lgpPwrMeasBatteryCabinet

OBJECT-IDENTITY
1.3.6.1.4.1.476.1.42.3.5.2.1.10
Status
current
Sub-identifiers
0
This sub-tree is used to register the voltage between the most negative and the most postive terminals of a battery cabinet. To determine the cabinet being described in a multi-cabinet system, this point implements an additional two indexes. The first index describes the module the cabinet is located in. The second index describes the cabinet number. In an SMS(Single-Module System) the first index is always 1. Example: lgpPwrMeasBatteryCabinet.2.4 'lgpPwrMeasBatteryCabinet' = Point is a battery cabinet. '.2' = Cabinet is in the second module. '.4' = Cabinet number 4