airFMSysHumDeadband

OBJECT-TYPE
1.3.6.1.4.1.318.1.1.13.1.4.6.4
Access
read-write
Status
mandatory
Sub-identifiers
0
The humidity range that controls output when the selected control sensor humidity is below the setpoint. At the top of this range, the humidification mode outputs at 100%. The deadband does not apply to PID-controlled modes. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.
INTEGER