The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than tlpUpsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to tlpUpsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).
INTEGER { unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4) }