MIB Viewer

upsParameterSecondTable

OBJECT-TYPE
1.3.6.1.4.1.818.1.1.12.10.11
Access
not-accessible
Status
current
Sub-identifiers
1
A list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..16)): Read sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParametersRead <number> PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue <number> PDU-SET upsParametersWrite <number>
SEQUENCE OF UpsParameterSecondEntry