MIB Viewer

upsSmartConfigRatedOutputVoltage

OBJECT-TYPE
1.3.6.1.4.1.935.1.1.1.5.2.1
Access
read-write
Status
mandatory
Source
XPPC-MIB
Sub-identifiers
0
The nominal output voltage from the UPS in 1/10 VAC. Possible values are 1000, 1200, 2080, 2200, 2250, 2300 and 2400. NOTE: Only units that are 2200, 2250, 2300 and 2400 can be changed. Allowable values are 2200, 2250, 2300 and 2400. For these adjustable units, if a value other than a supported value is provided in a set request, the UPS interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used.
INTEGER