MIB Viewer

batteryCriticalNotification

NOTIFICATION-TYPE
1.3.6.1.2.1.233.0.3
Status
current
Sub-identifiers
0
This notification can be generated when the current charge of the battery falls so low that it cannot provide a sufficient power supply function for regular operation of the powered device(s). The battery needs to be charged before it can be used for regular power supply again. The battery may still provide sufficient power for a 'sleep' mode of a powered device(s) or for a transition into an 'off' mode. If the critical state is caused by a single cell or a set of cells of the battery, then object batteryCellIdentifier should be set to a value that identifies the cell or set of cells. Otherwise, the value of object batteryCellIdentifier should be set to the empty string when this notification is generated. The notification should not be sent again for the same battery before either the battery charge has increased through charging to a non-critical value or an indication of a maintenance action has been detected, such as a battery disconnection event or a reinitialization of the battery monitoring system. This notification should not be sent when the battery is in a charging mode, i.e., the value of object batteryChargingOperState is charging(2).