Output current is reported by tlpAtsOutputCurrent, tlpAtsOutputCurrentMin and tlpAtsOutputCurrentMax. These values are all reported in hundredths (0.01A), which accommodates all models; however, on any given device the actual precision may vary. This value describes the actual precision, which can be used as a divisor against the output current values to obtain the true output current measurement. For example, if tlpAtsOutputCurrent reports 530 and tlpAtsDeviceOutputCurrentPrecision is tenths(1), then the actual output current is 5.3.
INTEGER { none(0), tenths(1), hundredths(2) }