upsSmartConfigLowBatteryRunTime

OBJECT-TYPE
1.3.6.1.4.1.17420.1.1.2.5.2.8
Access
read-write
Status
mandatory
Sub-identifiers
0
The desired run time in seconds once the low battery condition is reached. Allowed values are 120, 300, 420, or 600 seconds. During this time the UPS will produce a constant warning tone which can not be disabled. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.
INTEGER