lgpPwrStateUpsModuleRedundantCount

OBJECT-TYPE
1.3.6.1.4.1.476.1.42.3.5.3.41.2
Access
read-only
Status
current
Sub-identifiers
0
Number of redundant UPS modules in the system. In a single module system, the value is zero. This value is dependent upon the present load and the number of modules (i.e. the value may change during normal operation based upon a load change). This value represents the number of extra modules above the minimum needed to support the load.