MIB Viewer

upsAdvTestCalibrationResults

OBJECT-TYPE
1.3.6.1.4.1.318.1.1.1.7.2.6
Access
read-only
Status
mandatory
Sub-identifiers
0
The results of the last runtime calibration. Value ok(1) means a successful runtime calibration. Value invalidCalibration(2) indicates last calibration did not take place since the battery capacity was below 100%. Value calibrationInProgress(3) means a calibration is occurring now. Value refused(4) means the test was refused, it did not take place. Value aborted(5) indicates the test started but either someone cancelled it or the system encountered an error. Value pending(6) the test will commence shortly.
INTEGER { ok(1), invalidCalibration(2), calibrationInProgress(3), refused(4), aborted(5), pending(6) }