MIB Viewer

airFMSysCompMinOnTime

OBJECT-TYPE
1.3.6.1.4.1.318.1.1.13.1.4.5.1
Access
read-write
Status
mandatory
Sub-identifiers
0
Set the minimum time the compressor continues to operate after it is started. The delay protects the compressor from damage. Caution: Reducing this delay shortens compressor life. Measured in seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.
INTEGER