MIB Viewer

agnSensorsStatus

OBJECT-TYPE
1.3.6.1.4.1.164.6.2.28
Access
read-only
Status
current
Sub-identifiers
0
This entry specifies the Sensors (Temperature sensors or others) existence and status. Each sensor will be represented by 2 bits, where the first bit (right) will specify the existence: (0= Not exist, 1=exist), and the left bit will specify it's status (0= OK, 1=FAIL), so for each sensor: 00 - sensor does not exist 01 - sensor exists and status is OK 11 - sensor exists and status is not OK ( e.g. temperature exceeds pre-defined threshold) bits 0-1 are for first sensor bits 2-3 are for 2nd sensor (if exists) and so on... Bit 0 is the LSB.
OCTET STRING