MIB Viewer

mtrapinfoBmEventId

OBJECT-TYPE
1.3.6.1.4.1.3808.2.2.6
Access
read-only
Status
mandatory
Source
CPS-MIB
Sub-identifiers
0
Allow CPS traps with an integer argument for providing detail information about Battery Manager specific event identifier. Not being defined in the MIB, only reply 0. Known Specific Event ID: Battery Manager 0 - not used 1 - Alarm: The battery manager system fault. 2 - Info: Device configuration changed. 3 - Alarm: Probe configuration mismatched. 4 - Info: Probe configuration matched. 5 - Alarm: Communication with battery manager has been lost. 6 - Info: Communication with battery manager has been restored. 7 - Alarm: Communication with LCD has been lost. 8 - Info: Communication with LCD has been restored. 9 - Warning: Enter battery equalization active mode. 10- Warning: Leave battery equalization active mode. 11- Alarm: Battery equalizing has failed. 12- Info: Battery equalizing succeed. Known Specific Event ID: Battery Probes 101 - Alarm: Low battery voltage. 102 - Alarm: High battery voltage. 103 - Info: Battery voltage event has cleared. 104 - Alarm: Low battery temperature. 105 - Alarm: High battery temperature. 106 - Info: Battery temperature event has cleared. 107 - Alarm: Critical low battery resistance. 108 - Alarm: Critical high battery resistance. 109 - Warning: Low battery resistance. 110 - Warning: high battery resistance. 111 - Info: Battery resistance event has cleared. 112 - Alarm: Battery resistance health has crossed alarm threshold. 113 - Warning: Battery resistance health has crossed warning threshold. 114 - Info: Battery resistance health has returned to Normal.
INTEGER