cpqSiMonitorConditionDegraded

TRAP-TYPE
1.3.6.1.4.1.232.2003
Sub-identifiers
0
A fault reporting feature has exceeded normal limits for the monitor indicated by the cpqSiMonitorIndex. The monitor`s condition is degraded due to the internal temperature exceeding normal operating limits. The monitor is still useable, but action should be taken to return the condition to OK. User Action: Physically check for obstructions to air flow around the monitor. Check the thermostat in the room that the system occupies. Allow the monitor to cool by turning off the monitor for 5 minutes then turn the monitor back on. After the monitor cools, another alarm indicating an improving condition, such as Monitor OK, will be issued.