upsAutoRestart

OBJECT-TYPE
1.3.6.1.2.1.33.1.8.5
Access
read-write
Status
current
Source
UPS-MIB
Sub-identifiers
0
Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.
INTEGER { on(1), off(2) }