MIB Viewer

cfgPsInvTestAutoStopTimer

OBJECT-TYPE
1.3.6.1.4.1.5802.1.3.1.2.2.2.2.1
Access
read-write
Status
current
Sub-identifiers
0
This MIB defines the maximum duration of a remote inverter test, in minutes. The transponder uses a default 15-minute period. When the timer reaches the end of the set period, the test stops automatically. Note that the internal Power Supply settings may stop the inverter test before this timer has expired. The DHT will also stop the Inverter test if the voltage of any battery drops below 10.875V. The value of this MIB is stored in non-volatile memory.
INTEGER (1..300)