MIB Viewer

inputControlUnitInputConfiguration

OBJECT-TYPE
1.3.6.1.4.1.12148.10.11.2.1.7
Access
read-write
Status
current
Source
SP2-MIB
Sub-identifiers
0
Configuration of the input type. Configurations available for different controllers are as follows: SP2 Basic(normally open, normally closed); SP2 BasicInd(normally open,normally closed, temperature, temp 4-20mA, voltage); Compack inputs 1-4(clock, virtual),inputs 5-7(normally open,normally closed, temperature, temp 4-20mA, voltage, clock); SmartpackS inputs 1-4(clock, virtual), inputs 5-8(normally open,normally closed,voltage,temperature,temp 4-20mA), inputs 9-10(normally open,normally closed,voltage); Smartpack R inputs 1-6(normally open,normally closed,diode matrix,clock, voltage),inputs 7-10(clock, virtual).
INTEGER { normallyOpen (1), normallyClosed (2), diodeMatrix (3), voltage (4), clock (5), virtual (6), temperature (7), temp4-20mA (8) }