MIB Viewer

eoPowerNameplate

OBJECT-TYPE
1.3.6.1.2.1.229.1.2.1.2
Access
read-only
Status
current
Sub-identifiers
0
This object indicates the rated maximum consumption for the fully populated Energy Object. The nameplate power requirements are the maximum power numbers given in SI watts and, in almost all cases, are well above the expected operational consumption. Nameplate power is widely used for power provisioning. This value is specified in either units of watts or voltage and current. The units are therefore SI watts or equivalent Volt-Amperes with the magnitude (milliwatts, kilowatts, etc.) indicated separately in eoPowerUnitMultiplier.
Unsigned32