MIB Viewer

lgpEnvConfigBmsResetTimer

OBJECT-TYPE
1.3.6.1.4.1.476.1.42.3.4.4.36
Access
read-write
Status
current
Sub-identifiers
0
The current count-down time for a BMS to continue controlling the fan speed. If this value reaches 0, then the condition lgpConditionBmsResetTimerExpired will be generated. If a BMS wants to continue controlling the fan speed, it must reset this timer. Typical values range from 0 to 120 minutes (actual valid ranges may differ from unit to unit).
Unsigned32