Reading this variable returns bit mask indicating which UPSs in a parallel system are alive. Management software should poll only these UPSs on their snmp branches 11-18 as follows: 1 FirstUPS alive 2 SecondUPS alive 4 ThirdUPS alive 8 FourthUPS alive 16 FifthUPS alive 32 SixthUPS alive 64 SeventhUPS alive 128 EigthUPS alive Since the management software should always monitor the GenericUPS branch (10), this value has no meaning for single upses (which provide values on that snmp branch), and should be set to zero in that case.
Integer32