
1.3.6.1.4.1.21111.1.2.7.3ScalarsolarEnergyHourEread-onlycurrent0xfeffffff:doing inquiry 0xffffffff:error
1.3.6.1.4.1.21111.1.2.7.4ScalarsolarEnergyDayTread-writecurrentthe time when we will inquiry energy in the day
1.3.6.1.4.1.21111.1.2.7.5ScalarsolarEnergyDayEread-onlycurrent0xfeffffff:doing inquiry 0xffffffff:error
1.3.6.1.4.1.21111.1.2.7.6ScalarsolarEnergyMonTread-writecurrentthe time
1.3.6.1.4.1.21111.1.2.7.7ScalarsolarEnergyMonEread-onlycurrent0xfeffffff:doing inquiry 0xffffffff:error
1.3.6.1.4.1.21111.1.2.7.8ScalarsolarEnergyYearTread-writecurrentThe time
1.3.6.1.4.1.21111.1.2.7.9ScalarsolarEnergyYearEread-onlycurrent0xfeffffff:doing inquiry 0xffffffff:error
1.3.6.1.4.1.21111.1.2.7.10ScalarsolarEnergyHourIDread-onlycurrentID.
1.3.6.1.4.1.21111.1.2.7.11ScalarsolarEnergyDayIDread-onlycurrentID.
1.3.6.1.4.1.21111.1.2.7.12ScalarsolarEnergyMonIDread-onlycurrentID.
1.3.6.1.4.1.21111.1.2.7.13ScalarsolarEnergyYearIDread-onlycurrentID.
1.3.6.1.4.1.21111.1.2.8NodesolarTest
1.3.6.1.4.1.21111.1.2.8.1ScalarsolarTestStartSelfTestread-writecurrentSetting this object to 'start' to start test
1.3.6.1.4.1.21111.1.2.8.2ScalarsolarTestSelfTestResultread-onlycurrentan Integer ranging from 0 to 9. 0 means self test being processed, 1 means self test succeed, 2 means self test fail.
1.3.6.1.4.1.21111.1.2.8.3ScalarsolarTestGridOutHVolread-onlycurrentSelf test grid output high voltage
1.3.6.1.4.1.21111.1.2.8.4ScalarsolarTestGridOutLVolread-onlycurrentSelf test grid output low voltage
1.3.6.1.4.1.21111.1.2.8.5ScalarsolarTestGridOutHFreqread-onlycurrentSelf test grid output high frequency
1.3.6.1.4.1.21111.1.2.8.6ScalarsolarTestGridOutLFreqread-onlycurrentSelf test grid output low frequency
1.3.6.1.4.1.21111.1.2.8.7ScalarsolarTestChOutHVolread-onlycurrentThe check time of self test grid output high voltage
1.3.6.1.4.1.21111.1.2.8.8ScalarsolarTestChOutLVolread-onlycurrentThe check time of self test grid output low voltage
1.3.6.1.4.1.21111.1.2.8.9ScalarsolarTestChOutHFreqread-onlycurrentThe check time of self test grid output high frequency
1.3.6.1.4.1.21111.1.2.8.10ScalarsolarTestChOutLFreqread-onlycurrentThe check time of self test grid output low frequency
1.3.6.1.4.1.21111.1.2.9NodesolarDefValue
1.3.6.1.4.1.21111.1.2.9.1ScalarsolarDefGridOutVolHLossread-onlycurrentThe default setting value of grid output voltage high loss point
1.3.6.1.4.1.21111.1.2.9.2ScalarsolarDefGridOutVolLLossread-onlycurrentThe default setting value of grid output voltage lowloss point
1.3.6.1.4.1.21111.1.2.9.3ScalarsolarDefGridOutFreqHLossread-onlycurrentThe default setting value Grid output frequency high loss point
1.3.6.1.4.1.21111.1.2.9.4ScalarsolarDefGridOutFreqLLossread-onlycurrentThe default setting value Grid output frequency low loss point
1.3.6.1.4.1.21111.1.2.9.5ScalarsolarDefGridInVolHLossread-onlycurrentThe default setting value Grid input voltage high loss point
1.3.6.1.4.1.21111.1.2.9.6ScalarsolarDefGridInVolLLossread-onlycurrentThe default setting value Grid input voltage low loss point
1.3.6.1.4.1.21111.1.2.9.7ScalarsolarDefGridInFreqHLossread-onlycurrentThe default setting value Grid input frequency high loss point
1.3.6.1.4.1.21111.1.2.9.8ScalarsolarDefGridInFreqLLossread-onlycurrentThe default setting value Grid input frequency low loss point
1.3.6.1.4.1.21111.1.2.9.9ScalarsolarDefUpLimitPVVolread-onlycurrentThe default setting value The upper limit of PV input voltage
1.3.6.1.4.1.21111.1.2.9.10ScalarsolarDefLowLimitPVVolread-onlycurrentThe default setting value The lowest limit of PV input voltage
1.3.6.1.4.1.21111.1.2.9.11ScalarsolarDefPVHVolMPPTread-onlycurrentThe default setting value The PV input high voltage for MPPT
1.3.6.1.4.1.21111.1.2.9.12ScalarsolarDefPVLVolMPPTread-onlycurrentThe default setting value The PV input low voltage for MPPT
1.3.6.1.4.1.21111.1.2.9.13ScalarsolarDefMaxOutPowerread-onlycurrentThe default setting value Max output power
1.3.6.1.4.1.21111.1.2.9.14ScalarsolarDefAverageVolHLossread-onlycurrentThe default setting value Long time grid average voltage high loss point
1.3.6.1.4.1.21111.1.2.9.15ScalarsolarDefLCDSleepTimeread-onlycurrentThe default setting value LCD sleep time
1.3.6.1.4.1.21111.1.2.9.16ScalarsolarDefBatteryNumread-onlycurrentThe default setting value Battery piece number
1.3.6.1.4.1.21111.1.2.9.17ScalarsolarDefBattTtlCapacitread-onlycurrentThe default setting value Battery total capacity
1.3.6.1.4.1.21111.1.2.9.18ScalarsolarDefChargerCurrentread-onlycurrentThe default setting value Charger current
1.3.6.1.4.1.21111.1.2.9.19ScalarsolarDefMaxChargeVolread-onlycurrentThe default setting the max charging voltage
1.3.6.1.4.1.21111.1.2.9.20ScalarsolarDefMaxChargeCurrread-onlycurrentThe default setting the max charging current
1.3.6.1.4.1.21111.1.2.9.21ScalarsolarDefWaiteTimeFeedread-onlycurrentThe default setting waiting time for feeding
1.3.6.1.4.1.21111.1.2.9.22ScalarsolarDefMaxGridOutVolHLossread-onlycurrentThe max grid output voltage high loss point
1.3.6.1.4.1.21111.1.2.9.23ScalarsolarDefMinGridOutVolHLossread-onlycurrentThe min grid output voltage high loss point
1.3.6.1.4.1.21111.1.2.9.24ScalarsolarDefMaxGridOutVolLLossread-onlycurrentThe max grid output voltage low loss point
1.3.6.1.4.1.21111.1.2.9.25ScalarsolarDefMinGridOutVolLLossread-onlycurrentThe min grid output voltage low loss point
1.3.6.1.4.1.21111.1.2.9.26ScalarsolarDefMaxGridOutFreqHLossread-onlycurrentThe max grid output frequency high loss point
1.3.6.1.4.1.21111.1.2.9.27ScalarsolarDefMinGridOutFreqHLossread-onlycurrentThe min grid output frequency high loss point
1.3.6.1.4.1.21111.1.2.9.28ScalarsolarDefMaxGridOutFreqLLossread-onlycurrentThe max grid output frequency low loss point
1.3.6.1.4.1.21111.1.2.9.29ScalarsolarDefMinGridOutFreqLLossread-onlycurrentThe min grid output frequency low loss point
1.3.6.1.4.1.21111.1.2.9.30ScalarsolarDefMaxWaiteTimeFeedread-onlycurrentThe max waiting time for feeding
1.3.6.1.4.1.21111.1.2.9.31ScalarsolarDefMinWaiteTimeFeedread-onlycurrentThe min waiting time for feeding
1.3.6.1.4.1.21111.1.2.9.32ScalarsolarDefMaxMaxFChargVoltread-onlycurrentThe max voltage for max floating charging voltage
1.3.6.1.4.1.21111.1.2.9.33ScalarsolarDefMinMaxFChargVoltread-onlycurrentThe min voltage for max floating charging voltage
1.3.6.1.4.1.21111.1.2.9.34ScalarsolarDefMaxMaxRChargCurrread-onlycurrentThe upper limit of max charging current(real charging)
1.3.6.1.4.1.21111.1.2.9.35ScalarsolarDefMinMaxRChargCurrread-onlycurrentThe lower limit of max charging current(real charging)
1.3.6.1.4.1.21111.1.2.9.36ScalarsolarDefMaxMaxPVInputVoltread-onlycurrentThe upper limit of max PV input voltage
1.3.6.1.4.1.21111.1.2.9.37ScalarsolarDefMinMaxPVInputVoltread-onlycurrentThe lower limit of max PV input voltage
1.3.6.1.4.1.21111.1.2.9.38ScalarsolarDefMaxMinPVInputVoltread-onlycurrentThe upper limit of min PV input voltage
1.3.6.1.4.1.21111.1.2.9.39ScalarsolarDefMinMinPVInputVoltread-onlycurrentThe lowest limit of min PV input voltage
1.3.6.1.4.1.21111.1.2.9.40ScalarsolarDefMaxHighMPPTVoltread-onlycurrentThe max MPPT high voltage
1.3.6.1.4.1.21111.1.2.9.41ScalarsolarDefMinHighMPPTVoltread-onlycurrentThe min MPPT high voltage
1.3.6.1.4.1.21111.1.2.9.42ScalarsolarDefMaxLowMPPTVoltread-onlycurrentThe max MPPT low voltage
1.3.6.1.4.1.21111.1.2.9.43ScalarsolarDefMinLowMPPTVoltread-onlycurrentThe min MPPT low voltage
1.3.6.1.4.1.21111.1.2.9.44ScalarsolarDefMaxOutputPowerread-onlycurrentThe max output power
1.3.6.1.4.1.21111.1.2.9.45ScalarsolarDefMinOutputPowerread-onlycurrentThe min output power
1.3.6.1.4.1.21111.1.2.9.46ScalarsolarDefMaxRChargVoltread-onlycurrentThe min charging voltage
1.3.6.1.4.1.21111.1.2.9.47ScalarsolarDefMinRChargVoltread-onlycurrentThe max charging voltage
1.3.6.1.4.1.21111.1.2.10NodesolarFaultInfo
1.3.6.1.4.1.21111.1.2.10.1ScalarsolarFaultCurrentIDread-onlycurrentcurrent fault ID.
1.3.6.1.4.1.21111.1.2.10.2ScalarsolarFaultQueryFaultIDread-writecurrentquery fault ID.
1.3.6.1.4.1.21111.1.2.10.3ScalarsolarFaultQueryResultread-onlycurrentQuery fault info result.
1.3.6.1.4.1.21111.1.2.10.4ScalarsolarFaultFaultKindread-onlycurrentDevice Fault kind.
1.3.6.1.4.1.21111.1.2.10.5ScalarsolarFaultFaultTimeread-onlycurrentDevice Fault time.format is YYYYMMDDHHMMSS
1.3.6.1.4.1.21111.1.2.10.6ScalarsolarFaultPVStatusread-onlycurrentPV running status before fault. b31-b16:reserved b15 : PV1 boost on b14 : PV2 boost on b13 : PV3 boost on b12 : Inverter on b11 : 1: PV1 MPPT by boost; 0: PV1 …
1.3.6.1.4.1.21111.1.2.10.7ScalarsolarFaultTemperatureread-onlycurrentMax Temperature of the detecting pointers before fault.
1.3.6.1.4.1.21111.1.2.10.8ScalarsolarFaultBattVoltread-onlycurrentBattery voltage before fault.
1.3.6.1.4.1.21111.1.2.10.9ScalarsolarFaultPV1Voltageread-onlycurrentPV1 input voltage before fault.
1.3.6.1.4.1.21111.1.2.10.10ScalarsolarFaultPV1Currentread-onlycurrentPV1 current before fault.
1.3.6.1.4.1.21111.1.2.10.11ScalarsolarFaultPV2Voltageread-onlycurrentPV2 input voltage before fault.
1.3.6.1.4.1.21111.1.2.10.12ScalarsolarFaultPV2Currentread-onlycurrentPV2 current before fault.
1.3.6.1.4.1.21111.1.2.10.13ScalarsolarFaultPV3Voltageread-onlycurrentPV3 input voltage before fault.
1.3.6.1.4.1.21111.1.2.10.14ScalarsolarFaultPV3Currentread-onlycurrentPV3 current before fault.
1.3.6.1.4.1.21111.1.2.10.15ScalarsolarFaultNumLinesread-onlycurrentAC output,Grid and Inverter lines number.
1.3.6.1.4.1.21111.1.2.10.16ScalarsolarFaultGridFrequencyread-onlycurrentGrid frequency before fault.
1.3.6.1.4.1.21111.1.2.10.17ScalarsolarFaultACOutFrequencyread-onlycurrentAC output Frequency before fault.
1.3.6.1.4.1.21111.1.2.10.18ScalarsolarFaultLoadPercentread-onlycurrentOutput load percentage before fault.
1.3.6.1.4.1.21111.1.2.10.19TablesolarFaultTablenot-accessiblecurrentA list of fault table entries. The number of entries is given by the value of solarFault NumLines.
1.3.6.1.4.1.21111.1.2.10.19.1RowsolarFaultEntrynot-accessiblecurrentAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.21111.1.2.10.19.1.1ColumnsolarFaultLineIndexread-onlycurrentThe number of inverter,grid and ACOutput line identifier.
1.3.6.1.4.1.21111.1.2.10.19.1.2ColumnsolarFaultInverterVoltread-onlycurrentInverter voltage before fault.
1.3.6.1.4.1.21111.1.2.10.19.1.3ColumnsolarFaultInverterCurrread-onlycurrentInverter current before fault.
1.3.6.1.4.1.21111.1.2.10.19.1.4ColumnsolarFaultGridVoltageread-onlycurrentGrid voltage before fault.
1.3.6.1.4.1.21111.1.2.10.19.1.5ColumnsolarFaultGridCurrentread-onlycurrentGrid current before fault.
1.3.6.1.4.1.21111.1.2.10.19.1.6ColumnsolarFaultACOutputVoltread-onlycurrentAC output voltage before fault.
1.3.6.1.4.1.21111.1.2.10.19.1.7ColumnsolarFaultACOutputCurrread-onlycurrentAC output current before fault.
1.3.6.1.4.1.21111.1.2.11NodesolarControl
1.3.6.1.4.1.21111.1.2.11.1ScalarsolarCtlFeedGridread-writecurrentSetting this object to turn feeding grid enable(1) or disable(2)
1.3.6.1.4.1.21111.1.2.12NodesolarAgentConfig
1.3.6.1.4.1.21111.1.2.12.1ScalarsolarAgentDatetimeread-writecurrentThe datetime in agent, format is (MM/DD/YYYY hh:mm:ss)
1.3.6.1.4.1.21111.1.2.13NodesolarCommConfig
1.3.6.1.4.1.21111.1.2.13.1ScalarSolarCommBaudRateread-writecurrentThe solar inverter communicate baudrate
1.3.6.1.4.1.21111.1.2.13.2ScalarSolarCommDatabitsread-writecurrentThe solar inverter communicate data bits
1.3.6.1.4.1.21111.1.2.13.3ScalarSolarCommStopbitsread-writecurrentThe solar inverter communicate stop bits
1.3.6.1.4.1.21111.1.2.13.4ScalarSolarCommParityread-writecurrentThe solar inverter communicate Parity
1.3.6.1.4.1.21111.1.2.13.5ScalarSolarCommTimeoutread-writecurrentThe solar inverter communicate timeout
1.3.6.1.4.1.21111.1.2.14NodesolarConfig
1.3.6.1.4.1.21111.1.2.14.1ScalarsolarCfgGridOutVolHLossread-writecurrentgrid output voltage high loss point
1.3.6.1.4.1.21111.1.2.14.2ScalarsolarCfgGridOutVolLLossread-writecurrentgrid output voltage low loss point
1.3.6.1.4.1.21111.1.2.14.3ScalarsolarCfgGridOutFreqHLossread-writecurrentgrid output frequency high loss point
1.3.6.1.4.1.21111.1.2.14.4ScalarsolarCfgGridOutFreqLLossread-writecurrentgrid output frequency low loss point
1.3.6.1.4.1.21111.1.2.14.5ScalarsolarCfgCurrentMaxOutPowerread-writecurrentthe max output power. ener solar:0-030000
1.3.6.1.4.1.21111.1.2.14.6ScalarsolarCfgPVHVolMPPTread-writecurrentthe PV input high voltage for MPPT
1.3.6.1.4.1.21111.1.2.14.7ScalarsolarCfgPVLVolMPPTread-writecurrentSet the PV input low voltage for MPPT
1.3.6.1.4.1.21111.1.2.14.8ScalarsolarCfgUpLimitPVVolread-writecurrentSet the upper limit of PV input voltage
1.3.6.1.4.1.21111.1.2.14.9ScalarsolarCfgLowLimitPVVolread-writecurrentSet the lowest limit of PV input voltage
1.3.6.1.4.1.21111.1.2.14.10ScalarsolarCfgLCDSleepTimeread-writecurrentSetting LCD sleep time,0 means always light, the unit is 30s.
1.3.6.1.4.1.21111.1.2.14.11ScalarsolarCfgGridInVolHLossread-writecurrentSet grid input voltage high loss point
1.3.6.1.4.1.21111.1.2.14.12ScalarsolarCfgGridInVolLLossread-writecurrentSet grid input voltage low loss point
1.3.6.1.4.1.21111.1.2.14.13ScalarsolarCfgGridInFreqHLossread-writecurrentgrid input frequency high loss point
1.3.6.1.4.1.21111.1.2.14.14ScalarsolarCfgGridInFreqLLossread-writecurrentgrid input frequency low loss point
1.3.6.1.4.1.21111.1.2.14.15ScalarsolarCfgAverageVolHLossread-writecurrentthe grid long time average voltage high loss point
1.3.6.1.4.1.21111.1.2.14.16ScalarsolarCfgAverageVolLLossread-writecurrentthe grid long time average voltage low loss point
1.3.6.1.4.1.21111.1.2.14.17ScalarsolarCfgSetDefaultValueread-writecurrentSetting control parsameter to default valuse
1.3.6.1.4.1.21111.1.2.14.18ScalarsolarCfgWaiteTimeFeedread-writecurrentSetting waiting time for feeding
1.3.6.1.4.1.21111.1.2.14.19ScalarsolarCfgSilenceBuzzerread-writecurrentSetting this object to Enable/disable silence buzzer or open buzzer
1.3.6.1.4.1.21111.1.2.14.20ScalarsolarCfgBuzzerInStandbyread-writecurrentSetting this object to Enable/disable buzzer audible in standby mode
1.3.6.1.4.1.21111.1.2.14.21ScalarsolarCfgAutoRestartread-writecurrentEnable/disable auto-Restart. (for hybrid)
1.3.6.1.4.1.21111.1.2.14.22ScalarsolarCfgBatMAudibleWarnread-writecurrentEnable/disable battery mode audible warning (for hybrid)
1.3.6.1.4.1.21111.1.2.14.23ScalarsolarCfgBatOpenCheckread-writecurrentEnable/disable battery open status check (for hybrid)
1.3.6.1.4.1.21111.1.2.14.24ScalarsolarCfgSiteFaultDetectread-writecurrentEnable/disable Site fault detect (for hybrid)
1.3.6.1.4.1.21111.1.2.14.25ScalarsolarCfgHotStandbyMSread-writecurrentHot standby master/slave PEM means master, PDM means slave (for hybrid)
1.3.6.1.4.1.21111.1.2.14.26ScalarsolarCfgBatDpDischgProtread-writecurrentEnable/disable battery deep discharge protect (for hybrid)
1.3.6.1.4.1.21111.1.2.14.27ScalarsolarCfgBatLowDischgProtread-writecurrentEnable/disable battery low protect (if disable, the battery will discharge to 6V) (for hybrid)
1.3.6.1.4.1.21111.1.2.14.28ScalarsolarCfgCodeStartread-writecurrentEnable/disable code start (for hybrid)
1.3.6.1.4.1.21111.1.2.14.29ScalarsolarCfgBypassForbidread-writecurrentEnable/disable bypass forbidding (for hybrid)
1.3.6.1.4.1.21111.1.2.14.30ScalarsolarCfgBypassWhenOffread-writecurrentEnable/disable bypass when device turn off. (for hybrid)
1.3.6.1.4.1.21111.1.2.14.31ScalarsolarCfgShortRestart3read-writecurrentEnable/disable short restart 3 times (for hybrid)
1.3.6.1.4.1.21111.1.2.14.32ScalarsolarCfgShortClearread-writecurrentEnable/disable inverter short clear function (for hybrid)
1.3.6.1.4.1.21111.1.2.14.33ScalarsolarCfgMaxChargeVolread-writecurrentMax floating charging voltage (for hybrid)
1.3.6.1.4.1.21111.1.2.14.34ScalarsolarCfgMaxChargeCurrread-writecurrentMax floating charging current (for hybrid)
1.3.6.1.4.1.21111.1.2.14.35ScalarsolarCfgChargingEnableread-writecurrentEnable/disable charging on grid mode (for hybrid)
1.3.6.1.4.1.21111.1.2.15NodesolarTraps
1.3.6.1.4.1.21111.1.2.15.1NodecmpPVFailurePV fail
1.3.6.1.4.1.21111.1.2.15.2NodecmpAutoAdjustFailureAuto adjust processing
1.3.6.1.4.1.21111.1.2.15.3NodecmpExFlashFailureExternal flash fail
1.3.6.1.4.1.21111.1.2.15.4NodecmpPVLossFailurePV loss
1.3.6.1.4.1.21111.1.2.15.5NodecmpPVLowFailurePV low
1.3.6.1.4.1.21111.1.2.15.6NodecmpLandingFailureIslanding detect
1.3.6.1.4.1.21111.1.2.15.7NodecmpInitialFailureInitial fail
1.3.6.1.4.1.21111.1.2.15.8NodecmpGridVolHLossFailureGrid voltage high loss
1.3.6.1.4.1.21111.1.2.15.9NodecmpGridVolLLossFailureGrid voltage low loss
1.3.6.1.4.1.21111.1.2.15.10NodecmpGridFreqHLossFailureGrid frequency high loss
1.3.6.1.4.1.21111.1.2.15.11NodecmpGridFreqLLossFailureGrid frequency low loss
1.3.6.1.4.1.21111.1.2.15.12NodecmpFeedVolOverFailureFeeding average voltage over
1.3.6.1.4.1.21111.1.2.15.13NodecmpGetEnergyFGridWarnget energy from the grid
1.3.6.1.4.1.21111.1.2.15.14NodecmpEPOActiveWarnEPO active
1.3.6.1.4.1.21111.1.2.15.15NodecmpBusOverVolFailBus over voltage
1.3.6.1.4.1.21111.1.2.15.16NodecmpBusUnderVolFailBus under voltage
1.3.6.1.4.1.21111.1.2.15.17NodecmpBusSoftStartTimeOutBus soft start time out
1.3.6.1.4.1.21111.1.2.15.18NodecmpInverterStartTimeOutInverter soft start time out
1.3.6.1.4.1.21111.1.2.15.19NodecmpInverterShortInverter short
1.3.6.1.4.1.21111.1.2.15.20NodecmpPVOverTemperatureOver temperature
1.3.6.1.4.1.21111.1.2.15.21NodecmpPVRelayFaultRelay fault
1.3.6.1.4.1.21111.1.2.15.22NodecmpDCCurrentFailDC current fail
1.3.6.1.4.1.21111.1.2.15.23NodecmpPVHighVolFailPV high voltage
1.3.6.1.4.1.21111.1.2.15.24NodecmpPVPowerDownPower down
1.3.6.1.4.1.21111.1.2.15.25NodecmpPVInputShortFailPV input short
1.3.6.1.4.1.21111.1.2.15.26NodecmpPVGFCIOverFailGFCI over
1.3.6.1.4.1.21111.1.2.15.27NodecmpPVIsolationLowPV isolation low
1.3.6.1.4.1.21111.1.2.15.28NodecmpInverterDCCurrOverInverter DC current over
1.3.6.1.4.1.21111.1.2.15.29NodecmpMCUDSPLineFailLine value consistent fail between MCU & DSP
1.3.6.1.4.1.21111.1.2.15.30NodecmpPVGFCISensorFailGFCI sensor fail
1.3.6.1.4.1.21111.1.2.15.31NodecmpMCUDSPConnectFailConnect fail between MCU & DSP
1.3.6.1.4.1.21111.1.2.15.32NodecmpMCUDSPCommuicateFailCommunication fail between MCU & DSP
1.3.6.1.4.1.21111.1.2.15.33NodecmpPVGroundLossFailGround loss
1.3.6.1.4.1.21111.1.2.15.34NodecmpPVPowerOnModePower On Mode
1.3.6.1.4.1.21111.1.2.15.35NodecmpPVStandbyModeStandby Mode
1.3.6.1.4.1.21111.1.2.15.36NodecmpPVBypassModeBypass Mode
1.3.6.1.4.1.21111.1.2.15.37NodecmpPVLineModeLine Mode
1.3.6.1.4.1.21111.1.2.15.38NodecmpPVBatteryModeBattery Mode
1.3.6.1.4.1.21111.1.2.15.39NodecmpPVBatteryTestModeBattery Test Mode
1.3.6.1.4.1.21111.1.2.15.40NodecmpPVFaultModeFault Mode
1.3.6.1.4.1.21111.1.2.15.41NodecmpPVShutdownModeShutdown Mode
1.3.6.1.4.1.21111.1.2.15.42NodecmpPVGridModeGrid mode
1.3.6.1.4.1.21111.1.2.15.43NodecmpPVOtherModeother solar inverter mode
1.3.6.1.4.1.21111.1.2.15.44NodecmpPVChargeModeCharge mode
1.3.6.1.4.1.21111.1.2.15.45NodecmpPVBatteryUnderBattery under
1.3.6.1.4.1.21111.1.2.15.46NodecmpPVBatteryLowBattery low
1.3.6.1.4.1.21111.1.2.15.47NodecmpPVBatteryOpenBattery open
1.3.6.1.4.1.21111.1.2.15.48NodecmpPVBatDischatgeLowBattery discharge low
1.3.6.1.4.1.21111.1.2.15.49NodecmpPVOverLowOver low
1.3.6.1.4.1.21111.1.2.15.130NodecmpPVChAbnormal1EMD Channels 1 Abnormal
1.3.6.1.4.1.21111.1.2.15.131NodecmpPVChAbnormal2EMD Channels 2 Abnormal
1.3.6.1.4.1.21111.1.2.15.132NodecmpPVChAbnormal3EMD Channels 3 Abnormal
1.3.6.1.4.1.21111.1.2.15.133NodecmpPVChAbnormal4EMD Channels 4 Abnormal
1.3.6.1.4.1.21111.1.2.15.134NodecmpPVChAbnormal5EMD Channels 5 Abnormal: smoke alarm
1.3.6.1.4.1.21111.1.2.15.135NodecmpPVChAbnormal6EMD Channels 6 Abnormal
1.3.6.1.4.1.21111.1.2.15.136NodecmpPVChAbnormal7EMD Channels 7 Abnormal
1.3.6.1.4.1.21111.1.2.15.137NodecmpPVChAbnormal8EMD Channels 8 Abnormal
1.3.6.1.4.1.21111.1.2.15.998ScalarSolartrapfaultnodev1v2not-accessiblecurrentThe share trap-node for send fault traps
1.3.6.1.4.1.21111.1.2.15.999ScalarSolartrapleafnodev1v2not-accessiblecurrentThe share trap-node for send all warn traps
1.3.6.1.4.1.21111.1.2.16NodesolarExtend
1.3.6.1.4.1.21111.1.2.16.1ScalarsolarExWorkTemperatureread-onlycurrentThe temperature of work environment
1.3.6.1.4.1.21111.1.2.16.2ScalarsolarExWorkhumidityread-onlycurrentThe humidity of work environment
1.3.6.1.4.1.21111.1.2.16.3ScalarsolarExSmokeScoperead-onlycurrentThe smokeScope of work environment
1.3.6.1.4.1.21111.1.2.16.4ScalarsolarExEMDAlarm1read-onlycurrentEnvironment detector alarm 1
1.3.6.1.4.1.21111.1.2.16.5ScalarsolarExEMDAlarm2read-onlycurrentEnvironment detector alarm 2
1.3.6.1.4.1.21111.1.2.16.6ScalarsolarExEMDAlarm3read-onlycurrentEnvironment detector alarm 3
1.3.6.1.4.1.21111.1.2.16.7ScalarsolarExEMDAlarm4read-onlycurrentEnvironment detector alarm 4
1.3.6.1.4.1.21111.1.3Nodecharger
1.3.6.1.4.1.21111.1.4Nodeats
1.3.6.1.4.1.21111.1.4.1NodeatsIdent
1.3.6.1.4.1.21111.1.4.1.1ScalarATSIdManufacturerread-onlymandatoryThe name of the solar manufacturer.
1.3.6.1.4.1.21111.1.4.1.2ScalarATSIdProtocolread-onlymandatoryThe solar Protocol id.
1.3.6.1.4.1.21111.1.4.1.3ScalarATSIdModelNameread-onlymandatoryThe ATS Model designation.
1.3.6.1.4.1.21111.1.4.1.4ScalarATSIdSerialNumberread-onlymandatoryThe ATS serial no.
1.3.6.1.4.1.21111.1.4.1.5ScalarATSIdNameread-writemandatoryA string identifying the ATS. This object should be set by the administrator.
1.3.6.1.4.1.21111.1.4.1.6ScalarATSIdFWVersionread-onlymandatoryMain CPU firmware version.
1.3.6.1.4.1.21111.1.4.1.7ScalarATSIdATSTyperead-onlymandatoryATS type.
1.3.6.1.4.1.21111.1.4.2NodeatsRating
1.3.6.1.4.1.21111.1.4.2.1ScalarATSRatOutVoltageread-onlycurrentThe rating output voltage of ATS
1.3.6.1.4.1.21111.1.4.2.2ScalarATSRatOutCurrentread-onlycurrentThe rating output current of ATS
1.3.6.1.4.1.21111.1.4.2.3ScalarATSRatOutFrequencyread-onlycurrentThe rating output frequency of ATS
1.3.6.1.4.1.21111.1.4.3NodeatsInformation
1.3.6.1.4.1.21111.1.4.3.1ScalarATSInfoSource1InVolread-onlycurrentThe source 1 input voltage of ATS
1.3.6.1.4.1.21111.1.4.3.2ScalarATSInfoSource1Freqread-onlycurrentThe source 1 frequency of ATS
1.3.6.1.4.1.21111.1.4.3.3ScalarATSInfoSource2InVolread-onlycurrentThe source 2 input voltage of ATS
1.3.6.1.4.1.21111.1.4.3.4ScalarATSInfoSource2Freqread-onlycurrentThe source 2 frequency of ATS
1.3.6.1.4.1.21111.1.4.3.5ScalarATSInfoOutputLoadread-onlycurrentLoad percentage
1.3.6.1.4.1.21111.1.4.3.6ScalarATSInfoOutputCurrentread-onlycurrentThe output current of the ATS system
1.3.6.1.4.1.21111.1.4.3.7ScalarATSInfoSynchronAngleread-onlycurrentThe Synchron Angle of the ATS system
1.3.6.1.4.1.21111.1.4.3.8ScalarATSInfoTemperatureread-onlycurrentThe Internal temperature of the ATS system
1.3.6.1.4.1.21111.1.4.4NodeatsControl
1.3.6.1.4.1.21111.1.4.5NodeatsAgentConfig
1.3.6.1.4.1.21111.1.4.5.1ScalarATSAgentDatetimeread-writecurrentThe datetime in agent, format is (MM/DD/YYYY hh:mm:ss)
1.3.6.1.4.1.21111.1.4.6NodeatsCommConfig
1.3.6.1.4.1.21111.1.4.6.1ScalarATSCommBaudRateread-writecurrentThe ATS communicate baudrate
1.3.6.1.4.1.21111.1.4.6.2ScalarATSCommDatabitsread-writecurrentThe ATS communicate data bits
1.3.6.1.4.1.21111.1.4.6.3ScalarATSCommStopbitsread-writecurrentThe ATS communicate stop bits
1.3.6.1.4.1.21111.1.4.6.4ScalarATSCommParityread-writecurrentThe ATS communicate Parity
1.3.6.1.4.1.21111.1.4.6.5ScalarATSCommTimeoutread-writecurrentThe ATS communicate timeout
1.3.6.1.4.1.21111.1.4.7NodeatsConfig
1.3.6.1.4.1.21111.1.4.7.1ScalarATSCfgSource1VolHLossread-writecurrentSet source1 voltage high loss
1.3.6.1.4.1.21111.1.4.7.2ScalarATSCfgSource1VolHBackread-writecurrentSet source1 voltage high back
1.3.6.1.4.1.21111.1.4.7.3ScalarATSCfgSource1VolLLossread-writecurrentSet source1 voltage low loss
1.3.6.1.4.1.21111.1.4.7.4ScalarATSCfgSource1VolLBackread-writecurrentSet source1 voltage low back
1.3.6.1.4.1.21111.1.4.7.5ScalarATSCfgSource1FreqHLossread-writecurrentSet source1 frequency high loss
1.3.6.1.4.1.21111.1.4.7.6ScalarATSCfgSource1FreqHBackread-writecurrentSet source1 frequency high back
1.3.6.1.4.1.21111.1.4.7.7ScalarATSCfgSource1FreqLLossread-writecurrentSet source1 frequency low loss
1.3.6.1.4.1.21111.1.4.7.8ScalarATSCfgSource1FreqLBackread-writecurrentSet source1 frequency low back
1.3.6.1.4.1.21111.1.4.7.9ScalarATSCfgSource2VolHLossread-writecurrentSet source2 voltage high loss
1.3.6.1.4.1.21111.1.4.7.10ScalarATSCfgSource2VolHBackread-writecurrentSet source2 voltage high back
1.3.6.1.4.1.21111.1.4.7.11ScalarATSCfgSource2VolLLossread-writecurrentSet source2 voltage low loss
1.3.6.1.4.1.21111.1.4.7.12ScalarATSCfgSource2VolLBackread-writecurrentSet source2 voltage low back
1.3.6.1.4.1.21111.1.4.7.13ScalarATSCfgSource2FreqHLossread-writecurrentSet source2 frequency high loss
1.3.6.1.4.1.21111.1.4.7.14ScalarATSCfgSource2FreqHBackread-writecurrentSet source2 frequency high back
1.3.6.1.4.1.21111.1.4.7.15ScalarATSCfgSource2FreqLLossread-writecurrentSet source2 frequency low loss
1.3.6.1.4.1.21111.1.4.7.16ScalarATSCfgSource2FreqLBackread-writecurrentSet source2 frequency low back
1.3.6.1.4.1.21111.1.4.7.17ScalarATSCfgOverLoadAlarmPointread-writecurrentSet over load alarm point
1.3.6.1.4.1.21111.1.4.7.18ScalarATSCfgOverLoadFaultPointread-writecurrentSet over load fault point
1.3.6.1.4.1.21111.1.4.7.19ScalarATSCfgAcceptablePhasesread-writecurrentSet acceptable phases
1.3.6.1.4.1.21111.1.4.7.20ScalarATSCfgBreakingTimeread-writecurrentSet breaking time
1.3.6.1.4.1.21111.1.4.7.21ScalarATSCfgBlankingTimeread-writecurrentSet blanking time
1.3.6.1.4.1.21111.1.4.8NodeatsTraps
1.3.6.1.4.1.21111.1.4.8.1NodecmpATSSourceS1VolBadSource S1 Voltage rms bad
1.3.6.1.4.1.21111.1.4.8.2NodecmpATSSourceS1FreqBadSource S1 frequency bad
1.3.6.1.4.1.21111.1.4.8.3NodecmpATSSourceS1WaveBadSource S1 wave bad
1.3.6.1.4.1.21111.1.4.8.4NodecmpATSSourceS2VolBadSource S2 Voltage rms bad
1.3.6.1.4.1.21111.1.4.8.5NodecmpATSSourceS2FreqBadSource S2 frequency bad
1.3.6.1.4.1.21111.1.4.8.6NodecmpATSSourceS2WaveBadSource S2 wave bad
1.3.6.1.4.1.21111.1.4.8.7NodecmpATSOnSourceS2On Source S2
1.3.6.1.4.1.21111.1.4.8.8NodecmpATSOnSourceS1On Source S1
1.3.6.1.4.1.21111.1.4.8.9NodecmpATSSourceS2PreferredSource S2 Preferred Source
1.3.6.1.4.1.21111.1.4.8.10NodecmpATSSynchronBadSynchron bad
1.3.6.1.4.1.21111.1.4.8.11NodecmpATSAuxPower1FailAux. Power1 failure
1.3.6.1.4.1.21111.1.4.8.12NodecmpATSAuxPower2FailAux. Power2 failure
1.3.6.1.4.1.21111.1.4.8.13NodecmpATSShortFaultShort fault
1.3.6.1.4.1.21111.1.4.8.14NodecmpATSOverloadFaultOverload fault
1.3.6.1.4.1.21111.1.4.8.15NodecmpATSOverloadAlarmOverload Alarm
1.3.6.1.4.1.21111.1.4.8.16NodecmpATSOnFaultModeOn fault mode
1.3.6.1.4.1.21111.1.4.8.130NodecmpATSChAbnormal1EMD Channels 1 Abnormal
1.3.6.1.4.1.21111.1.4.8.131NodecmpATSChAbnormal2EMD Channels 2 Abnormal
1.3.6.1.4.1.21111.1.4.8.132NodecmpATSChAbnormal3EMD Channels 3 Abnormal
1.3.6.1.4.1.21111.1.4.8.133NodecmpATSChAbnormal4EMD Channels 4 Abnormal
1.3.6.1.4.1.21111.1.4.8.134NodecmpATSChAbnormal5EMD Channels 5 Abnormal: smoke alarm
1.3.6.1.4.1.21111.1.4.8.135NodecmpATSChAbnormal6EMD Channels 6 Abnormal
1.3.6.1.4.1.21111.1.4.8.136NodecmpATSChAbnormal7EMD Channels 7 Abnormal
1.3.6.1.4.1.21111.1.4.8.137NodecmpATSChAbnormal8EMD Channels 8 Abnormal
1.3.6.1.4.1.21111.1.4.8.999ScalarATStrapleafnodev1v2not-accessiblecurrentThe share trap-node for send all traps
1.3.6.1.4.1.21111.1.4.9NodeatsExtend
1.3.6.1.4.1.21111.1.4.9.1ScalarATSExWorkTemperatureread-onlycurrentThe temperature of work environment
1.3.6.1.4.1.21111.1.4.9.2ScalarATSExWorkhumidityread-onlycurrentThe humidity of work environment
1.3.6.1.4.1.21111.1.4.9.3ScalarATSExSmokeScoperead-onlycurrentThe smokeScope of work environment
1.3.6.1.4.1.21111.1.4.9.4ScalarATSExEMDAlarm1read-onlycurrentEnvironment detector alarm 1
1.3.6.1.4.1.21111.1.4.9.5ScalarATSExEMDAlarm2read-onlycurrentEnvironment detector alarm 2
1.3.6.1.4.1.21111.1.4.9.6ScalarATSExEMDAlarm3read-onlycurrentEnvironment detector alarm 3
1.3.6.1.4.1.21111.1.4.9.7ScalarATSExEMDAlarm4read-onlycurrentEnvironment detector alarm 4