ePDUOutletConfigMonitoredNearOverloadThreshold

OBJECT-TYPE
1.3.6.1.4.1.3808.1.1.3.3.4.3.1.5
Access
read-write
Status
mandatory
Source
CPS-MIB
Sub-identifiers
0
A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in watts. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than the value returned by the ePDUOutletConfigMonitoredLowLoadThreshold OID. Maximum value must be less than or equal to the value returned by the ePDUOutletConfigMonitoredOverloadThreshold OID. 0 will be returned if the unit is not Outlet Monitored Rack PDU.