This MIB module defines MIB objects which provide mechanisms for remote management capabilities of Tripplite PowerAlert and related software.
Imported Objects
RFC-1215TRAP-TYPE
SNMPv2-CONFNOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIGauge32 Integer32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-IDENTITY OBJECT-TYPE
SNMPv2-TCAutonomousType DateAndTime DisplayString RowStatus TimeInterval TimeStamp TruthValue VariablePointer
TRIPPLITEtripplite
UPS-MIBNonNegativeInteger PositiveInteger
OIDNameAccessStatusDescription
1.3.6.1.4.1.850.2NodetlEnumerations
1.3.6.1.4.1.850.2.1NodetlOperatingSystems
1.3.6.1.4.1.850.2.1.1Nodehpux9
1.3.6.1.4.1.850.2.1.2Nodesunos4
1.3.6.1.4.1.850.2.1.3Nodesolaris
1.3.6.1.4.1.850.2.1.4Nodeosf
1.3.6.1.4.1.850.2.1.5Nodeultrix
1.3.6.1.4.1.850.2.1.6Nodehpux10
1.3.6.1.4.1.850.2.1.7Nodenetbsd1
1.3.6.1.4.1.850.2.1.8Nodefreebsd
1.3.6.1.4.1.850.2.1.9Nodeirix
1.3.6.1.4.1.850.2.1.10Nodelinux
1.3.6.1.4.1.850.2.1.11Nodebsdi
1.3.6.1.4.1.850.2.1.12Nodeopenbsd
1.3.6.1.4.1.850.2.1.13Nodewin32
1.3.6.1.4.1.850.2.1.14Nodehpux11
1.3.6.1.4.1.850.2.1.50Nodewin9x
1.3.6.1.4.1.850.2.1.51Nodewinnt
1.3.6.1.4.1.850.2.1.52Nodesolspark
1.3.6.1.4.1.850.2.1.53Nodesolintel
1.3.6.1.4.1.850.2.1.54Nodeaix
1.3.6.1.4.1.850.2.1.55Nodesco
1.3.6.1.4.1.850.2.1.56Nodeosx
1.3.6.1.4.1.850.2.1.255Nodeunknown
1.3.6.1.4.1.850.20NodetlConformance
1.3.6.1.4.1.850.20.1NodetlCompliances
1.3.6.1.4.1.850.20.2NodetlGroups
1.3.6.1.4.1.850.20.2.1NodetlSubsetGroups
1.3.6.1.4.1.850.20.2.2NodetlBasicGroups
1.3.6.1.4.1.850.20.2.3NodetlFullGroups
1.3.6.1.4.1.850.20.2.3.100NodetlUpsFullGroups
1.3.6.1.4.1.850.20.2.3.100.1GrouptlUpsFullIdentGroupcurrentThe tlUpsFullIdentGroup defines objects which are common to the Ident group of fully compliant Tripplite UPS's
1.3.6.1.4.1.850.20.2.3.100.2GrouptlUpsFullBatteryGroupcurrentThe tlUpsFullBatteryGroup defines objects which are common to the Battery group of fully compliant Tripplite UPS's
1.3.6.1.4.1.850.20.2.3.100.6NodetlUpsFullAlarmGroup
1.3.6.1.4.1.850.20.2.3.100.6.1GrouptlUpsFullAlarmObjsGroupcurrentThe tlUpsFullAlarmObjsGroup defines objects which are common to the Alarm group of fully compliant Tripplite UPS's
1.3.6.1.4.1.850.20.2.3.100.7GrouptlUpsFullTestGroupcurrentThe tlUpsFullTestGroup defines objects which are common to the Test group of fully compliant Tripplite UPS's
1.3.6.1.4.1.850.20.2.3.100.8GrouptlUpsFullControlGroupcurrentThe tlUpsFullControlGroup defines objects which are common to the Control group of fully compliant Tripplite UPS's
1.3.6.1.4.1.850.20.2.3.100.9GrouptlUpsFullConfigGroupcurrentThe tlUpsFullConfigGroup defines objects which are common to the Config group of fully compliant Tripplite UPS's
1.3.6.1.4.1.850.20.2.3.100.10GrouptlUpsFullOutletGroupcurrentThe tlUpsFullOutletGroup defines objects which are common to the Outlet group of fully compliant Tripplite UPS's
1.3.6.1.4.1.850.90IdentitytlPowerAlertThis MIB module defines MIB objects which provide mechanisms for remote management capabilities of Tripplite PowerAlert and related software.
1.3.6.1.4.1.850.90.1NodetlPASystem
1.3.6.1.4.1.850.90.1.1NodetlPAContacts
1.3.6.1.4.1.850.90.1.1.1NodetlPAEmailContacts
1.3.6.1.4.1.850.90.1.1.1.1ScalartlPANumberOfEmailContactsread-onlycurrentThe number email contacts currently defined.
1.3.6.1.4.1.850.90.1.1.1.2TabletlPAEmailContactsTablenot-accessiblecurrentA list email contact entries. The number of entries is given by the value of tlPANumberOfEmailContacts.
1.3.6.1.4.1.850.90.1.1.1.2.1RowtlPAEmailContactEntrynot-accessiblecurrentAn entry containing email contacts information.
1.3.6.1.4.1.850.90.1.1.1.2.1.1ColumntlPAEmailContactIndexread-onlycurrentThis is the index number of the email contact.
1.3.6.1.4.1.850.90.1.1.1.2.1.2ColumntlPAEmailContactRowStatusread-writecurrentThe row status for the tlPAEmailContactTable row
1.3.6.1.4.1.850.90.1.1.1.2.1.3ColumntlPAEmailContactNameread-writecurrentThe name of the email contact.
1.3.6.1.4.1.850.90.1.1.1.2.1.4ColumntlPAEmailContactAddressread-writecurrentThe address of the email contact.
1.3.6.1.4.1.850.90.1.1.2NodetlPASnmpContacts
1.3.6.1.4.1.850.90.1.1.2.1ScalartlPANumberOfSnmpContactsread-onlycurrentThe number SNMP contacts currently defined.
1.3.6.1.4.1.850.90.1.1.2.2TabletlPASnmpContactsTablenot-accessiblecurrentA list SNMP contact entries. The number of entries is given by the value of tlPANumberOfSnmpContacts.
1.3.6.1.4.1.850.90.1.1.2.2.1RowtlPASnmpContactEntrynot-accessiblecurrentAn entry containing SNMP contacts information.
1.3.6.1.4.1.850.90.1.1.2.2.1.1ColumntlPASnmpContactIndexread-onlycurrentThis is the index number of this SNMP contact.
1.3.6.1.4.1.850.90.1.1.2.2.1.2ColumntlPASnmpContactRowStatusread-writecurrentThe row status for the tlPASnmpContactTable row
1.3.6.1.4.1.850.90.1.1.2.2.1.3ColumntlPASnmpContactNameread-writecurrentThe name of the SNMP contact.
1.3.6.1.4.1.850.90.1.1.2.2.1.4ColumntlPASnmpContactIpAddressread-writecurrentThe IP address of the SNMP contact.
1.3.6.1.4.1.850.90.1.1.2.2.1.5ColumntlPASnmpContactPortread-writecurrentThe port of the SNMP contact.
1.3.6.1.4.1.850.90.1.1.2.2.1.6ColumntlPASnmpContactSnmpVersionread-writecurrentThe SNMP contact version to use for sending traps.
1.3.6.1.4.1.850.90.1.1.2.2.1.7ColumntlPASnmpContactSecurityNameread-writecurrentThe SNMP contact security name.
1.3.6.1.4.1.850.90.1.1.2.2.1.8ColumntlPASnmpContactPrivPasswordread-writecurrentThe SNMP contact priv password to use for sending V3 traps.
1.3.6.1.4.1.850.90.1.1.2.2.1.9ColumntlPASnmpContactAuthPasswordread-writecurrentThe SNMP contact auth password to use for sending V3 traps.
1.3.6.1.4.1.850.100NodetlUPS
1.3.6.1.4.1.850.100.1NodetlUpsObjects
1.3.6.1.4.1.850.100.1.1NodetlUpsIdent
1.3.6.1.4.1.850.100.1.1.1ScalartlUpsIdentUpsSoftwareChecksumread-onlycurrentA checksum for the UPS software.
1.3.6.1.4.1.850.100.1.1.2ScalartlUpsIdentSerialNumread-onlycurrentSerial number for the UPS.
1.3.6.1.4.1.850.100.1.1.3ScalartlUpsIdentIDread-writecurrentA user-supplied ID for the UPS.
1.3.6.1.4.1.850.100.1.1.4ScalartlUpsSnmpCardSerialNumread-onlycurrentSerial number for the UPS.
1.3.6.1.4.1.850.100.1.1.5ScalartlUpsSelectedDeviceIDread-writecurrentThe device ID selected to be used for retrieving data for this mib. As the snmp web card has only one device, this is read only for it
1.3.6.1.4.1.850.100.1.1.6ScalartlUpsLocationread-writecurrentThe device location string.
1.3.6.1.4.1.850.100.1.2NodetlUpsBattery
1.3.6.1.4.1.850.100.1.2.1ScalartlUpsBatteryAgeread-onlycurrentThe age of the battery in years. This is equal to the current date minus tlConfigBattReplDate.
1.3.6.1.4.1.850.100.1.2.2ScalartlUpsTemperatureFread-onlycurrentThe temperature of the battery, in Farenheight degrees. This is calculated from upsBatteryTemperature, which is in Celsius degrees.
1.3.6.1.4.1.850.100.1.2.3ScalartlUpsExternalBatteryAgeread-onlycurrentThe age of external battery in years. This is equal to the current date minus tlConfigExternalBattReplDate.
1.3.6.1.4.1.850.100.1.3NodetlUpsInput
1.3.6.1.4.1.850.100.1.3.1ScalartlUpsInputNumVoltagesread-onlycurrentThe number of input voltages. Phase to phase or phase to neutral. This variable indicates the number of rows in the input table.
1.3.6.1.4.1.850.100.1.3.2TabletlUpsInputVoltageTablenot-accessiblecurrentA list of voltage input table entries. The number of entries is given by the value of tlUpsInputNumVoltages.
1.3.6.1.4.1.850.100.1.3.2.1RowtlUpsInputVoltageEntrynot-accessiblecurrentAn entry containing information applicable to a particular input voltage.
1.3.6.1.4.1.850.100.1.3.2.1.1ColumntlUpsInputVoltageIndexnot-accessiblecurrentThe input voltage identifier.
1.3.6.1.4.1.850.100.1.3.2.1.2ColumntlUpsInputVoltageTyperead-onlycurrentWhether voltage measured is phase to phase or phase to neutral.
1.3.6.1.4.1.850.100.1.3.2.1.3ColumntlUpsInputVoltageread-onlycurrentThe magnitude of the present input voltage. A value of 6553 indicates Unknown.
1.3.6.1.4.1.850.100.1.3.3ScalartlUpsInputSourceSelectread-writecurrentThe determination as to which of two AC input lines is designated as the primary input source. The other is designated as the secondary input source. This valu…
1.3.6.1.4.1.850.100.1.3.4ScalartlUpsPhaseImbalanceread-onlycurrentPercentage of imbalance of the 3 phases.
1.3.6.1.4.1.850.100.1.3.5ScalartlUpsInputSourceAvailabilityread-onlycurrentThe determination as to which of two AC input lines are available. The agent will return either inputSourceA(1) or inputSourceB(2) if only one line is availabl…
1.3.6.1.4.1.850.100.1.3.6ScalartlUpsInputSourceInUseread-onlycurrentThe determination as to which one of two AC input lines is in use.
1.3.6.1.4.1.850.100.1.3.7ScalartlUpsInputSourceTransitionCountread-onlycurrentThe number of times the device transitions between primary and secondary sources. Most devices are limied to 65533 transitions, after which the value will not …
1.3.6.1.4.1.850.100.1.4NodetlUpsOutput
1.3.6.1.4.1.850.100.1.4.5ScalartlUpsOutputPowerTotalread-onlycurrentThe power capacity of the device.
1.3.6.1.4.1.850.100.1.4.6ScalartlUpsOutputCircuitsread-onlycurrentThe number of output circuits. This variable indicates the number of rows in the output circuit table.
1.3.6.1.4.1.850.100.1.4.7TabletlUpsOutputCircuitTablenot-accessiblecurrentA list of output currents table entries. The number of entries is given by the value of tlUpsOutputNumCircuits.
1.3.6.1.4.1.850.100.1.4.7.1RowtlUpsOutputCircuitEntrynot-accessiblecurrentAn entry containing information applicable to a particular output circuit.
1.3.6.1.4.1.850.100.1.4.7.1.1ColumntlUpsOutputCircuitIndexnot-accessiblecurrentThe output circuit identifier.
1.3.6.1.4.1.850.100.1.4.7.1.2ColumntlUpsOutputCircuitStatusread-onlycurrentWhether the breaker is open or closed.
1.3.6.1.4.1.850.100.1.4.7.1.3ColumntlUpsOutputCircuitLoadCurrentread-onlycurrentThe magnitude of the present output current in tenths of an amp. A value of 65534 indicates Unknown.
1.3.6.1.4.1.850.100.1.4.7.1.4ColumntlUpsOutputCircuitVoltageread-onlycurrentThe magnitude of the present circuit voltage in tenths of an volt.
1.3.6.1.4.1.850.100.1.4.7.1.5ColumntlUpsOutputCircuitPowerread-onlycurrentThe magnitude of the present power in watts. tenths of an amp.
1.3.6.1.4.1.850.100.1.4.7.1.6ColumntlUpsOutputCircuitPowerFactorread-onlycurrentThe power factor of all receptacles in a given circuit as a %.
1.3.6.1.4.1.850.100.1.4.8ScalartlUpsAggregatePowerFactorread-onlycurrentThe aggregrate power factor of all phases.
1.3.6.1.4.1.850.100.1.6NodetlUpsAlarm
1.3.6.1.4.1.850.100.1.6.1ScalartlUpsAlarmsPresentread-onlycurrentThe present number of active alarm conditions.
1.3.6.1.4.1.850.100.1.6.2TabletlUpsAlarmTablenot-accessiblecurrentA list of alarm table entries.
1.3.6.1.4.1.850.100.1.6.2.1RowtlUpsAlarmEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.
1.3.6.1.4.1.850.100.1.6.2.1.1ColumntlUpsAlarmIdread-onlycurrentA unique identifier for an alarm condition.
1.3.6.1.4.1.850.100.1.6.2.1.2ColumntlUpsAlarmDescrread-onlycurrentA description of the alarm condition.
1.3.6.1.4.1.850.100.1.6.2.1.3ColumntlUpsAlarmTimeread-onlycurrentThe value of sysUpTime when the alarm condition was detected.
1.3.6.1.4.1.850.100.1.6.2.1.4ColumntlUpsAlarmDetailread-onlycurrentA textual description of the alarm condition.
1.3.6.1.4.1.850.100.1.6.2.1.5ColumntlUpsAlarmDeviceIdread-onlycurrentA numeric identifier for the device on which the alarm is active.
1.3.6.1.4.1.850.100.1.6.2.1.6ColumntlUpsAlarmDeviceNameread-onlycurrentA string identifier for the device on which the alarm is active.
1.3.6.1.4.1.850.100.1.6.2.1.7ColumntlUpsAlarmLocationread-onlycurrentThe location of the device on which the alarm is active.
1.3.6.1.4.1.850.100.1.6.2.1.8ColumntlUpsAlarmGroupread-onlycurrentThe category/group of this alarm.
1.3.6.1.4.1.850.100.1.6.2.1.9ColumntlUpsAlarmIpread-onlycurrentThe originating IP address associated with this alarm.
1.3.6.1.4.1.850.100.1.6.2.1.10ColumntlUpsAlarmMacread-onlycurrentThe originating mac address associated with this alarm.
1.3.6.1.4.1.850.100.1.6.3NodetlUpsWellKnownAlarms
1.3.6.1.4.1.850.100.1.6.3.1IdentitytlUpsAlarmPrimaryPowerOutagecurrentThe primary power source is not present.
1.3.6.1.4.1.850.100.1.6.3.2IdentitytlUpsAlarmSecondaryPowerOutagecurrentThe secondary power source is not present.
1.3.6.1.4.1.850.100.1.6.3.3IdentitytlUpsAlarmLoadLevelAboveThresholdcurrentThe load level is above the designated threshold.
1.3.6.1.4.1.850.100.1.6.3.4IdentitytlUpsAlarmOutputCurrentChangedcurrentThe output current changed from its last known value.
1.3.6.1.4.1.850.100.1.6.3.5IdentitytlUpsAlarmBatteryAgeAboveThresholdcurrentOne or more batteries have been determined to require replacement.
1.3.6.1.4.1.850.100.1.6.3.6IdentitytlUpsAlarmLoadOffcurrentThe load is off.
1.3.6.1.4.1.850.100.1.6.3.7IdentitytlUpsAlarmUserDefinedcurrentA user-defined event is in alarm.
1.3.6.1.4.1.850.100.1.6.3.8IdentitytlUpsAlarmBatteryBadcurrentOne or more batteries have been determined to require replacement.
1.3.6.1.4.1.850.100.1.6.3.9IdentitytlUpsAlarmOnBatterycurrentThe UPS is drawing power from the batteries.
1.3.6.1.4.1.850.100.1.6.3.10IdentitytlUpsAlarmLowBatterycurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
1.3.6.1.4.1.850.100.1.6.3.11IdentitytlUpsAlarmDepletedBatterycurrentThe UPS will be unable to sustain the present load when and if the utility power is lost.
1.3.6.1.4.1.850.100.1.6.3.12IdentitytlUpsAlarmTempBadcurrentA temperature is out of tolerance.
1.3.6.1.4.1.850.100.1.6.3.13IdentitytlUpsAlarmInputBadcurrentAn input condition is out of tolerance.
1.3.6.1.4.1.850.100.1.6.3.14IdentitytlUpsAlarmOutputBadcurrentAn output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.850.100.1.6.3.15IdentitytlUpsAlarmOutputOverloadcurrentThe output load exceeds the UPS output capacity.
1.3.6.1.4.1.850.100.1.6.3.16IdentitytlUpsAlarmOnBypasscurrentThe Bypass is presently engaged on the UPS.
1.3.6.1.4.1.850.100.1.6.3.17IdentitytlUpsAlarmBypassBadcurrentThe Bypass is out of tolerance.
1.3.6.1.4.1.850.100.1.6.3.18IdentitytlUpsAlarmOutputOffAsRequestedcurrentThe UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.4.1.850.100.1.6.3.19IdentitytlUpsAlarmUpsOffAsRequestedcurrentThe entire UPS has shutdown as commanded.
1.3.6.1.4.1.850.100.1.6.3.20IdentitytlUpsAlarmChargerFailedcurrentAn uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.4.1.850.100.1.6.3.21IdentitytlUpsAlarmUpsOutputOffcurrentThe output of the UPS is in the off state.
1.3.6.1.4.1.850.100.1.6.3.22IdentitytlUpsAlarmUpsSystemOffcurrentThe UPS system is in the off state.
1.3.6.1.4.1.850.100.1.6.3.23IdentitytlUpsAlarmFanFailurecurrentThe failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.850.100.1.6.3.24IdentitytlUpsAlarmFuseFailurecurrentThe failure of one or more fuses has been detected.
1.3.6.1.4.1.850.100.1.6.3.25IdentitytlUpsAlarmGeneralFaultcurrentA general fault in the UPS has been detected.
1.3.6.1.4.1.850.100.1.6.3.26IdentitytlUpsAlarmDiagnosticTestFailedcurrentThe result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.850.100.1.6.3.27IdentitytlUpsAlarmCommunicationsLostcurrentA problem has been encountered in the communications between the agent and the UPS.
1.3.6.1.4.1.850.100.1.6.3.28IdentitytlUpsAlarmAwaitingPowercurrentThe UPS output is off and the UPS is awaiting the return of input power.
1.3.6.1.4.1.850.100.1.6.3.29IdentitytlUpsAlarmShutdownPendingcurrentA upsShutdownAfterDelay countdown is underway.
1.3.6.1.4.1.850.100.1.6.3.30IdentitytlUpsAlarmShutdownImminentcurrentThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.
1.3.6.1.4.1.850.100.1.6.3.31IdentitytlUpsAlarmTestInProgresscurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.850.100.1.6.3.32IdentitytlUpsAlarmCircuitBreaker1OpencurrentCircuit breakers #1 is open.
1.3.6.1.4.1.850.100.1.6.3.33IdentitytlUpsAlarmCircuitBreaker2OpencurrentCircuit breakers #2 is open.
1.3.6.1.4.1.850.100.1.6.3.34IdentitytlUpsAlarmCircuitBreaker3OpencurrentCircuit breakers #3 is open.
1.3.6.1.4.1.850.100.1.6.3.35IdentitytlUpsAlarmCircuitBreaker4OpencurrentCircuit breakers #4 is open.
1.3.6.1.4.1.850.100.1.6.3.36IdentitytlUpsAlarmCircuitBreaker5OpencurrentCircuit breakers #5 is open.
1.3.6.1.4.1.850.100.1.6.3.37IdentitytlUpsAlarmCircuitBreaker6OpencurrentCircuit breakers #6 is open.
1.3.6.1.4.1.850.100.1.6.3.38IdentitytlUpsAlarmCircuitBreaker7OpencurrentCircuit breakers #7 is open.
1.3.6.1.4.1.850.100.1.6.3.39IdentitytlUpsAlarmCircuitBreaker8OpencurrentCircuit breakers #8 is open.
1.3.6.1.4.1.850.100.1.6.3.40IdentitytlUpsAlarmCurrent1AboveThresholdcurrentThe output current on line 1 exceeds load limits.
1.3.6.1.4.1.850.100.1.6.3.41IdentitytlUpsAlarmCurrent2AboveThresholdcurrentThe output current on line 2 exceeds load limits.
1.3.6.1.4.1.850.100.1.6.3.42IdentitytlUpsAlarmCurrent3AboveThresholdcurrentThe output current on line 3 exceeds load limits.
1.3.6.1.4.1.850.100.1.6.3.43IdentitytlUpsAlarmRuntimeBelowWarningLevelcurrentThe battery seconds remaining is below warning level.
1.3.6.1.4.1.850.100.1.6.3.44IdentitytlUpsAlarmBusStartVoltageLowcurrentThe inverter start up bus voltage is too low.
1.3.6.1.4.1.850.100.1.6.3.45IdentitytlUpsAlarmBusOverVoltagecurrentThe inverter bus voltage is too high.
1.3.6.1.4.1.850.100.1.6.3.46IdentitytlUpsAlarmBusUnderVoltagecurrentThe inverter bus voltage is too low.
1.3.6.1.4.1.850.100.1.6.3.47IdentitytlUpsAlarmBusVoltageUnbalancedcurrentThe inverter bus voltage is not balanced.
1.3.6.1.4.1.850.100.1.6.3.48IdentitytlUpsAlarmInverterSoftStartBadcurrentThe inverter bus voltage cannot reach desired voltage within a specified duration.
1.3.6.1.4.1.850.100.1.6.3.49IdentitytlUpsAlarmInverterOverVoltagecurrentThe inverter voltage is too high.
1.3.6.1.4.1.850.100.1.6.3.50IdentitytlUpsAlarmInverterUnderVoltagecurrentThe inverter voltage is too low.
1.3.6.1.4.1.850.100.1.6.3.51IdentitytlUpsAlarmInverterCircuitBadcurrentThe inverter output is shorted.
1.3.6.1.4.1.850.100.1.6.3.52IdentitytlUpsAlarmBatteryOverVoltagecurrentThe battery voltage is too high.
1.3.6.1.4.1.850.100.1.6.3.53IdentitytlUpsAlarmBatteryUnderVoltagecurrentThe battery voltage is too low.
1.3.6.1.4.1.850.100.1.6.3.54IdentitytlUpsAlarmSiteWiringFaultcurrentThe utility input wiring is faulty.
1.3.6.1.4.1.850.100.1.6.3.55IdentitytlUpsAlarmOverTemperatureProtectioncurrentThe over temperature protection is activated.
1.3.6.1.4.1.850.100.1.6.3.56IdentitytlUpsAlarmOverChargedcurrentThe UPS is over charged.
1.3.6.1.4.1.850.100.1.6.3.57IdentitytlUpsAlarmEPOActivecurrentThe EPO is currently activate.
1.3.6.1.4.1.850.100.1.6.3.58IdentitytlUpsAlarmBypassFrequencyBadcurrentThe bypass frequency is out of tolerance.
1.3.6.1.4.1.850.100.1.6.3.59IdentitytlUpsAlarmExternalSmartBatteryAgeAboveThresholdcurrentOne or more external smart batteries have been determined to require replacement.
1.3.6.1.4.1.850.100.1.6.3.60IdentitytlUpsAlarmExternalNonSmartBatteryAgeAboveThresholdcurrentOne or more external non-smart batteries have been determined to require replacement.
1.3.6.1.4.1.850.100.1.6.3.61IdentitytlUpsAlarmSmartBatteryCommLostcurrentCommunications with the smart batteries was lost.
1.3.6.1.4.1.850.100.1.6.3.62IdentitytlUpsAlarmSourceAOutagecurrentInput power source A is not present.
1.3.6.1.4.1.850.100.1.6.3.63IdentitytlUpsAlarmSourceBOutagecurrentInput power source B is not present.
1.3.6.1.4.1.850.100.1.6.3.64IdentitytlUpsAlarmWatchdogResetcurrentThe internal watchdog triggered a reset of the device.
1.3.6.1.4.1.850.100.1.6.7ScalartlUpsAlarmDevNameread-onlydeprecatedThe name of the device, tlDevName, corresponding to the device that is associated with this alarm.
1.3.6.1.4.1.850.100.1.6.8ScalartlUpsAlarmDevLocationread-onlydeprecatedThe location of the device, tlDevLocation, corresponding to the device that is associated with this alarm.
1.3.6.1.4.1.850.100.1.6.9ScalartlUpsAlarmCategoryread-onlydeprecatedThe category, tlDevEvtCategory, of this alarm.
1.3.6.1.4.1.850.100.1.7NodetlUpsTest
1.3.6.1.4.1.850.100.1.7.1ScalartlUpsTestDateread-onlycurrentThe date of the last self-test run on the ups, in the format YYYYMMDD.
1.3.6.1.4.1.850.100.1.7.2ScalartlUpsTestResultsDetailread-onlycurrentResult of the last self-test run on the ups.
1.3.6.1.4.1.850.100.1.8NodetlUpsControl
1.3.6.1.4.1.850.100.1.8.1ScalartlUpsWatchdogSupportedread-onlycurrentIndicates whether or not this UPS supports a watchdog reboot.
1.3.6.1.4.1.850.100.1.8.2ScalartlUpsWatchdogSecsBeforeRebootread-writecurrentThe maximum number of seconds that can expire between polls that the engine makes to the UPS for data. If this time runs out, then the UPS will cycle its outpu…
1.3.6.1.4.1.850.100.1.8.3NodetlUpsWellKnownControls
1.3.6.1.4.1.850.100.1.8.3.1ScalartlUpsControlSelfTestread-writecurrentSet to TRUE to initiate Self Test
1.3.6.1.4.1.850.100.1.8.3.2ScalartlUpsControlRampread-writecurrentSet to TRUE to initiate Ramp
1.3.6.1.4.1.850.100.1.8.3.3ScalartlUpsControlShedread-writecurrentSet to TRUE to initiate Shed
1.3.6.1.4.1.850.100.1.8.3.4ScalartlUpsControlUpsOnread-writecurrentSet to TRUE to turn UPS on
1.3.6.1.4.1.850.100.1.8.3.5ScalartlUpsControlUpsOffread-writecurrentSet to TRUE to turn UPS off
1.3.6.1.4.1.850.100.1.9NodetlUpsConfig
1.3.6.1.4.1.850.100.1.9.1ScalartlUpsConfigBattReplDateread-writecurrentThe date on which the battery was last replaced, in the format YYYYMMDD.
1.3.6.1.4.1.850.100.1.9.4ScalartlUpsConfigDisplayUnitsread-writecurrentSelects English or Metric display for all readings. This selection may not be available on all devices. Further, some devices may support this selection, but n…
1.3.6.1.4.1.850.100.1.9.5ScalartlUpsConfigExternalBattReplDateread-writecurrentThe date on which the external battery was last replaced, in the format YYYYMMDD.
1.3.6.1.4.1.850.100.1.10NodetlUpsOutlet
1.3.6.1.4.1.850.100.1.10.1ScalartlUpsOutletNumOutletsread-onlycurrentThe number of available Outlets in this device.
1.3.6.1.4.1.850.100.1.10.2TabletlUpsOutletTablenot-accessiblecurrentA list of all device Outlets for all devices.
1.3.6.1.4.1.850.100.1.10.2.1RowtlUpsOutletEntrynot-accessiblecurrentAn entry containing Outlet information applicable to a particular device managed by this agent.
1.3.6.1.4.1.850.100.1.10.2.1.1ColumntlUpsOutletIndexread-onlycurrentThis is the index number of this Outlet for the device indicated by tlDeviceIndex.
1.3.6.1.4.1.850.100.1.10.2.1.2ColumntlUpsOutletStateread-onlycurrentThe current state of the Outlet.
1.3.6.1.4.1.850.100.1.10.2.1.3ColumntlUpsOutletTyperead-onlycurrentThis is a bit field that indicates the type of this Outlet. When 0, the outlet is not controllable and has none of the other features indicated in the bit map.…
1.3.6.1.4.1.850.100.1.10.2.1.4ColumntlUpsOutletControlread-writecurrentControls the state of the Outlet.
1.3.6.1.4.1.850.100.1.10.2.1.5ColumntlUpsOutletNameread-writecurrentA string identifying the devices attached to the output(s) of the device.
1.3.6.1.4.1.850.100.1.10.2.1.6ColumntlUpsOutletRampActionread-writecurrentThe ramp action to take on the Outlet.
1.3.6.1.4.1.850.100.1.10.2.1.7ColumntlUpsOutletRampDataTyperead-writecurrentThe type of data associated with ramp action.
1.3.6.1.4.1.850.100.1.10.2.1.8ColumntlUpsOutletRampDataread-writecurrentThe data value associated with type of ramp data.
1.3.6.1.4.1.850.100.1.10.2.1.9ColumntlUpsOutletShedActionread-writecurrentThe shed action to take on the Outlet.
1.3.6.1.4.1.850.100.1.10.2.1.10ColumntlUpsOutletShedDataTyperead-writecurrentThe type of data associated with shed action.
1.3.6.1.4.1.850.100.1.10.2.1.11ColumntlUpsOutletShedDataread-writecurrentThe data value associated with type of shed data.
1.3.6.1.4.1.850.100.1.10.2.1.12ColumntlUpsOutletGroupNdxread-writecurrenttlUpsOutletGroupIndex of corresponding outlet group, or 0 if ungrouped.
1.3.6.1.4.1.850.100.1.10.2.1.13ColumntlUpsOutletCurrentread-onlycurrentThe value of this outlet's current, represented as 0.1A.
1.3.6.1.4.1.850.100.1.10.2.1.14ColumntlUpsOutletPowerread-onlycurrentThe value of this outlet's power in watts.
1.3.6.1.4.1.850.100.1.11NodetlUpsOutletGroup
1.3.6.1.4.1.850.100.1.11.1ScalartlUpsOutletNumOutletGroupsread-onlycurrentThe number of available Outlet Groups in this device.
1.3.6.1.4.1.850.100.1.11.2TabletlUpsOutletGroupTablenot-accessiblecurrentA list of device outlet group entries. The number of entries is given by the value of tlUpsOutletNumOutletGroups.
1.3.6.1.4.1.850.100.1.11.2.1RowtlUpsOutletGroupEntrynot-accessiblecurrentAn entry containing outlet group information applicable to a particular device managed by this agent
1.3.6.1.4.1.850.100.1.11.2.1.1ColumntlUpsOutletGroupIndexread-onlycurrentThis is the index number of this load group for the device.
1.3.6.1.4.1.850.100.1.11.2.1.2ColumntlUpsOutletGroupRowStatusread-writecurrentRow status for the tlUpsOutletGroupTable
1.3.6.1.4.1.850.100.1.11.2.1.3ColumntlUpsOutletGroupNameread-writecurrentThe name of this outlet group.
1.3.6.1.4.1.850.100.1.11.2.1.4ColumntlUpsOutletGroupDescread-writecurrentA description for this outlet group.
1.3.6.1.4.1.850.100.1.11.2.1.5ColumntlUpsOutletGroupStateread-onlycurrentThe current state of the outlet group.
1.3.6.1.4.1.850.100.1.11.2.1.6ColumntlUpsOutletGroupControlread-writecurrentControls the state of every outlet associated with the group.
1.3.6.1.4.1.850.100.1.12NodetlUpsMainOutlet
1.3.6.1.4.1.850.100.1.12.1ScalartlUpsMainOutletStateread-onlycurrentThe current state of the main output of the device.
1.3.6.1.4.1.850.100.1.12.2ScalartlUpsMainOutletControllableread-onlycurrentIndicates if this device has controllable outlets
1.3.6.1.4.1.850.100.1.12.3ScalartlUpsMainOutletControlread-writecurrentControls the state of the main outlet of the device.
1.3.6.1.4.1.850.100.1.13NodetlUpsEnvironment
1.3.6.1.4.1.850.100.1.13.1ScalartlUpsTemperatureread-onlycurrentThe ambient temperature. The measurement returned will either be in units of Celsius (C) or Fahrenheit (F) depending upon whether Metric or English was selecte…
1.3.6.1.4.1.850.100.2NodetlUpsTraps
1.3.6.1.4.1.850.100.2.3NotificationtlUpsTrapAlarmEntryAddedcurrentThis trap is sent each time an alarm is inserted into to the alarm table.
1.3.6.1.4.1.850.100.2.3NodetlUpsTrapAlarmEntryAddedV1This trap is sent each time an alarm is inserted into to the alarm table.
1.3.6.1.4.1.850.100.2.4NotificationtlUpsTrapAlarmEntryRemovedcurrentThis trap is sent each time an alarm is removed from the alarm table.
1.3.6.1.4.1.850.100.2.4NodetlUpsTrapAlarmEntryRemovedV1This trap is sent each time an alarm is removed from the alarm table.
1.3.6.1.4.1.850.100.2.5NotificationtlUpsTrapSystemStartupcurrentUsed to inform another entity of an engine's startup. The varbinds that follow are: OBJ1 = tlEngineType Obj1Value = The type of engine providing this data OBJ2…
1.3.6.1.4.1.850.100.2.6NotificationtlUpsTrapSystemShutdowncurrentUsed to inform another entity of an engine's startup. The varbinds that follow are: OBJ1 = tlEngineType Obj1Value = The type of engine providing this data OBJ2…
1.3.6.1.4.1.850.101NodetlEnviroSense
1.3.6.1.4.1.850.101.1NodetlEnvEnvironment
1.3.6.1.4.1.850.101.1.1NodetlEnvTemperatureData
1.3.6.1.4.1.850.101.1.1.1ScalartlEnvTemperatureCread-onlycurrentThe ambient temperature (C).
1.3.6.1.4.1.850.101.1.1.2ScalartlEnvTemperatureFread-onlycurrentThe ambient temperature (F).
1.3.6.1.4.1.850.101.1.1.3ScalartlEnvTemperatureLowLimitread-writecurrentThe lower alarm limit for ambient temperature (F).
1.3.6.1.4.1.850.101.1.1.4ScalartlEnvTemperatureHighLimitread-writecurrentThe upper alarm limit for ambient temperature (F).
1.3.6.1.4.1.850.101.1.1.5ScalartlEnvTemperatureInAlarmread-onlycurrentIndicates whether or not temperature is in alarm.
1.3.6.1.4.1.850.101.1.2NodetlEnvHumidityData
1.3.6.1.4.1.850.101.1.2.1ScalartlEnvHumidityread-onlycurrentThe ambient humidity (%).
1.3.6.1.4.1.850.101.1.2.2ScalartlEnvHumidityLowLimitread-writecurrentThe lower alarm limit for ambient humidity (%).
1.3.6.1.4.1.850.101.1.2.3ScalartlEnvHumidityHighLimitread-writecurrentThe upper alarm limit for ambient humidity (%).
1.3.6.1.4.1.850.101.1.2.4ScalartlEnvHumidityInAlarmread-onlycurrentIndicates whether or not humidity is in alarm.
1.3.6.1.4.1.850.101.2NodetlEnvContacts
1.3.6.1.4.1.850.101.2.1TabletlEnvContactTablenot-accessiblecurrentA table of contacts.
1.3.6.1.4.1.850.101.2.1.1RowtlEnvContactEntrynot-accessiblecurrentAn entry containing information applicable to a particular contact.
1.3.6.1.4.1.850.101.2.1.1.1ColumntlEnvContactIndexread-onlycurrentThe table row index for the contact.
1.3.6.1.4.1.850.101.2.1.1.2ColumntlEnvContactNameread-writecurrentThe name or description of the contact.
1.3.6.1.4.1.850.101.2.1.1.3ColumntlEnvContactStatusread-onlycurrentThe current status of the contact.
1.3.6.1.4.1.850.101.2.1.1.4ColumntlEnvContactConfigread-writecurrentThe configuration of the contact.
1.3.6.1.4.1.850.103NodetlCooling
1.3.6.1.4.1.850.103.1NodetlCoolingEnvironment
1.3.6.1.4.1.850.103.1.1NodetlCoolingIdent
1.3.6.1.4.1.850.103.1.1.1ScalartlCoolingModelread-onlycurrentThe model name for the AC Unit.
1.3.6.1.4.1.850.103.1.1.2ScalartlCoolingManufacturerread-onlycurrentThe manufacturer of the AC Unit.
1.3.6.1.4.1.850.103.1.1.3ScalartlCoolingSerialNumberread-onlycurrentThe serial number of the AC unit.
1.3.6.1.4.1.850.103.1.1.4ScalartlCoolingFirmwareVersionread-onlycurrentThe firmware version of the AC Unit.
1.3.6.1.4.1.850.103.1.1.5ScalartlCoolingHostSoftwareVersionread-onlycurrentThe hardware version of the AC unit.
1.3.6.1.4.1.850.103.1.1.6ScalartlCoolingNameread-writecurrentThe user defined name for the AC Unit.
1.3.6.1.4.1.850.103.1.1.7ScalartlCoolingLocationread-writecurrentThe user defined location of the AC Unit.
1.3.6.1.4.1.850.103.1.2NodetlCoolingStatus
1.3.6.1.4.1.850.103.1.2.1ScalartlCoolingCondOutletTempread-onlycurrentThe condenser outlet air stream temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits.
1.3.6.1.4.1.850.103.1.2.2ScalartlCoolingCondInletTempread-onlycurrentThe condenser inlet air stream temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits.
1.3.6.1.4.1.850.103.1.2.3ScalartlCoolingRefrigerantTempread-onlycurrentThe temperature of the refrigerant in the suction line. This is displayed in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplay…
1.3.6.1.4.1.850.103.1.2.4ScalartlCoolingEvapSurfaceTempread-onlycurrentThe surface temperature of the evaporator in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits.
1.3.6.1.4.1.850.103.1.2.5ScalartlCoolingSuctionPressureread-onlycurrentThe pressure of the compressor suction line in tenths of (Mpa/psi) depending on the value of tlCoolingDisplayUnits.
1.3.6.1.4.1.850.103.1.2.6ScalartlCoolingDischargePressureread-onlycurrentThe pressure of the compressor discharge line in tenths of (Mpa/psi) depending on the value of tlCoolingDisplayUnits.
1.3.6.1.4.1.850.103.1.2.7ScalartlCoolingEvapFanSpeedread-onlycurrentThe current speed of the evaporator fan.
1.3.6.1.4.1.850.103.1.2.8ScalartlCoolingCondFanSpeedread-onlycurrentThe current speed of the condenser fan.
1.3.6.1.4.1.850.103.1.2.9ScalartlCoolingCompFrequencyread-onlycurrentThe operating frequency of the compressor in tenths of Arms.
1.3.6.1.4.1.850.103.1.2.10ScalartlCoolingEEVPercentageread-onlycurrentThe opening percentage of the EEV.
1.3.6.1.4.1.850.103.1.2.11ScalartlCoolingUnitCurrentread-onlycurrentThe the total current draw of the unit in tenths of Arms.
1.3.6.1.4.1.850.103.1.2.12ScalartlCoolingFanCurrentread-onlycurrentThethe current draw of the Evaporator and Condenser fans in tents of Arms.
1.3.6.1.4.1.850.103.1.2.13ScalartlCoolingCompCurrentread-onlycurrentThe operating current of the compressor in Arms.
1.3.6.1.4.1.850.103.1.2.14ScalartlCoolingReturnAirTempread-onlycurrentThe return air temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits.
1.3.6.1.4.1.850.103.1.2.15ScalartlCoolingSuctionTempread-onlycurrentThe temperature of the compressor suction line in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits.
1.3.6.1.4.1.850.103.1.2.16ScalartlCoolingSupplyAirTempread-onlycurrentThe supply air temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits.
1.3.6.1.4.1.850.103.1.3NodetlCoolingRunTimes
1.3.6.1.4.1.850.103.1.3.1ScalartlCoolingAirFilterRunHoursread-onlycurrentTotal hours the air filter has been under operation.
1.3.6.1.4.1.850.103.1.3.2ScalartlCoolingEvapFanRunDaysread-onlycurrentTotal days the evaporator fan has been under operation.
1.3.6.1.4.1.850.103.1.3.3ScalartlCoolingCondFanRunDaysread-onlycurrentTotal days the condenser fan has been under operation.
1.3.6.1.4.1.850.103.1.3.4ScalartlCoolingCompressorRunDaysread-onlycurrentTotal days the compressor has been under operation.
1.3.6.1.4.1.850.103.1.3.5ScalartlCoolingCondPumpRunDaysread-onlycurrentTotal days the condensate pump has been under operation.
1.3.6.1.4.1.850.103.1.3.6ScalartlCoolingAtomizerRunDaysread-onlycurrentTotal days the atomizer has been under operation.
1.3.6.1.4.1.850.103.1.4NodetlCoolingConfig
1.3.6.1.4.1.850.103.1.4.1ScalartlCoolingOnOffread-writecurrentTurn the unit off or on.
1.3.6.1.4.1.850.103.1.4.2ScalartlCoolingSetPointTempread-writecurrentThe set point temperature the unit will control the temperature to in tenths of degrees in Celsius or Fahrenheit based upon tleCoolDisplayUnits.
1.3.6.1.4.1.850.103.1.4.3ScalartlCoolingAutoStartread-writecurrentSpecified if the unit should start automatically on power up.
1.3.6.1.4.1.850.103.1.4.4ScalartlCoolingFanSpeedOverrideread-writecurrentSpeed of evaporator fan set by the user.
1.3.6.1.4.1.850.103.1.4.5ScalartlCoolingControlTyperead-writecurrentWhich temperature to be used as a control point.
1.3.6.1.4.1.850.103.1.4.6ScalartlCoolingCurrentRemoteTempread-writecurrentThe external remote temperature in tenths of degrees in Celsius or Fahrenheit depending upon value of tlCoolingDisplayUnits
1.3.6.1.4.1.850.103.1.4.7ScalartlCoolingDisplayUnitsread-writecurrentSelects English or Metric display for all readings.
1.3.6.1.4.1.850.103.1.4.8ScalartlCoolingBeepOnKeyread-writecurrentIndicates if the display sounds a beep when a key is pressed.
1.3.6.1.4.1.850.103.1.4.9ScalartlCoolingOutputRelaySourceread-writecurrentThe alarm level that causes the ouput relay to activate.
1.3.6.1.4.1.850.103.1.4.10ScalartlCoolingOffOnLeakread-writecurrentIndicates if the unit should stop cooling when leak input is activated.
1.3.6.1.4.1.850.103.1.4.11ScalartlCoolingOffOnInputContactread-writecurrentIndicates if the unit should stop cooling when input contact is activated.
1.3.6.1.4.1.850.103.1.4.12ScalartlCoolingInputContactTyperead-writecurrentThe input contact type.
1.3.6.1.4.1.850.103.1.4.13ScalartlCoolingOutputRelayDefaultread-writecurrentType of contact to make when output relay is activated.
1.3.6.1.4.1.850.103.1.4.14ScalartlCoolingAirFilterIntervalread-writecurrentThe number of weeks before the air filter needs to be changed.
1.3.6.1.4.1.850.103.1.4.15ScalartlCoolingWaterLeakContactTyperead-writecurrentThe input contact type.
1.3.6.1.4.1.850.103.1.5NodetlCoolingThresholds
1.3.6.1.4.1.850.103.1.5.1ScalartlCoolingMaxAirFilterRunHoursread-writecurrentThe maximum interval for air filter run hours before warning is annunciated.
1.3.6.1.4.1.850.103.1.5.2ScalartlCoolingEnableAirFilterAlarmread-writecurrentWhen enabled indicated that an alarm should occur when the maximum number of air filter run hours has been exceeded.
1.3.6.1.4.1.850.103.1.5.3ScalartlCoolingMaxSupplyTempread-writecurrentMaximum allowed supply air temperature before firing an alarm.
1.3.6.1.4.1.850.103.1.5.4ScalartlCoolingMinSupplyTempread-writecurrentMinimum allowed supply air temperature allowed before firing an alarm.
1.3.6.1.4.1.850.103.1.5.5ScalartlCoolingTempDiffAlarmread-writecurrentMaximum allowed air temperature deviation from set allowed before firing an alarm.
1.3.6.1.4.1.850.103.1.5.6ScalartlCoolingMaxReturnAirTempread-writecurrentWhen enabled indicated that an alarm should occur when the maximum number of air filter run hours has been exceeded.
1.3.6.1.4.1.850.103.6NodetlCoolingAlarm
1.3.6.1.4.1.850.103.6.3NodetlCoolingWellKnownAlarms
1.3.6.1.4.1.850.103.6.3.1IdentitytlCoolingSupplyAirSensorFaultcurrentThe supply air sensor is in fault.
1.3.6.1.4.1.850.103.6.3.2IdentitytlCoolingReturnAirSensorFaultcurrentThe return air sensor is in fault.
1.3.6.1.4.1.850.103.6.3.3IdentitytlCoolingCondenserInletAirSensorFaultcurrentThe condenser inlet air sensor is in fault.
1.3.6.1.4.1.850.103.6.3.4IdentitytlCoolingCondenserOutletAirSensorFaultcurrentThe condenser outlet air sensor is in fault.
1.3.6.1.4.1.850.103.6.3.5IdentitytlCoolingSuctionTemperatureSensorFaultcurrentThe suction temperature sensor is in fault.
1.3.6.1.4.1.850.103.6.3.6IdentitytlCoolingEvaporatorTemperatureSensorFaultcurrentThe evaporator temperature sensor is in fault.
1.3.6.1.4.1.850.103.6.3.7IdentitytlCoolingAirFilterCloggedcurrentThe air filter is clogged.
1.3.6.1.4.1.850.103.6.3.8IdentitytlCoolingAirFilterRunHoursViolationcurrentThe air filter run hours was violated.
1.3.6.1.4.1.850.103.6.3.9IdentitytlCoolingSuctionPressureSensorFaultcurrentThe suction pressure sensor is in fault.
1.3.6.1.4.1.850.103.6.3.10IdentitytlCoolingInverterCommunicationsFaultcurrentThe inverter communications is in fault.
1.3.6.1.4.1.850.103.6.3.11IdentitytlCoolingRemoteShutdownViaInputContactcurrentA remote shutdown was triggerd by an input contact.
1.3.6.1.4.1.850.103.6.3.12IdentitytlCoolingCondensatePumpFaultcurrentThe condensate pump is in fault.
1.3.6.1.4.1.850.103.6.3.13IdentitytlCoolingLowRefrigerantStartupFaultcurrentThe low refrigerant startup is in fault.
1.3.6.1.4.1.850.103.6.3.14IdentitytlCoolingCondenserFanFaultcurrentThe condenser fan is in fault.
1.3.6.1.4.1.850.103.6.3.15IdentitytlCoolingCondenserFailurecurrentThe condenser has failed.
1.3.6.1.4.1.850.103.6.3.16IdentitytlCoolingEvaporatorCoolingFailurecurrentThe evaporator cooling is in fault.
1.3.6.1.4.1.850.103.6.3.17IdentitytlCoolingReturnAirTempHighcurrentThe return air temperature is high.
1.3.6.1.4.1.850.103.6.3.18IdentitytlCoolingSupplyAirTempHighcurrentThe supply air temperature is high.
1.3.6.1.4.1.850.103.6.3.19IdentitytlCoolingEvaporatorFailurecurrentThe evaporator has failed.
1.3.6.1.4.1.850.103.6.3.20IdentitytlCoolingEvaporatorFreezeUpcurrentThe evaporator is frozen.
1.3.6.1.4.1.850.103.6.3.21IdentitytlCoolingDischargePressureHighcurrentThe discharge pressure is high.
1.3.6.1.4.1.850.103.6.3.22IdentitytlCoolingPressureGaugeFailurecurrentThe pressure gauge has failed.
1.3.6.1.4.1.850.103.6.3.23IdentitytlCoolingDischargePressurePersistentHighcurrentThe discharge pressure is persistently high.
1.3.6.1.4.1.850.103.6.3.24IdentitytlCoolingSuctionPressureLowStartFailurecurrentCannot start due to low suction pressure.
1.3.6.1.4.1.850.103.6.3.25IdentitytlCoolingSuctionPressureLowcurrentThe suction pressure is low.
1.3.6.1.4.1.850.103.6.3.26IdentitytlCoolingSuctionPressurePersistentLowcurrentThe suction pressure is persistently low.
1.3.6.1.4.1.850.103.6.3.27IdentitytlCoolingStartupLinePressureImbalancecurrentThe startup line pressure is in imbalance.
1.3.6.1.4.1.850.103.6.3.28IdentitytlCoolingCompressorFailurecurrentThe compressor has failed.
1.3.6.1.4.1.850.103.6.3.29IdentitytlCoolingCurrentLimitcurrentThe current is out of range.
1.3.6.1.4.1.850.103.6.3.30IdentitytlCoolingWaterLeakcurrentWater is leaking.
1.3.6.1.4.1.850.103.6.3.31IdentitytlCoolingFanUnderCurrentcurrentThe fan is under current.
1.3.6.1.4.1.850.103.6.3.32IdentitytlCoolingFanOverCurrentcurrentThe fan is over current.
1.3.6.1.4.1.850.103.6.3.33IdentitytlCoolingDischargePressureSensorFaultcurrentThe discharge pressure sensor is in fault.
1.3.6.1.4.1.850.103.6.3.34IdentitytlCoolingWaterFullcurrentWater is Full.
1.3.6.1.4.1.850.103.6.3.35IdentitytlCoolingAutoCoolingOncurrentAutomatic cooling was activated to lower the temperature below the remote set point.
1.3.6.1.4.1.850.103.6.3.36IdentitytlCoolingPowerButtonPressedcurrentPower button was pressed on the front panel.
1.3.6.1.4.1.850.103.6.3.37IdentitytlCoolingDisconnectedFromDevicecurrentThe device communications is disconnected.
1.3.6.1.4.1.850.104NodetlSrCoolNet
1.3.6.1.4.1.850.104.1NodetlSrCoolNetData
1.3.6.1.4.1.850.104.1.1NodetlSrCoolNetIdent
1.3.6.1.4.1.850.104.1.1.1ScalartlSrCoolNetModelread-onlycurrentThe model name for the device attached to the SRCOOLNET.
1.3.6.1.4.1.850.104.1.1.2ScalartlSrCoolNetManufacturerread-onlycurrentThe manufacturer of the AC Unit.
1.3.6.1.4.1.850.104.1.1.3ScalartlSrCoolNetSerialNumberread-onlycurrentThe serial number of the SRCOOLNET device.
1.3.6.1.4.1.850.104.1.1.4ScalartlSrCoolNetHostSoftwareVersionread-onlycurrentThe software version of the SRCOOLNET device.
1.3.6.1.4.1.850.104.1.1.5ScalartlSrCoolNetNameread-writecurrentThe user defined name for the AC Unit.
1.3.6.1.4.1.850.104.1.1.6ScalartlSrCoolNetLocationread-writecurrentThe user defined location of the AC Unit.
1.3.6.1.4.1.850.104.1.2NodetlSrCoolNetStatus
1.3.6.1.4.1.850.104.1.2.1ScalartlSrCoolNetModeread-onlycurrentThe current mode of SRCOOLNET.
1.3.6.1.4.1.850.104.1.2.2ScalartlSrCoolNetFanSpeedread-onlycurrentThe current speed of the fan.
1.3.6.1.4.1.850.104.1.2.3ScalartlSrCoolNetReturnAirTempread-onlycurrentThe return air stream temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlSrCoolNetDisplayUnits.
1.3.6.1.4.1.850.104.1.2.4ScalartlSrCoolNetWaterFullread-onlycurrentIndicates the water reservoir is full or not full.
1.3.6.1.4.1.850.104.1.2.5ScalartlSrCoolNetCurrentRemoteTempread-onlycurrentThe EnviroSense temperature in tenths of degrees in Celsius or Fahrenheit depending upon value of tlSrCoolNetDisplayUnits. Only available if EnviroSense is con…
1.3.6.1.4.1.850.104.1.2.6ScalartlSrCoolNetDisplayUnitsread-onlycurrentSelects English or Metric display for all readings. AC unit must be manually configured to match this setting.
1.3.6.1.4.1.850.104.1.3NodetlSrCoolNetConfig
1.3.6.1.4.1.850.104.1.3.1ScalartlSrCoolNetOnOffread-writecurrentTurn the unit off or on.
1.3.6.1.4.1.850.104.1.3.2ScalartlSrCoolSetModeread-writecurrentSet the operating mode of cooling unit. Unit must be ON to set mode.
1.3.6.1.4.1.850.104.1.3.3ScalartlSrCoolNetSetPointTempread-writecurrentThe local set point temperature in tenths of degrees in Celsius or Fahrenheit based upon tlSrCoolNetDisplayUnits.
1.3.6.1.4.1.850.104.1.3.4ScalartlSrCoolNetRemoteSetPointTempread-writecurrentThe remote set point temperature in tenths of degrees in Celsius or Fahrenheit based upon tlSrCoolNetDisplayUnits. Only available when EnviroSense is connected…
1.3.6.1.4.1.850.104.1.3.5ScalartlSrCoolNetFanSpeedSettingread-writecurrentSet the fan speed of the AC unit.
1.3.6.1.4.1.850.104.1.3.6ScalartlSrCoolNetRemoteSetpointEnableread-writecurrentUse remote temperature setpoint for control point versus return air temp. Only available when EnviroSense is connected to SRCOOLNET.
1.3.6.1.4.1.850.104.1.3.7ScalartlSrCoolNetFanAlwaysOnread-writecurrentLeave fans on when not cooling. Only available when EnviroSense is connected to SRCOOLNET.
1.3.6.1.4.1.850.104.2NodetlSrCoolNetAlarm
1.3.6.1.4.1.850.104.2.1NodetlSrCoolNetWellKnownAlarms
1.3.6.1.4.1.850.104.2.1.1IdentitytlSrCoolNetWaterFullAlarmcurrentWater reservoir full.