MIB Viewer

psStringDischargeCurrent

OBJECT-TYPE
1.3.6.1.4.1.5591.1.4.3.1.4
Access
read-only
Status
optional
Sub-identifiers
0
Scaled representation of battery string discharge current. This is an RMS value in 1/100 Amps.If multiple strings are installed but only one measurement sensor is used, this value represents the total battery discharge current. When batteries are being charged, this value will = 0. This item requires an entry in the properties MIB.
INTEGER ( 0..65535 )