mtrapinfoBmEventId
OBJECT-TYPE
1.3.6.1.4.1.3808.2.2.6
Description
Allow CPS traps with an integer argument for providing detail information about Battery Manager specific event identifier. Not being defined in the MIB, only reply 0. Known Specific Event ID: Battery Manager 0 - not used 1 - Alarm: The battery manager system fault. 2 - Info: Device configuration changed. 3 - Alarm: Probe configuration mismatched. 4 - Info: Probe configuration matched. 5 - Alarm: Communication with battery manager has been lost. 6 - Info: Communication with battery manager has been restored. 7 - Alarm: Communication with LCD has been lost. 8 - Info: Communication with LCD has been restored. 9 - Warning: Enter battery equalization active mode. 10- Warning: Leave battery equalization active mode. 11- Alarm: Battery equalizing has failed. 12- Info: Battery equalizing succeed. Known Specific Event ID: Battery Probes 101 - Alarm: Low battery voltage. 102 - Alarm: High battery voltage. 103 - Info: Battery voltage event has cleared. 104 - Alarm: Low battery temperature. 105 - Alarm: High battery temperature. 106 - Info: Battery temperature event has cleared. 107 - Alarm: Critical low battery resistance. 108 - Alarm: Critical high battery resistance. 109 - Warning: Low battery resistance. 110 - Warning: high battery resistance. 111 - Info: Battery resistance event has cleared. 112 - Alarm: Battery resistance health has crossed alarm threshold. 113 - Warning: Battery resistance health has crossed warning threshold. 114 - Info: Battery resistance health has returned to Normal.
Syntax
INTEGER