MIB Viewer

batteryTemperatureNotification

NOTIFICATION-TYPE
1.3.6.1.2.1.233.0.4
Status
current
Sub-identifiers
0
This notification can be generated when the measured temperature (batteryTemperature) rises above the threshold defined by object batteryAlarmHighTemperature or falls below the threshold defined by object batteryAlarmLowTemperature. If the low or high temperature has been detected for a single cell or a set of cells of the battery and not for the entire battery, then object batteryCellIdentifier should be set to a value that identifies the cell or set of cells. Otherwise, the value of object batteryCellIdentifier should be set to the empty string when this notification is generated. It may occur that the temperature alternates between values slightly below and slightly above a threshold. For limiting the notification rate in such a case, this notification should not be sent again for the same battery or cell, respectively, within a time interval of 10 minutes. An exception to the rate limitations occurs immediately after the reinitialization of the battery monitoring system. At this point in time, if the battery temperature is above the threshold defined by object batteryAlarmHighTemperature or below the threshold defined by object batteryAlarmLowTemperature, respectively, then this notification should be sent, independent of the time at which previous notifications for the same battery or cell, respectively, had been sent.