MIB Viewer

eoACPwrAttributesPowerAccuracy

OBJECT-TYPE
1.3.6.1.2.1.230.1.1.1.6
Access
read-only
Status
current
Sub-identifiers
0
This object indicates a percentage value, in hundredths of a percent, representing the presumed accuracy of active, reactive, and apparent power usage reporting. For example, 1010 means the reported usage is accurate to +/- 10.1 percent. This value is zero if the accuracy is unknown. ANSI and IEC define the following accuracy classes for power measurement: IEC 62053-22 & 60044-1 class 0.1, 0.2, 0.5, 1, & 3. ANSI C12.20 class 0.2 & 0.5
Integer32 (0..10000)